Chapter 3 Ambient Environment and Installation<br />

Power supply:<br />

Make sure the voltage applied is correct to avoid<br />

damaging the inverter.<br />

A molded-case circuit breaker must be installed<br />

between the AC source and the inverter<br />

Molded-case circuit breaker:<br />

Use a molded-case circuit breaker that conforms to<br />

the rated voltage and current of the inverter to<br />

control the power ON/OFF and protect the inverter.<br />

Do not use the inverter as the switch for run/stop<br />

switch.<br />

Leakage breaker:<br />

Install a leakage breaker to prevent error operation<br />

caused by electric leakage and to protect operators<br />

Setting current should be 200mA or above and the<br />

operating time at 0.1 second or longer to prevent<br />

malfunction.<br />

Magnetic contactor:<br />

Normal operations do not need a magnetic contactor.<br />

But a contactor has to be installed in primiary side<br />

when performing functions such as external control<br />

and auto restart after power failure, or when using<br />

brake controller.<br />

Do not use the magnetic contactor as the run/stop<br />

switch of the inverter.<br />

AC reactor for power improvement:<br />

When inverters below 200V/400V 15KW are<br />

supplied with high capacity (above 600KVA) power<br />

source or an AC reactor can be connected to<br />

improve the power performance.<br />

Input noise filter:<br />

A filter must be installed when there are inductive<br />

load around the inverter<br />

Inverter:<br />

Input power terminals L1, L2, and L3 can be used in<br />

any sequence regardless of phases.<br />

Output terminals T1, T2, and T3 are connected to U,<br />

V, and W terminals of the motor. If the motor is<br />

reversed while the inverter is forward, just swap any<br />

two terminals of T1, T2, and T3.<br />

To avoid damaging the inverter, do not connect the<br />

input terminals T1, T2, and T3 to AC power.<br />

Connect the ground terminal properly. 200 V series:<br />

class 3 grounding,