CV7300 Instruction Manual - TECO-Westinghouse Motor Company
CV7300 Instruction Manual - TECO-Westinghouse Motor Company
CV7300 Instruction Manual - TECO-Westinghouse Motor Company
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
1.1.2 During Power ON<br />
Danger<br />
Chapte 1 Safety Precautions<br />
Do not plug or unplug the connectors on the inverter when electrified to avoid the<br />
control panel damage resulting from erratic transition voltage surge due to contact<br />
bounce.<br />
When momentary power loss is longer than 2 seconds (the larger of horse power, the<br />
longer of time), the inverter does not have enough storage power to control the circuit;<br />
Therefore, when power is regenerated, the operation of the inverter is based on the<br />
setup of 1-00 / 2-05 and the condition of external switch, this is considered to be<br />
「restart」in the following paragraphs.<br />
When the momentary power loss is short, the inverter still has enough storage power<br />
to control the circuit. Therefore, when power is regenerated, the inverter will<br />
automatically restart depending on the setup of 2-00/2-01.<br />
When restart the inverter, the operation of the inverter is based on the setup of 1-00<br />
and 2-05 and the condition of external switch (FWD/REV button). Attention: the<br />
start operation is irrelevant with 2-00/2-01/2-02/2-03.<br />
1. When 1-00=0000, the inverter will not automatically run after restart.<br />
2. When 1-00=0001 and the external switch (FWD/REV button) is OFF, the inverter<br />
will not run after restart.<br />
3. When 1-00=0001, the external switch (FWD/REV button) is ON, and 2-05=0000,<br />
the inverter will run automatically after restart. Attention: In the sake of safety,<br />
please turn off the external switch (FWD/REV button) after power loss to avoid<br />
underling damage to the machine and the human body after sudden regeneration of<br />
power.<br />
To ensure the safety of people and machine, please refer to the description and<br />
suggestion of 2-05<br />
1.1.3 Before Operation<br />
Danger<br />
Make sure the model and capacity are the same as those set by 15-0.<br />
Caution<br />
The inverter will flash the power voltage set by 0-07 for 5 seconds when applying power.<br />
1-2