06.03.2026 Aufrufe

CrossBoard 800 A – for rear feeding V1.1.0 EN

CrossBoard 800 A – for rear feeding V1.1.0

CrossBoard 800 A – for rear feeding V1.1.0

MEHR ANZEIGEN
WENIGER ANZEIGEN

Verwandeln Sie Ihre PDFs in ePaper und steigern Sie Ihre Umsätze!

Nutzen Sie SEO-optimierte ePaper, starke Backlinks und multimediale Inhalte, um Ihre Produkte professionell zu präsentieren und Ihre Reichweite signifikant zu maximieren.

CrossBoard

THE GLOBAL

STANDARD

800 A

CrossBoard 800 A – for rear feeding

Fast

Completely pre-assembled out-of-thebox

power distribution system with a

rated current of 800 A (IEC/UL)

High-end

High short-circuit resistance

Hybrid

Hybrid busbar design for plug and clamp

connections on the same system

Plug-and-play

Plug-and-play assembly with CRITO rear

feeding and mounting modules

Safe

Consistent touch-safe protection IP20,

extendable to IP40

Space-saving

Space-saving on the front through rear

feed with CRITO

Further information at www.woehner.com


Further information at www.woehner.com

CrossBoard 2


Crossboard 800 A - for rear feeding

CrossBoard 3

basic system 800 A

connection module

11805 01065

poles 3-pole 3-pole

min. cross-section

max. cross-section

95 mm²

300 mm²

rated current (IEC) 800 A 800 A

rated voltage (IEC) AC 800 V 690 V

rated surge voltage U imp 6 kV 6 kV

rated peak withstand current I pk

max.

rated short-time withstand

current I cw (1.0 s) max.

80 kA 30 kA

40 kA

min. cross-section UL AWG 2

max. cross-section UL MCM 600

rated current (UL) 800 A 800 A

rated voltage (UL) AC 800 V 600 V

SCCR unprotected max.

40 kA

SCCR protected max. 100 100

SCCR (generiert)

100 kA with JDDZ fuse Class L/T 800 A / 600 V AC

65 kA with any DIVQ/7 circuit breaker 800 A / 480 V

AC

100 kA with JDDZ fuse Class L/T 800 A / 600 V AC

65 kA with any DIVQ/7 circuit breaker 800 A / 480 V

AC

degree of protection

front degree of protection

IP20

IP20

width 500 200

height 200 200

depth 45 65

These basic systems cannot be mounted directly.

The connection module 01065 and at least one mounting module 01067 must be mounted in the correct position on the mounting plate.

The CrossBoard is then plugged onto these modules.

other CrossBoard versions with identical electrical values:

Part No. Width

11806 600 mm

11807 700 mm

11808 800 mm

11809 900 mm

11810 1000 mm

11811 1100 mm

Further information at www.woehner.com


CrossBoard 4

Headquarters

Wöhner GmbH & Co. KG

Elektrotechnische Systeme

Mönchrödener Str. 10

96472 Rödental

Germany

www.woehner.com

Order hotline

+49 9563 751 161

order@woehner.de

Technical hotline

+49 9563 751 508

support@woehner.de

CrossBoard 800 A – for

rear feeding

V1.1.0 EN

Hurra! Ihre Datei wurde hochgeladen und ist bereit für die Veröffentlichung.