8<br />

9<br />

Error display : e38<br />

Is the outdoor<br />

air temperature thermistor<br />

connector connection<br />

OK?<br />

NO<br />

Repair<br />

YES<br />

Is the outdoor<br />

air temperature thermistor<br />

characteristics OK, is there<br />

no broken wire?<br />

YES<br />

NO<br />

Defective outdoor air<br />

temperature thermistor<br />

Replacement<br />

● Display conditions<br />

If the temperature sensed by the thermistor is –30ºC or lower continuously<br />

for 5 seconds between 2 minutes and 2 minutes 20 seconds after<br />

the compressor goes ON, the compressor stops. After a 3 minute delay,<br />

the compressor restarts. If this state is detected 3 times in 40 (60) minutes.<br />

Note (1) Values in ( ) show for the case of the 301~601 models.<br />

Error display : e39<br />

[Defective discharge pipe thermistor]<br />

Indoor unit<br />

Outdoor unit<br />

Red LED<br />

Stays OFF Red LED 1 time flash<br />

Green LED Keeps flashing Green LED Keeps flashing<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

Is the discharge<br />

pipe thermistor<br />

connector connection<br />

OK?<br />

NO<br />

Repair<br />

[Defective outdoor air temperature thermistor]<br />

Indoor unit<br />

Outdoor unit<br />

Red LED<br />

Stays OFF Red LED<br />

1 time flash<br />

Green LED Keeps flashing Green LED Keeps flashing<br />

Note (1) The green LED in the outdoor unit is used in the FDCA301 ~ 601 models only.<br />

YES<br />

Are the discharge<br />

pipe thermistor characteristics<br />

OK, is there no<br />

broken wire?<br />

Defective discharge pipe<br />

thermistor Replacement<br />

● Display conditions<br />

If the temperature sensed by the thermistor is –10ºC or lower continuously<br />

for 5 seconds between 10 minutes and 10 minutes 20<br />

seconds (2minutes and 2minutes 20seconds) after the compressor<br />

goes ON, the compressor stops. After a 3 minute delay, the compressor<br />

restarts. If this state is detected 3 times in 40 (60) minutes.<br />

Note (1) Values in ( ) show for the case of the 301~601 models.<br />

NO<br />

- 29 -<br />

YES<br />

Thermistor resistance (kΩ)[T 0°C<br />

0<br />

---50 0 50<br />

Temperature [T](°C)<br />

Defective outdoor unit control<br />

PCB Replacement (Defective<br />

discharge pipe thermistor<br />

input circuit)<br />

50<br />

Temperature-resistance<br />

characteristics of discharge<br />

pipe thermistor (ThO-D)<br />

T< 80°C<br />

T> 80°C<br />

0<br />

0 20 50 80 100 120<br />

Temperature [T] (°C)<br />

40<br />

30<br />

20<br />

10<br />

0<br />

10<br />

5<br />

0<br />

Thermistor resistance (kΩ)[T>0°C]<br />

Thermistor resistance (kΩ)[T > 80°C]