T6984, T7984<br />
are microprocessor-based thermostats that<br />
provide proportional-plus-integral individual room<br />
temperature control in zoned commercial Heating,<br />
Ventilation and Air Conditioning systems such as<br />
hydronic heating and/or cooling, pressure<br />
dependent VAV or by-pass box, with or<br />
without terminal reheat.<br />
<strong>Modulating</strong> <strong>Electronic</strong> <strong>Thermostats</strong> for Commercial Buildings<br />
The T6984 family provides floating SPST<br />
control. T7984 series provides modulating<br />
(2 to 10 Vdc analog) control. Optional features include<br />
automatic heat/cool changeover, reheat control, remote<br />
night setback with local timed override, and remote<br />
sensor on VAV models. Vertical or horizontal,<br />
they have an attractive appearance.
T6984, T7984 <strong>Modulating</strong> <strong>Electronic</strong> <strong>Thermostats</strong> for Commercial Buildings<br />
Features<br />
• PI control action provides accurate, stable room temperature control.<br />
• T6984 models are used with Series 60 direct-coupled damper actuators<br />
such as ML6161 or ML684, or with Series 60 valve actuators<br />
such as VC6930 or M6410.<br />
• T7984 models are used with Series 70 direct-coupled actuators such<br />
as ML7161 or ML7984, or with valve actuators such as ML7285,<br />
ML7421, ML7425, ML7474 or ML7475.<br />
• All models have user-friendly setpoint knob.<br />
• All models feature output status LEDs for installer check-out.<br />
• Locking cover and range stops are standard.<br />
• Night setback models provide selection of two different offset temperatures<br />
and use central time switch control.<br />
Model Specifications T6984:<br />
• Night setback models also feature 2 1/2 hr. local timed override.<br />
• Heat/cool models provide automatic changeover with 3° or 5°F<br />
(1.5 °or 3°C) selectable Zero Energy Band (Z.E.B.) to meet<br />
requirements of ASHRAE 90.1.<br />
• Heat/cool models have installer-definable setpoint at midpoint<br />
of Z.E.B., at heating setpoint, or at cooling setpoint.<br />
• Reheat models feature fast/slow response selection to match<br />
heating system dynamics<br />
• T6984 features selectable motor timing from 20 sec. to 7 min.<br />
• Horizontal or vertical formats.<br />
Setpoint Range: 55–90°F (13–32°C) – T6984A,C,E,T7984A<br />
Heating 55–75°F* (13–24°C) – T6984B,D,T7984B,C<br />
Cooling 75*–90°F (24–32°C) – T6984B,D,T7984B,C<br />
* The maximum heating setpoint and minimum cooling<br />
setpoint is electronically limited to 75°F(24°C).<br />
Accuracy: 1°F (0.4°C) Precision: ±1°F (0.4°C)<br />
Accessories: 272845 Remote Sensor (wall mounted); 272847<br />
Remote Sensor (duct mounted); 272846 Adapter Plate for<br />
2-gang NEMA or British 75 mm elect. box<br />
Model Specifications T7984:<br />
Model<br />
Stage 1<br />
(Cooling)<br />
Stage 1<br />
H/C C/O<br />
Reheat<br />
Output<br />
Night<br />
Setback<br />
Sensor<br />
Model<br />
Stage 1<br />
(Cooling)<br />
Stage 1<br />
H/C C/O<br />
Reheat<br />
Output<br />
Night<br />
Setback<br />
Sensor<br />
T6984A<br />
T6984B<br />
T6984C<br />
floating<br />
floating<br />
floating<br />
n/a<br />
n/a<br />
optional<br />
n/a<br />
on/off<br />
n/a<br />
n/a<br />
n/a<br />
n/a<br />
internal<br />
internal<br />
internal<br />
T7984A<br />
T7984B<br />
analog<br />
analog<br />
optional<br />
optional<br />
n/a<br />
on/off<br />
n/a<br />
remote<br />
internal<br />
internal<br />
T6984D<br />
T6984E<br />
floating<br />
floating<br />
optional<br />
optional<br />
on/off<br />
n/a<br />
remote<br />
n/a<br />
internal<br />
remote or<br />
internal<br />
T7984C<br />
analog<br />
optional<br />
analog<br />
remote<br />
remote or<br />
internal<br />
Installation Options T6984<br />
Installation Options T7984<br />
Perameter<br />
Motor Timing<br />
Selection<br />
20;30;60;90;120/150;240 or 420<br />
Model<br />
A B C D E<br />
• • • • •<br />
Perameter<br />
Night Setback<br />
Selection<br />
5°F (3°C) heat/cool offset,or 10°F(5°C) heat<br />
offset,20°F(11°C) cool offset<br />
Model<br />
A B C<br />
•<br />
Night Setback<br />
5°F (3°C) heat/cool offset, or 10°F<br />
(5°C) setback/cooling shutdown<br />
•<br />
Zero<br />
Energy Band<br />
3°F (1.5°C); or, 5°F (3°C)<br />
• •<br />
Zero<br />
Energy Band<br />
3°F (1.5°C); or, 5°F (3°C)<br />
• •<br />
Setpoint<br />
Definition<br />
Heating; Cooling or H/C midpoint<br />
• •<br />
Setpoint<br />
Definition<br />
Heating; Cooling or H/C midpoint<br />
• •<br />
Reheat Time<br />
Constant<br />
Fast (7.5 min.);or Normal (15 min.)<br />
• •<br />
Reheat Time<br />
Constant<br />
Fast (7.5 min.);or Normal (15 min.)<br />
• •<br />
Main<br />
Sensor<br />
Remote or internal<br />
•<br />
Home and Building <strong>Control</strong><br />
<strong>Honeywell</strong> Inc.<br />
1985 Douglas Drive North<br />
Golden Valley, MN 55422<br />
<strong>Honeywell</strong> Limited<br />
155 Gordon Baker Road<br />
North York, ON M2H 3N7<br />
Helping You <strong>Control</strong> Your World<br />
6A1497 7/97