<strong>Expo</strong>-<strong>Telektron</strong> <strong>Mini<strong>Purge</strong></strong> Z purge Handbook ML 307 Issue A<br />

6.6.2 <strong>Purge</strong> air from Control Unit to pressurized enclosure.<br />

When the control unit is directly mounted onto the pressurized enclosure, no connection will<br />

C:\Main System Files\Marketing\Memo\ML307 ISSUE A.doc<br />

Page 6-3<br />

normally be necessary, as the purge air will discharge into the pressurized enclosure directly.<br />

When the control unit is not direct mounted, or where internal air distribution is necessary a<br />

connection should be made from the purge air outlet on the control unit (normally ½” NPT<br />

Female), via pipe pressure rated at least to the supply pressure, to the pressurized enclosure.<br />

This should be kept as short as possible and should be adequately sized to ensure that the full<br />

purge flow can be delivered.<br />

6.6.3 Control Unit to enclosure pressure monitor.<br />

When the control unit is directly mounted onto the pressurized enclosure, no connection will<br />

normally be necessary, as the enclosure pressure monitor point will sense directly inside the<br />

pressurized enclosure. Only if the control unit is not directly mounted or if there are fans, which<br />

may create, localized low-pressure areas within the pressurized enclosure is it necessary to<br />

pipe this connection. The connection is made to the enclosure pressure sensor fitting<br />

(normally 1/8” NPT Female) on the control unit. There is virtually no flow in this circuit so small<br />

bore tube may be used. <strong>Expo</strong>-<strong>Telektron</strong> recommends 6mm (¼”) bore tube. It is important that<br />

all connections are free of leaks.<br />

6.6.4 Control unit to flow sensor.<br />

For Continuous Flow CF systems this function is performed by the enclosure pressure sensor<br />

monitor connection. On Leakage Compensation LC systems this connection is made from the<br />

enclosure flow sensor fitting (normally 1/8” NPT Female) on the control unit, to the fitting<br />

(normally 1/8” NPT Female) on the Relief Valve (RLV). Tube and connections are all internal to<br />

the pressurized enclosure. Again, <strong>Expo</strong>-<strong>Telektron</strong> recommends 6mm (¼”) bore tube.<br />

6.6.5 Power supplies and their isolation<br />

All power entering the pressurized enclosure must be controlled manually by the user.<br />

Reference should be made to NFPA 496 or the relevant local codes.<br />