Belimo Project: 1100 Peachtree, Atlanta, Georgia<br />

<strong>Technical</strong> <strong>Documentation</strong><br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves <br />

(PICCV) Patented<br />

Effective December 2007


Control Valve Product Range<br />

2<br />

Electronic <strong>Pressure</strong> <strong>Independent</strong><br />

<strong>Characterized</strong> Control Valves <br />

U.S. Patent<br />

PICCV Two-way<br />

1/2” to 2”<br />

PICCV<br />

Service: Chilled/Hot Water,<br />

60% glycol<br />

Flow Rate: 0.5-100 GPM<br />

Material: Brass Body<br />

Brass/Stainless Trim<br />

Control: Floating<br />

Multi-Function Technology ®<br />

Spring Return or<br />

Non-Spring Return<br />

Typical Application<br />

Air Handling Units: – Heating Coils<br />

– Cooling Coils<br />

Unit Ventilators<br />

VAV Box Re-heat Coils<br />

Heat Pumps<br />

Electronic<br />

<strong>Characterized</strong> Control Valves <br />

U.S. Patent<br />

CCV<br />

B2… Series Two-way<br />

B3… Series Three-way<br />

Mixing/Diverting<br />

B6… Series Two-way Flanged<br />

1/2” to 3”<br />

Service: Chilled/Hot Water,<br />

60% glycol<br />

Cv Range: 0.3-240<br />

Material: Stainless Trim or<br />

Brass Trim<br />

Control: On/Off, Floating, 2-10 VDC<br />

Multi-Function Technology ®<br />

Spring Return or<br />

Non-Spring Return<br />

Typical Application<br />

Air Handling Units: – Heating Coils<br />

– Cooling Coils<br />

Fan Coil Units: – Heating Coils<br />

– Cooling Coils<br />

Unit Ventilators<br />

VAV Box Re-heat Coils<br />

Bypass Loops<br />

Electronic Zone Valves<br />

ZONE2…N Series Two-way NPT<br />

ZONE2…S Series Two-way Sweat<br />

ZONE3…N Series Three-way<br />

Diverting NPT<br />

ZONE3…S Series Three-way<br />

Diverting Sweat<br />

1/2” to 1”<br />

Service: Chilled/Hot Water,<br />

50% glycol<br />

C v Range: 1.0 - 8.0<br />

Material: Brass Body<br />

Control: On/Off<br />

Spring Return<br />

Typical Application<br />

Fan Coil Units: – Heating Coils<br />

– Cooling Coils<br />

Baseboard Radiation<br />

For detailed information and submittal data, see <strong>Technical</strong> <strong>Documentation</strong> at www.belimo.com or on CD-ROM.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Electronic Globe Valves<br />

G2…(S) Two-way Screwed<br />

Series Bronze or Stainless Trim<br />

G6…C (S) Two-way Flanged ANSI 125<br />

Series Bronze or Stainless Trim<br />

G6…(S) Two-way Flanged ANSI 125<br />

Series Bronze or Stainless Trim<br />

G6…(S)-250 Two-way Flanged ANSI 250<br />

Series Bronze or Stainless Trim<br />

G3…(D) Three-way Screwed<br />

Series Bronze Trim<br />

G7…D (S) Three-way Flanged<br />

Series ANSI 125 Bronze or<br />

Stainless Trim<br />

G7…D (S)-250 Three-way Flanged<br />

Series ANSI 250 Bronze or<br />

Stainless Trim<br />

Three-way Valves available in Mixing or Diverting<br />

1/2” to 6”<br />

Service: Chilled/Hot Water,<br />

60% Glycol, Steam<br />

Cv Range: 0.4-344 (Two-way)<br />

2.2-340 (Three-way Mix.)<br />

4.4-248 (Three-way Div.)<br />

Material: Stainless Steel Stem,<br />

Bronze Trim or<br />

Stainless Trim<br />

Control: On/Off, Floating, 2-10 VDC<br />

Multi-Function Technology ®<br />

Spring Return or<br />

Non-Spring Return<br />

Typical Application<br />

Air Handling Units: – Heating Coils<br />

– Cooling Coils<br />

Fan Coil Units: – Heating Coils<br />

– Cooling Coils<br />

Unit Ventilators<br />

VAV Box Re-heat Coils<br />

Bypass Loops<br />

Electronic Butterfly Valves<br />

F6… Series Two-way<br />

(HS,HSU)<br />

F7… Series Three-way<br />

(HS,HSU) Mixing/Diverting<br />

F6… SHP Two-way ANSI 150/300<br />

Series<br />

F7… SHP Three-way ANSI 150/300<br />

Series Mixing/Diverting<br />

Typical Application<br />

Chiller and Cooling Tower Isolation<br />

Change-over Systems<br />

Large Air Handler Coil Control<br />

Bypass Control Applications<br />

Control Valve Product Range<br />

B2… Two-way Screwed<br />

VS Series Stainless Steel Trim<br />

B3… Three-way Mixing/<br />

VS Series Diverting Screwed<br />

Stainless Steel Trim<br />

B2… Two-way Screwed<br />

VSS Series Stainless Steel Body<br />

and Trim<br />

B6… Two-way Flanged<br />

VS Series Stainless Steel Trim<br />

2” to 30” 1/2” to 10”<br />

Service: Chilled/Hot Water,<br />

50% Glycol<br />

Cv Range: 115-73,426<br />

Material: Stainless Shaft<br />

Stainless Disc<br />

Cast Iron, Full Lug Body<br />

EPDM Liner<br />

Control: On/Off, Floating,<br />

2-10 VDC<br />

On/Off, Floating<br />

2-10 VDC,<br />

1-5 VDC, 4-20mA<br />

(NEMA 4 Actuator)<br />

Multi-Function Technology ®<br />

Spring Return or<br />

Non-Spring Return<br />

For detailed information and submittal data, see <strong>Technical</strong> <strong>Documentation</strong><br />

at www.belimo.com or on CD-ROM.<br />

Electronic Ball Valves – VS Series<br />

Service: Chilled/Hot Water,<br />

50% Glycol, Steam<br />

Cv Range: 1 to 12,400<br />

Material: Bronze or Stainless Body<br />

Stainless Steel Trim<br />

RPTFE Seats<br />

Control: On/Off, Floating,<br />

2-10 VDC<br />

On/Off, Floating<br />

2-10 VDC,<br />

1-5 VDC, 4-20mA<br />

(NEMA 4 Actuator)<br />

Multi-Function Technology ®<br />

Spring Return or<br />

Non-Spring Return<br />

Typical Application<br />

Unit Ventilators<br />

Humidifiers<br />

Heating and Cooling Coils<br />

Call Customer Service to discuss<br />

your application.<br />

3


Valve/Actuator Selection At A Glance<br />

Base product nomenclature<br />

PICCV-15-003-PT + LRX24-MFT<br />

4<br />

VALVE ACTUATOR<br />

PICCV 15-003 –PT LRX24 - MFT<br />

VALVE SIZES<br />

Valve Designation Sizes<br />

PICCV 15 1/2”<br />

TYPE OF VALVE<br />

20 3/4”<br />

25 1”<br />

32 1-1/4”<br />

40 1-1/2”<br />

50 2”<br />

PRESSURE INDEPENDENT<br />

CHARACTERIZED CONTROL<br />

VALVE (PICCV)<br />

PICCV 2-way Chrome Plated<br />

Brass Ball & Brass Stem<br />

GPM Ex:<br />

003 = 3.0 GPM<br />

Description<br />

Non-Spring<br />

Return Actuator<br />

Spring<br />

Return Actuator<br />

–PT with P/T ports to measure<br />

delta P to verify the flow rate<br />

without P/T ports<br />

LR…<br />

AR…<br />

TF<br />

LF…<br />

AF…<br />

24 VAC/DC<br />

Power*<br />

Rotary<br />

Rotary<br />

DESIGNATOR DESCRIPTION<br />

–MFT Multi-Function<br />

Technology ® (MFT)<br />

2 – 10 VDC Control<br />

or Selectable<br />

(See MFT chart<br />

opposite)<br />

-3 Floating control<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Specify upon ordering<br />

P-10019+NO+AHU<br />

ORDERING EXAMPLE<br />

Valve/Actuator Selection At A Glance<br />

MFT CONFIGURATION SET-UP TAGGING<br />

1<br />

2<br />

P-10019 NO AHU<br />

Choose the desired valve/actuator combination<br />

based on valve ratings and actuator control<br />

parameters from the following pages. PICCV-15-003-PT + LRX24-MFT ●<br />

Specify Configuration (important)<br />

SET UP*<br />

Non-Spring Models<br />

NO = Normally Open<br />

NC = Normally Closed<br />

Spring Return Models<br />

NO/FO = Normally Open/Fail Open<br />

NO/FC = Normally Open/Fail Closed<br />

NC/FO = Normally Closed/Fail Open<br />

NC/FC = Normally Closed/Fail Closed<br />

*Refers to valve port inlet to outlet,<br />

per flow arrow designation<br />

Valve set up required<br />

prior to ordering.<br />

TAGGING<br />

Valves may be tagged per<br />

customer specification<br />

Example:<br />

AHU<br />

FCU-2<br />

Multi-Function Technology<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-10118 2-6 VDC 100 2-10 VDC No Charge<br />

P-10119 6-10 VDC 100 2-10 VDC No Charge<br />

P-10137 2-5 VDC 100 2-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

• Multi-Function Technology: P-10019 (2-10 VDC input / 2-10 VDC feedback) ●<br />

• Set-up: NO (Normally Open) ●<br />

• Tagging: AHU ●<br />

PICCV-15-003-PT+LRX24-MFT+P-10019+NO+AHU Total List Price ●<br />

5


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />

Features and Benefits<br />

6<br />

● Characterizing disc –<br />

made of Tefzel ®<br />

known<br />

for excellent strength<br />

and chemical resistance<br />

● Thermal isolating adapter<br />

between flange and actuator<br />

● Easy direct coupling<br />

of actuator with a<br />

single screw<br />

● Forged brass valve<br />

body – no pin-hole<br />

leaks<br />

Disadvantages of Today’s Systems<br />

● Regulator<br />

Assembly<br />

● Time consuming balancing effort<br />

● Rebalancing required when adding to system or remodeling<br />

● Poor valve authority at average or low load<br />

● Balancing procedure dictates quality<br />

● Potential spreading of control problems can occur when one<br />

or more loops are instable, due to interactive nature of circuits<br />

● Low ∆T reduces efficiency of chillers, condensing boilers, or<br />

coils<br />

● Starving of terminals in less favored spaces results in long<br />

start-up time<br />

Features<br />

● Automatic dynamic system balancing<br />

● Field adjustable flow rate<br />

● 5 – 50 PSI differential pressure operating range (gradual<br />

flow will increase from 0-5 PSI)<br />

● 0.5 – 100 GPM (1/2” – 2”)<br />

● 5 year warranty<br />

*Teflon ® is a registered product of Dupont<br />

● Vent holes reduce<br />

condensation build-up<br />

● Non-corroding<br />

chrome-plated brass<br />

Advantages of the PICCV<br />

● Actuator can be mounted in four<br />

different positions<br />

● Perpendicular mounting flange<br />

and square drive head eliminate<br />

lateral forces on the stem<br />

● Blow-out proof stem with<br />

thrust-bearing Teflon ® disc and<br />

double O-ring design for long<br />

service life*<br />

● Teflon ® seats with O-rings<br />

provide constant seating<br />

force against the ball and<br />

reduce torque requirement*<br />

● Easy selection, no Cv calculation required<br />

● Hydronic balancing is simplified, as the circuits are not<br />

interactive<br />

● Flexible commissioning<br />

● One piece installation saves 50% of labor costs, installation<br />

space, and investment for for balancing valve<br />

● Reduces pumping costs<br />

● Maintains ∆T for higher efficiency of chillers and condensing<br />

boilers<br />

● Visualizes flow in a BMS system and provides accurate<br />

flow for each degree of opening<br />

● Prevents overflow or underflow for fast start-up<br />

Options<br />

Patented<br />

● P/T ports for flow or temperature measurement<br />

● Belimo PC-Tool for commissioning<br />

● Customized Flows<br />

● Certified Factory Calibrated Flows<br />

● Weather shields<br />

● Auxiliary switches<br />

● Metric threads<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

The Best Way to Control Flow<br />

Maintain design flow independent of<br />

pressure variations<br />

The PICCV is a two-way valve that will<br />

supply a specific flow for each degree<br />

of ball opening regardless of pressure<br />

variations in a system.<br />

Flow accuracy ≤ ± 5% (5 to 50 PSI)<br />

(absolute)<br />

Variation due to ≤ ± 5% (5 to 50 PSI)<br />

manufacturing<br />

tolerances<br />

Hysteresis ≤ 1%<br />

(absolute)<br />

Operation<br />

PICCV consists of a differential pressure<br />

regulator in series with a control valve.<br />

The amount of flow that passes through the<br />

valve is controlled by the use of a pressure<br />

regulator that moves according to the<br />

change in pressure above and below it.<br />

All pressure changes are absorbed by<br />

the pressure regulator allowing the<br />

differential pressure to be held constant<br />

over the control valve section thereby<br />

giving the same flow.<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve TM (PICCV)<br />

Flow Rate (GPM)<br />

14<br />

12<br />

10<br />

8<br />

6<br />

4<br />

2<br />

0<br />

Water<br />

enters<br />

valve –<br />

pressure<br />

is P1 (high)<br />

Water passes<br />

through regulator,<br />

disc, and ball –<br />

pressure drops<br />

PICCV Performance<br />

Operating Differential Range of 5 – 50 PSI<br />

0 5 10 15 20 25 30 35 40 45 50<br />

Differential <strong>Pressure</strong> PSI<br />

Regulator<br />

Section<br />

Control Valve<br />

Section<br />

Low pressure pulls regulator<br />

down against the spring force<br />

hence reducing the regulator<br />

opening, reducing the flow.<br />

100%<br />

90%<br />

80%<br />

70%<br />

60%<br />

50%<br />

40%<br />

Water exits<br />

valve –<br />

pressure<br />

is P2 (low)<br />

Ports sense pressure drop<br />

and transfer it through this<br />

channel below regulator<br />

% Ball Opening<br />

7


P2 Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />

with MFT, Non-Spring Return Actuator<br />

Two-way Valve with Chrome Plated Brass Ball and Brass Stem, NPT Female Ends<br />

Service: chilled or hot water, 60% glycol<br />

Flow Characteristic: equal percentage<br />

Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />

Ambient Temp Range: -22°F to 122°F [-30°C to 50°C]<br />

Differential <strong>Pressure</strong><br />

Across Valve Range (ΔP): 5 to 50 psid<br />

Maximum Flow Setting:<br />

Manual Field Adjustable – LRB24-3 Actuators<br />

PC Tool Field Adjustable – MFT Actuators<br />

P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem<br />

Valve Non-Spring Return Actuator<br />

Model Valve Floating Proportional/MFT<br />

# Flow Rate Nominal Size Close-<br />

PICCV Liter/ DN Off<br />

Valve GPM sec Inches mm psi LRB24-3† LRX24-MFT<br />

PICCV-15-0.50* 0.5 0.03 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-001* 1 0.06 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-1.50* 1.5 0.09 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-002* 2 0.13 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-003* 3 0.19 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-004* 4 0.25 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-005* 5 0.32 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-006 6 0.38 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-007 7 0.44 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-008 8 0.50 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-009 9 0.57 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-010 10 0.63 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-012** 12 0.76 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-014** 14 0.88 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-016** 16 1.01 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-018** 18 1.14 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

Electrical 3 ft cable 3 ft cable<br />

Connection 1/2” conduit fitting 1/2” conduit fitting<br />

When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 14).<br />

† Note: FlowSetR only available on (-3) actuator.<br />

Refer to page 53 for customized flows and certified factory calibration flows.<br />

Options (add to list price) LRB24-3-S<br />

Built-in aux. switch (-S) ❑ Pg 12<br />

*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />

**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />

8<br />

LRB24-3<br />

LRX24-MFT<br />

LRB…<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Service: chilled or hot water, 60% glycol<br />

Flow Characteristic: equal percentage<br />

Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />

Ambient Temp Range: -22°F to 122°F [-30°C to 50°C]<br />

Differential <strong>Pressure</strong><br />

Across Valve Range (ΔP): 5 to 50 psid<br />

Maximum Flow Setting:<br />

PC Tool Field Adjustable – MFT Actuators<br />

P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem<br />

Valve Spring Return Actuator<br />

Model Valve Proportional/MFT<br />

# Flow Rate Nominal Size Close-<br />

PICCV Liter/ DN Off<br />

Valve GPM sec Inches mm psi TF24-MFT US LF24-MFT US<br />

PICCV-15-0.50* 0.5 0.03 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-001* 1 0.06 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-1.50* 1.5 0.09 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-002* 2 0.13 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-003* 3 0.19 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-004* 4 0.25 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-005* 5 0.32 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-20-006 6 0.38 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-007 7 0.44 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-008 8 0.50 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-009 9 0.57 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-010 10 0.63 3/4” 20 200 ❑ Pg 19<br />

PICCV-25-012** 12 0.76 1” 25 200 ❑ Pg 19<br />

PICCV-25-014** 14 0.88 1” 25 200 ❑ Pg 19<br />

PICCV-25-016** 16 1.01 1” 25 200 ❑ Pg 19<br />

PICCV-25-018** 18 1.14 1” 25 200 ❑ Pg 19<br />

Electrical 3 ft cable 3 ft cable<br />

Connection 1/2” conduit fitting 1/2” conduit fitting<br />

When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 18).<br />

Refer to page 53 for customized flows and certified factory calibration flows.<br />

Options (add to list price) LF24-MFT-S US<br />

Built-in aux. switch (-S) ❑ Pg 19<br />

P2 Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with MFT, Spring Return Actuator<br />

*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />

**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />

Two-way Valve with Chrome Plated Brass Ball and Brass Stem, NPT Female Ends<br />

TF24-MFT US<br />

TF…<br />

LF24-MFT US<br />

LF…<br />

9


P2 Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />

with MFT, Non-Spring Return Actuator<br />

Two-way Valve with Chrome Plated Brass Ball and Brass Stem with P/T ports, NPT Female Ends<br />

Service: chilled or hot water, 60% glycol<br />

Flow Characteristic: equal percentage<br />

Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />

Ambient Temp Range: -22°F to 122°F [-30°C to 50°C]<br />

Differential <strong>Pressure</strong><br />

Across Valve Range (∆P): 5 to 50 psid<br />

Maximum Flow Setting:<br />

Manual Field Adjustable – LRB24-3 Actuators<br />

PC Tool Field Adjustable – MFT Actuators<br />

P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem, P/T ports<br />

Valve Non-Spring Return Actuator<br />

Model Valve Floating Proportional/MFT<br />

# Flow Rate Nominal Size Close-<br />

PICCV Liter/ DN Off LRB24-3 † LRX24-MFT<br />

Valve GPM sec Inches mm psi ARX24-MFT<br />

PICCV-15-0.50-PT* 0.5 0.03 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-001-PT* 1 0.06 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-1.50-PT* 1.5 0.09 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-002-PT* 2 0.13 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-003-PT* 3 0.19 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-004-PT* 4 0.25 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-15-005-PT* 5 0.32 1/2” 15 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-006-PT 6 0.38 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-007-PT 7 0.44 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-008-PT 8 0.50 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-009-PT 9 0.57 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-20-010-PT 10 0.63 3/4” 20 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-012-PT** 12 0.76 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-014-PT** 14 0.88 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-016-PT** 16 1.01 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-25-018-PT** 18 1.14 1” 25 200 ❑ Pg 12 ❑ Pg 13<br />

PICCV-32-018-PT 18 1.14 1-1/4” 32 200 ❑ Pg 23<br />

PICCV-32-020-PT 20 1.26 1-1/4” 32 200 ❑ Pg 23<br />

PICCV-32-022-PT 22 1.39 1-1/4” 32 200 ❑ Pg 23<br />

PICCV-32-024-PT 24 1.51 1-1/4” 32 200 ❑ Pg 23<br />

PICCV-32-026-PT 26 1.64 1-1/4” 32 200 ❑ Pg 23<br />

PICCV-40-026-PT 26 1.64 1-1/2” 40 200 ❑ Pg 23<br />

PICCV-40-028-PT 28 1.77 1-1/2” 40 200 ❑ Pg 23<br />

PICCV-40-030-PT 30 1.89 1-1/2” 40 200 ❑ Pg 23<br />

PICCV-40-033-PT 33 2.08 1-1/2” 40 200 ❑ Pg 23<br />

PICCV-50-033-PT 33 2.08 2” 50 200 ❑ Pg 23<br />

PICCV-50-036-PT 36 2.27 2” 50 200 ❑ Pg 23<br />

PICCV-50-040-PT 40 2.52 2” 50 200 ❑ Pg 23<br />

PICCV-50-044-PT 44 2.78 2” 50 200 ❑ Pg 31<br />

PICCV-50-048-PT 48 3.03 2” 50 200 ❑ Pg 31<br />

PICCV-50-052-PT 52 3.28 2” 50 200 ❑ Pg 31<br />

PICCV-50-056-PT 56 3.53 2” 50 200 ❑ Pg 31<br />

PICCV-50-060-PT 60 3.79 2” 50 200 ❑ Pg 31<br />

PICCV-50-065-PT 65 4.10 2” 50 200 ❑ Pg 31<br />

PICCV-50-070-PT 70 4.42 2” 50 200 ❑ Pg 31<br />

PICCV-50-075-PT 75 4.73 2” 50 200 ❑ Pg 31<br />

PICCV-50-080-PT 80 5.05 2” 50 200 ❑ Pg 31<br />

PICCV-50-090-PT 90 5.68 2” 50 200 ❑ Pg 31<br />

PICCV-50-100-PT 100 6.31 2” 50 200 ❑ Pg 31<br />

Electrical 3 ft cable 3 ft cable<br />

Connection 1/2” conduit fitting 1/2” conduit fitting<br />

When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 14).<br />

† Note: FlowSetR only available on (-3) actuator.<br />

Refer to page 53 for customized flows and certified factory calibration flows.<br />

Options (add to list price) LRB24-3-S<br />

Built-in aux. switch (-S) ❑ Pg 12<br />

*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />

**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />

10<br />

LRB24-3<br />

ARX24-MFT LRX24-MFT<br />

®<br />

ARX…<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® P2<br />

Service: chilled or hot water, 60% glycol<br />

Flow Characteristic: equal percentage<br />

Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />

Ambient Temp Range:<br />

Differential <strong>Pressure</strong><br />

-22°F to 122°F [-30°C to 50°C]<br />

Across Valve Range (∆P):<br />

Maximum Flow Setting:<br />

5 to 50 psid<br />

PC Tool Field Adjustable – MFT Actuators<br />

Series <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />

with MFT, Spring Return Actuator<br />

Two-way Valve with Chrome Plated Brass Ball and Brass Stem with P/T ports, NPT Female Ends<br />

P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem, P/T ports<br />

Valve Spring Return Actuator<br />

Model Valve Proportional/MFT<br />

# Flow Rate Nominal Size Close-<br />

PICCV Liter/ DN Off TF24-MFT US LF24-MFT US<br />

Valve GPM sec Inches mm psi AF24-MFT US<br />

PICCV-15-0.50-PT* 0.5 0.03 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-001-PT* 1 0.06 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-1.50-PT* 1.5 0.09 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-002-PT* 2 0.13 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-003-PT* 3 0.19 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-004-PT* 4 0.25 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-15-005-PT* 5 0.32 1/2” 15 200 ❑ Pg 17 ❑ Pg 19<br />

PICCV-20-006-PT 6 0.38 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-007-PT 7 0.44 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-008-PT 8 0.50 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-009-PT 9 0.57 3/4” 20 200 ❑ Pg 19<br />

PICCV-20-010-PT 10 0.63 3/4” 20 200 ❑ Pg 19<br />

PICCV-25-012-PT** 12 0.76 1” 25 200 ❑ Pg 19<br />

PICCV-25-014-PT** 14 0.88 1” 25 200 ❑ Pg 19<br />

PICCV-25-016-PT** 16 1.01 1” 25 200 ❑ Pg 19<br />

PICCV-25-018-PT** 18 1.14 1” 25 200 ❑ Pg 19<br />

PICCV-32-018-PT 18 1.14 1-1/4” 32 200 ❑ Pg 27<br />

PICCV-32-020-PT 20 1.26 1-1/4” 32 200 ❑ Pg 27<br />

PICCV-32-022-PT 22 1.39 1-1/4” 32 200 ❑ Pg 27<br />

PICCV-32-024-PT 24 1.51 1-1/4” 32 200 ❑ Pg 27<br />

PICCV-32-026-PT 26 1.64 1-1/4” 32 200 ❑ Pg 27<br />

PICCV-40-026-PT 26 1.64 1-1/2” 40 200 ❑ Pg 27<br />

PICCV-40-028-PT 28 1.77 1-1/2” 40 200 ❑ Pg 27<br />

PICCV-40-030-PT 30 1.89 1-1/2” 40 200 ❑ Pg 27<br />

PICCV-40-033-PT 33 2.08 1-1/2” 40 200 ❑ Pg 27<br />

PICCV-50-033-PT 33 2.08 2” 50 200 ❑ Pg 27<br />

PICCV-50-036-PT 36 2.27 2” 50 200 ❑ Pg 27<br />

PICCV-50-040-PT 40 2.52 2” 50 200 ❑ Pg 27<br />

PICCV-50-044-PT 44 2.78 2” 50 200 ❑ Pg 33<br />

PICCV-50-048-PT 48 3.03 2” 50 200 ❑ Pg 33<br />

PICCV-50-052-PT 52 3.28 2” 50 200 ❑ Pg 33<br />

PICCV-50-056-PT 56 3.53 2” 50 200 ❑ Pg 33<br />

PICCV-50-060-PT 60 3.79 2” 50 200 ❑ Pg 33<br />

PICCV-50-065-PT 65 4.10 2” 50 200 ❑ Pg 33<br />

PICCV-50-070-PT 70 4.42 2” 50 200 ❑ Pg 33<br />

PICCV-50-075-PT 75 4.73 2” 50 200 ❑ Pg 33<br />

PICCV-50-080-PT 80 5.05 2” 50 200 ❑ Pg 33<br />

PICCV-50-090-PT 90 5.68 2” 50 200 ❑ Pg 33<br />

PICCV-50-100-PT 100 6.31 2” 50 200 ❑ Pg 33<br />

Electrical 3 ft cable 3 ft cable<br />

Connection 1/2” conduit fitting 1/2” conduit fitting<br />

When ordering MFT, see configuration codes under “MFT Adjustment Tables” (for example, see page 18).<br />

Refer to page 53 for customized flows and certified factory calibration flows.<br />

Options (add to list price) LF24-MFT-S US AF24-MFT-S US<br />

Built-in aux. switch (-S) ❑ Pg 19 ❑ Pg 27 & 33<br />

*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />

**1” body has two different disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />

TF24-MFT US<br />

LF24-MFT US<br />

AF24-MFT US<br />

AF…<br />

11


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with Floating, Non-Spring Return Actuator, P/T Ports (Optional)<br />

Valve Specifications<br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 1/2”, 3/4”, 1”<br />

Type of end fitting<br />

Materials:<br />

female, NPT<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seat fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator components stainless steel/brass/Delrin 500 AF<br />

Spring stainless steel<br />

Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Optional-P/T)<br />

Body pressure rating 600 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />

1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />

3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />

5 GPM [.32 l/s]<br />

Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />

8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />

10 GPM [0.63 l/s]<br />

Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />

16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure<br />

operating range<br />

5 to 50 PSI<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body 1/2” = 2.52 lbs<br />

3/4” = 3.05 lbs<br />

1” = 4.98 lbs<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

12<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />

used in air handling units on heating and cooling coils and fan coil<br />

unit heating or cooling coils. Some other common applications<br />

include unit ventilators and VAV re-heat coils. This valve is suitable<br />

for use in a hydronic system with constant or variable flow.<br />

Actuator Specifications<br />

❏ LRB24-3… on/off-floating<br />

Power Supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power Consumption 1.5 W (0.2 W)<br />

Transformer Sizing 3 VA (Class 2 power source)<br />

Electrical Connection 3 ft, 18 GA plenum rated cable<br />

3 ft, 18 GA appliance rated cable (-S)<br />

1/2” conduit connector<br />

Overload Protection electronic throughout 0 to 95° rotation<br />

Control on/off, floating point<br />

Input Impedance 600Ω<br />

Direction of Rotation reversible with switch<br />

Position Indication handle<br />

Manual Override external push button and handle<br />

Running Time 95 seconds, constant independent of load<br />

Humidity 5 to 95% RH non condensing<br />

(EN 60730-1)<br />

Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />

Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />

Housing NEMA 2/IP54<br />

Housing Material UL94-5VA<br />

Agency Listings cULus acc. to UL60730-1A/-2-14,<br />

CAN/CSA E60730-1, CSA C22.2<br />

No. 24-93, CE acc. to 89/336/EEC and<br />

(-S Models) 2006/95/EC†<br />

Noise Level


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

Valve Specifications<br />

®<br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 1/2”, 3/4”, 1”<br />

Type of end fitting<br />

Materials:<br />

female, NPT<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seat fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator components stainless steel/brass/Delrin 500 AF<br />

Spring stainless steel<br />

Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Optional-P/T)<br />

Body pressure rating 600 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />

1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />

3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />

5 GPM [.32 l/s]<br />

Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />

8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />

10 GPM [0.63 l/s]<br />

Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />

16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure<br />

operating range<br />

5 to 50 PSI<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body 1/2” = 2.52 lbs<br />

3/4” = 3.05 lbs<br />

1” = 4.98 lbs<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />

used in air handling units on heating and cooling coils and fan coil<br />

unit heating or cooling coils. Some other common applications<br />

include unit ventilators and VAV re-heat coils. This valve is suitable<br />

for use in a hydronic system with constant or variable flow.<br />

This valve is designed with MFT functionality which facilitates<br />

the use of various control input.<br />

Actuator Specifications<br />

❏ LRX24-MFT<br />

Power Supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power Consumption 2 W (1.2 W)<br />

Transformer Sizing 3.5 VA (Class 2 power source)<br />

Electrical Connection 18 GA plenum rated cable<br />

1/2” conduit connector<br />

❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />

Overload Protection electronic throughout 0 to 95° rotation<br />

Operating Range Y 2 to 10 VDC, 4 to 20 mA (default)<br />

Variable (VDC, PWM, Floating Point,<br />

On/Off)<br />

Input Impedance 100kΩ (0.1 mA), 500Ω<br />

1500Ω (PWM, Floating Point, On/Off)<br />

Feedback Output U 2 to 10 Vdc, 0.5mA max<br />

VDC Variable<br />

Torque 45 in-lb [5 Nm]<br />

Direction of Rotation reversible with switch<br />

Position Indication reflective visual indicator (snap-on)<br />

Manual Override external push button<br />

Running Time Motor* 100 sec constant<br />

Humidity 5 to 95% RH non condensing<br />

(EN 60730-1)<br />

Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />

Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />

Housing NEMA 2/IP54<br />

Housing Material UL94-5VA<br />

Agency Listings cULus acc. to UL60730-1A/-2-14,<br />

CAN/CSA E60730-1, CSA C22.2<br />

No. 24-93, CE acc. to 89/336/EEC†<br />

Noise Level


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />

1/2”, 0.5 – 5 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-15-001 (-PT) can be ordered in 0.50 GPM or 1.0<br />

GPM flow rates. The PICCV-15-005 (-PT) can be ordered in<br />

1.5 GPM to 5.5 GPM flow rate increments, as stated in the<br />

table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 2 GPM flow rate.<br />

Solution: Order the PICCV-15-002<br />

Example 2: The application requires a 3.5 GPM flow rate.<br />

Solution: Order the PICCV-15-005 and re-program to the<br />

below setting for 3.5 GPM. As a standard, the<br />

PICCV is available in flows of 4 GPM and 3 GPM.<br />

If you desire 3.5 GPM and have a Normally<br />

Closed (NC) valve, simply reprogram the maximum<br />

setting to 71%, and minimum setting<br />

of 0% as indicated on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 74% 0% NEW<br />

PICCV-15-001(-PT) + LRX24-MFT ♦ 1 0.06 94% 0% NEW<br />

PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 48% 0%<br />

PICCV-15-001(-PT) + LRX24-MFT †♦ 1 0.06 73% 0%<br />

PICCV-15-1.50(-PT) + LRX24-MFT 1.5 0.09 57% 0%<br />

PICCV-15-002(-PT) + LRX24-MFT 2 0.13 64% 0%<br />

2.5 0.16 66% 0%<br />

PICCV-15-003(-PT) + LRX24-MFT 3 0.19 69% 0%<br />

3.5 0.22 71% 0%<br />

PICCV-15-004(-PT) + LRX24-MFT 4 0.25 76% 0%<br />

4.5 0.28 79% 0%<br />

PICCV-15-005(-PT) + LRX24-MFT 5 0.32 82% 0%<br />

5.5 0.35 87% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 100% 33% NEW<br />

PICCV-15-001(-PT) + LRX24-MFT ♦ 1 0.06 100% 12% NEW<br />

PICCV-15-0.50(-PT) + LRX24-MFT ♦ 0.5 0.03 100% 55%<br />

PICCV-15-001(-PT) + LRX24-MFT †♦ 1 0.06 100% 37%<br />

PICCV-15-1.50(-PT) + LRX24-MFT 1.5 0.09 100% 43%<br />

PICCV-15-002(-PT) + LRX24-MFT 2 0.13 100% 40%<br />

2.5 0.16 100% 37%<br />

PICCV-15-003(-PT) + LRX24-MFT 3 0.19 100% 35%<br />

3.5 0.22 100% 32%<br />

PICCV-15-004(-PT) + LRX24-MFT 4 0.25 100% 28%<br />

4.5 0.28 100% 25%<br />

PICCV-15-005(-PT) + LRX24-MFT 5 0.32 100% 20%<br />

5.5 0.35 100% 18%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

† Note: 1/2” valve has 2 disc sizes (.5 to 1 GPM) (1.5 to 5.5 GPM)<br />

♦ For replacement or re-programming, please contact <strong>Technical</strong> Support 800-543-9038.<br />

Multi-Function<br />

Technology<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

14<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 3 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-15-003 + LRX24-MFT + P-10019.<br />

Engineering Note: The 1/2” PICCV utilizes two uniquely engineered<br />

valve bodies to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered Multi-<br />

Function Technology®. The PICCV-15-001 offers nominal flow<br />

rates that are adjustable from 0.5 to 1.0 GPM. The PICCV-15-005<br />

offers nominal flow rates that are adjustable from 1.5 to 5.5 GPM<br />

range. Please follow MFT guideline settings when configuring the<br />

PICCV MFT actuators in the field.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® <strong>Pressure</strong><br />

Selecting the Proper Flow Rate:<br />

The PICCV-20-010 (-PT) can be ordered in 6 GPM to 10 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 6 GPM flow rate.<br />

Solution: Order the PICCV-20-006<br />

Example 2: The application requires a 8.5 GPM flow rate.<br />

Solution: Order the PICCV-20-010 and re-program to the<br />

below setting for 8.5 GPM. As a standard, the<br />

PICCV is available in flows of 8 GPM and 9 GPM.<br />

If you desire 8.5 GPM and have a Normally Closed<br />

(NC) valve, simply reprogram the maximum setting<br />

to 82%, and minimum setting of 0% as indicated<br />

on the chart below.<br />

<strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />

3/4”, 6 – 10 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-20-006(-PT) + LRX24-MFT 6 0.38 74% 0%<br />

6.5 0.41 75% 0%<br />

PICCV-20-007(-PT) + LRX24-MFT 7 0.44 77% 0%<br />

7.5 0.47 79% 0%<br />

PICCV-20-008(-PT) + LRX24-MFT 8 0.50 80% 0%<br />

8.5 0.54 82% 0%<br />

PICCV-20-009(-PT) + LRX24-MFT 9 0.57 83% 0%<br />

9.5 0.60 85% 0%<br />

PICCV-20-010(-PT) + LRX24-MFT 10 0.63 90% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-20-006(-PT) + LRX24-MFT 6 0.38 100% 31%<br />

6.5 0.41 100% 28%<br />

PICCV-20-007(-PT) + LRX24-MFT 7 0.44 100% 27%<br />

7.5 0.47 100% 25%<br />

PICCV-20-008(-PT) + LRX24-MFT 8 0.50 100% 24%<br />

8.5 0.54 100% 22%<br />

PICCV-20-009(-PT) + LRX24-MFT 9 0.57 100% 19%<br />

9.5 0.60 100% 18%<br />

PICCV-20-010(-PT) + LRX24-MFT 10 0.63 100% 13%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

Multi-Function<br />

Technology<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering,<br />

please specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 6 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-20-006 + LRX24-MFT + P-10019.<br />

Engineering Note: The 3/4” PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology®. The PICCV-20-010 offers nominal<br />

flow rates that are adjustable from 6 to 10 GPM. Please follow<br />

MFT guideline settings when configuring the PICCV MFT actuators<br />

in the field.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

15


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Non-Spring Return Actuator, P/T Ports (Optional)<br />

1”, 12 – 18 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV can be ordered in 2 ways. The PICCV-25-016<br />

can be reprogrammed to offer flows from 11 GPM – 16 GPM.<br />

Example 1: The application requires a 14 GPM flow rate.<br />

Solution: Order the PICCV-25-014<br />

Example 2: The application requires a 15 GPM flow rate.<br />

Solution: Order the PICCV-25-016 and re-program to the<br />

below setting for 15 GPM. As a standard, the<br />

PICCV is available in flows of 14 GPM and 16<br />

GPM. If you desire 15 GPM and have a Normally<br />

Closed (NC) valve, simply reprogram the maximum<br />

setting to 83%, and minimum setting of 0% as<br />

indicated on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

11 0.69 73% 0%<br />

PICCV-25-012(-PT) + LRX24-MFT 12 0.76 75% 0%<br />

13 0.82 77% 0%<br />

PICCV-25-014(-PT) + LRX24-MFT 14 0.88 80% 0%<br />

15 0.95 83% 0%<br />

PICCV-25-016(-PT) + LRX24-MFT† 16 1.01 100% 0%<br />

PICCV-25-018 (-PT)+ LRX24-MFT 17 1.07 78% 0%<br />

18 1.14 81% 0%<br />

19 1.20 92% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

11 0.69 100% 26%<br />

PICCV-25-012(-PT) + LRX24-MFT 12 0.76 100% 24%<br />

13 0.82 100% 20%<br />

PICCV-25-014(-PT) + LRX24-MFT 14 0.88 100% 16%<br />

15 0.95 100% 9%<br />

PICCV-25-016(-PT) + LRX24-MFT† 16 1.01 100% 0%<br />

PICCV-25-018(-PT) + LRX24-MFT 17 1.07 100% 22%<br />

18 1.14 100% 15%<br />

19 1.20 100% 11%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

† 1” valve has 2 disc sizes (11 GPM to 16 GPM) (17 GPM to 19 GPM)<br />

Multi-Function<br />

Technology<br />

16<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 14 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-25-014 + LRX24-MFT+ P-10019.<br />

Engineering Note: The 1” PICCV utilizes two uniquely engineered<br />

valve bodies to achieve the listed flow rate offerings. Variable<br />

GPMs are further realized using Belimo’s registered Multi-Function<br />

Technology®. The PICCV-25-016 offers nominal flow rates that<br />

are adjustable from 11 to 16 GPM. The PICCV-25-018 offers nominal<br />

flow rates that are adjustable from 17 to 19 GPM range.<br />

Please follow MFT guideline settings when configuring the PICCV<br />

MFT actuators in the field.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: LRX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® <strong>Pressure</strong><br />

<strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Spring Return Actuator, P/T Ports (Optional)<br />

Actuator Specifications<br />

TF24-MFT US<br />

Power supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power consumption running: 2.5 W; holding: 1 W<br />

Transformer sizing 4 VA (class 2 power source)<br />

Electrical connection TF24-MFT US 3 ft, 18 GA plenum rated cable<br />

1/2” conduit connector<br />

Overload protection electronic throughout 0° to 95° rotation<br />

Operating range Y 2 to 10 VDC<br />

4 to 20 mA<br />

(w/500Ω, 1/4 W resistor) ZG-R01<br />

Input impedance 100kΩ for 2 to 10 VDC (0.1 mA)<br />

500Ω for 4 to 20 mA<br />

Feedback output U<br />

1500Ω for PWM, Floating point and<br />

On-Off control<br />

2 to 10 VDC, 0.5 mA max<br />

Torque min 18 in-lb (2 Nm)<br />

Direction of rotation spring: reversible with cw/ccw mounting<br />

motor: reversible with built-in switch<br />

Mech. angle of rotation max 95°, adjust with mechanical stop<br />

Running time motor* 100 sec constant<br />

Running time spring


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Spring Return Actuator, P/T Ports (Optional)<br />

1/2”, 0.5 – 5 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-15-001 (-PT) can be ordered in 0.50 GPM or 1.0<br />

GPM flow rates. The PICCV-15-005 (-PT) can be ordered in<br />

1.5 GPM to 5.5 GPM flow rate increments, as stated in the<br />

table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 2 GPM flow rate.<br />

Solution: Order the PICCV-15-002<br />

Example 2: The application requires a 3.5 GPM flow rate.<br />

Solution: Order the PICCV-15-005 and re-program to the<br />

below setting for 3.5 GPM. As a standard, the<br />

PICCV is available in flows of 4 GPM and 3 GPM.<br />

If you desire 3.5 GPM and have a Normally<br />

Closed, Fail Open (NC, FO) valve, simply reprogram<br />

the maximum setting to 75%, and minimum<br />

setting of 0% as indicated on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on W<br />

Default* Flow Adjustments**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-15-0.50(-PT)+ TF24-MFT US 0.5 0.03 FO 80%, FC 73% FO, FC 0%<br />

PICCV-15-001(-PT) + TF24-MFT US† 1 0.06 FO 94%, FC 90% FO, FC 0%<br />

PICCV-15-1.50(-PT)+ TF24-MFT US 1.5 0.09 FO 62%, FC 58% FO, FC 0%<br />

PICCV-15-002(-PT) + TF24-MFT US 2 0.13 FO 66%, FC 62% FO, FC 0%<br />

2.5 0.16 FO 69%, FC 65% FO, FC 0%<br />

PICCV-15-003(-PT) + TF24-MFT US 3 0.19 FO 72%, FC 69% FO, FC 0%<br />

3.5 0.22 FO 75%, FC 71% FO, FC 0%<br />

PICCV-15-004(-PT) + TF24-MFT US 4 0.25 FO 77%, FC 73% FO, FC 0%<br />

4.5 0.25 FO 81%, FC 77% FO, FC 0%<br />

PICCV-15-005(-PT) + TF24-MFT US 5 0.32 FO 85%, FC 81% FO, FC 0%<br />

5.5 0.35 FO 89%, FC 85% FO, FC 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CW<br />

Default* Flow Adjustments**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-15-0.50(-PT)+ TF24-MFT US 0.5 0.03 FO, FC 100% FO 29%, FC 34%<br />

PICCV-15-001(-PT) + TF24-MFT US† 1 0.06 FO, FC 100% FO 13%, FC 15%<br />

PICCV-15-1.50(-PT)+ TF24-MFT US 1.5 0.09 FO, FC 100% FO 43%, FC 47%<br />

PICCV-15-002(-PT) + TF24-MFT US 2 0.13 FO, FC 100% FO 39%, FC 43%<br />

2.5 0.16 FO, FC 100% FO 36%, FC 41%<br />

PICCV-15-003(-PT) + TF24-MFT US 3 0.19 FO, FC 100% FO 34%, FC 38%<br />

3.5 0.22 FO, FC 100% FO 31%, FC 36%<br />

PICCV-15-004(-PT) + TF24-MFT US 4 0.25 FO, FC 100% FO 28%, FC 33%<br />

4.5 0.25 FO, FC 100% FO 25%, FC 29%<br />

PICCV-15-005(-PT) + TF24-MFT US 5 0.32 FO, FC 100% FO 20%, FC 25%<br />

5.5 0.35 FO, FC 100% FO 17%, FC 22%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

† Note: 1/2” valve has 2 disc sizes (.5 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />

Multi-Function<br />

Technology<br />

18<br />

Please note that the settings are different for Normally Closed,<br />

Fail Open or Fail Closed (NC, FO or FC) and Normally Open, Fail<br />

Open or Fail Closed (NO, FO or FC) operation. When ordering,<br />

please specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 3 GPM flow rate is required, spring return actuator,<br />

2-10 VDC signal.<br />

Solution: PICCV-15-003 + TF24-MFT US + P-10019.<br />

Engineering Note: The 1/2” PICCV utilizes two uniquely engineered<br />

valve bodies to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered Multi-<br />

Function Technology®. The PICCV-15-001 offers nominal flow rates<br />

that are adjustable from 0.5 to 1.0 GPM. The PICCV-15-005 offers<br />

nominal flow rates that are adjustable from 1.5 to 5.5 GPM range.<br />

Please follow MFT guideline settings when configuring the PICCV<br />

MFT actuators in the field.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: TF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

Valve Specifications<br />

® <strong>Pressure</strong><br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 1/2”, 3/4”, 1”<br />

Type of end fitting<br />

Materials:<br />

female, NPT<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seat fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator components stainless steel/brass/Delrin 500 AF<br />

Spring stainless steel<br />

Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Optional-PT)<br />

Body pressure rating 600 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />

1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />

3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />

5 GPM [.32 l/s]<br />

Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />

8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />

10 GPM [0.63 l/s]<br />

Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />

16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure<br />

operating range<br />

5 to 50 PSI<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body 1/2” = 2.52 lbs, 3/4” = 3.05 lbs<br />

1” = 4.98 lbs<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

<strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Spring Return Actuator, P/T Ports (Optional)<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />

used in air handling units on heating and cooling coils and fan coil<br />

unit heating or cooling coils. Some other common applications<br />

include unit ventilators and VAV re-heat coils. This valve is suitable<br />

for use in a hydronic system with constant or variable flow.<br />

This valve is designed with MFT functionality which facilitates<br />

the use of various control input.<br />

Actuator Specifications<br />

❏ LF24-MFT US<br />

Control MFT<br />

Control signal Y 2 to 10 VDC (Default)<br />

Power supply 24 VAC ± 20% 50/60 Hz, 24 VDC ± 10%<br />

Power consumption 2.5 W running, 1 W holding<br />

Transformer sizing 5 VA (Class 2 power source)<br />

Electrical connection 3 ft, 18 GA, plenum rated cable,<br />

1/2” conduit<br />

Overload protection electronic throughout 0 to 95° rotation<br />

Operating range 2 to 10 VDC, 4 to 20 mA<br />

(w/500 Ω, 1/4 W resistor) ZG-R01<br />

Input impedance 100kΩ for 2 to 10 VDC (0.1 mA)<br />

500Ω for 4 to 20 mA, 1500Ω for PWM,<br />

Floating point and On-Off control<br />

Feedback output U 2 to 10 VDC, 0.5 mA max<br />

Direction of rotation spring return reversible with CW/CCW<br />

mounting. Control direction selected by<br />

switch: CW=CW with decrease in signal<br />

CCW=CCW with a decrease in signal<br />

Running time motor* 100 sec constant<br />

Running time spring


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Spring Return Actuator, P/T Ports (Optional)<br />

1/2”, 0.5 – 5 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-15-001 (-PT) can be ordered in 0.50 GPM or 1.0<br />

GPM flow rates. The PICCV-15-005 (-PT) can be ordered in<br />

1.5 GPM to 5.5 GPM flow rate increments, as stated in the<br />

table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 2 GPM flow rate.<br />

Solution: Order the PICCV-15-002<br />

Example 2: The application requires a 3.5 GPM flow rate.<br />

Solution: Order the PICCV-15-005 and re-program to the<br />

below setting for 3.5 GPM. As a standard, the<br />

PICCV is available in flows of 4 GPM and 3 GPM.<br />

If you desire 3.5 GPM and have a Normally Closed<br />

(NC) valve, simply reprogram the maximum setting<br />

to 71%, and minimum setting of 0% as indicated<br />

on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />

Default* Flow Adjustments**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 FO 72%, FC 68%° FO, FC 0%° NEW<br />

PICCV-15-001(-PT) + LF24-MFT US♦ 1 0.06 FO 91%, FC 88%° FO, FC 0%° NEW<br />

PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 48% 0%<br />

PICCV-15-001(-PT) + LF24-MFT US†♦ 1 0.06 73% 0%<br />

PICCV-15-1.50(-PT) + LF24-MFT US♦ 1.5 0.09 57% 0%<br />

PICCV-15-002-PT + LF24-MFT US 2 0.13 64% 0%<br />

2.5 0.16 66% 0%<br />

PICCV-15-003(-PT) + LF24-MFT US 3 0.19 69% 0%<br />

3.5 0.22 71% 0%<br />

PICCV-15-004(-PT) + LF24-MFT US 4 0.25 76% 0%<br />

4.5 0.28 79% 0%<br />

PICCV-15-005(-PT) + LF24-MFT US 5 0.32 82% 0%<br />

5.5 0.35 87% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />

Default* Flow Adjustments**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 FO, FC 100%° FO 30%, FC 33%° NEW<br />

PICCV-15-001(-PT) + LF24-MFT US♦ 1 0.06 FO, FC 100%° FO 11%, FC 15%° NEW<br />

PICCV-15-0.50(-PT) + LF24-MFT US♦ 0.5 0.03 100% 55%<br />

PICCV-15-001(-PT) + LF24-MFT US†♦ 1 0.06 100% 37%<br />

PICCV-15-1.50(-PT) + LF24-MFT US 1.5 0.09 100% 43%<br />

PICCV-15-002(-PT) + LF24-MFT US 2 0.13 100% 40%<br />

2.5 0.16 100% 37%<br />

PICCV-15-003(-PT) + LF24-MFT US 3 0.19 100% 35%<br />

3.5 0.22 100% 32%<br />

PICCV-15-004(-PT) + LF24-MFT US 4 0.25 100% 28%<br />

4.5 0.28 100% 25%<br />

PICCV-15-005(-PT) + LF24-MFT US 5 0.32 100% 20%<br />

5.5 0.35 100% 18%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set. °FO = Fail Open, FC = Fail Closed<br />

† Note: 1/2” valve has 2 disc sizes (.5 to 1 GPM) (1.5 to 5.5 GPM)<br />

♦For replacement or re-programming, please contact <strong>Technical</strong> Support 800-543-9038.<br />

Multi-Function<br />

Technology<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 3 GPM flow rate is required, spring return actuator,<br />

2-10 VDC signal.<br />

Solution: PICCV-15-003 + LF24-MFT US + P-10019.<br />

Engineering Note: The 1/2” PICCV utilizes two uniquely engineered<br />

valve bodies to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered Multi-<br />

Function Technology®. The PICCV-15-001 offers nominal flow rates<br />

that are adjustable from 0.5 to 1.3 GPM. The PICCV-15-005 offers<br />

nominal flow rates that are adjustable from 1.5 to 5.5 GPM range.<br />

Please follow MFT guideline settings when configuring the PICCV<br />

MFT actuators in the field.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: LF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

20<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Selecting the Proper Flow Rate:<br />

The PICCV-20-010 (-PT) can be ordered in 6 GPM to 10 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 6 GPM flow rate.<br />

Solution: Order the PICCV-20-006<br />

Example 2: The application requires a 8.5 GPM flow rate.<br />

Solution: Order the PICCV-20-010 and re-program to the<br />

below setting for 8.5 GPM. As a standard, the<br />

PICCV is available in flows of 8 GPM and 9 GPM.<br />

If you desire 8.5 GPM and have a Normally Closed<br />

(NC) valve, simply reprogram the maximum setting<br />

to 82% and minimum setting of 0% as indicated on<br />

the chart below.<br />

Multi-Function<br />

Technology<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Spring Return Actuator, P/T Ports (Optional)<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering,<br />

please specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 6 GPM flow rate is required, spring return actuator,<br />

2-10 VDC signal.<br />

Solution: PICCV-20-006 + LF24-MFT US + P-10019.<br />

Engineering Note: The 3/4” PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology®. The PICCV-20-010 offers nominal<br />

flow rates that are adjustable from 6 to 10 GPM. Please follow<br />

MFT guideline settings when configuring the PICCV MFT actuators<br />

in the field.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: LF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

3/4”, 6 – 10 GPM<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />

Default* Flow Adjustments**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-20-006(-PT) + LF24-MFT US 6 0.38 74% 0%<br />

6.5 0.41 75% 0%<br />

PICCV-20-007(-PT) + LF24-MFT US 7 0.44 77% 0%<br />

7.5 0.47 79% 0%<br />

PICCV-20-008(-PT) + LF24-MFT US 8 0.50 80% 0%<br />

8.5 0.54 82% 0%<br />

PICCV-20-009(-PT) + LF24-MFT US 9 0.57 83% 0%<br />

9.5 0.60 85% 0%<br />

PICCV-20-010(-PT) + LF24-MFT US 10 0.63 90% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />

Default* Flow Adjustments**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-20-006(-PT) + LF24-MFT US 6 0.38 100% 31%<br />

6.5 0.41 100% 28%<br />

PICCV-20-007(-PT) + LF24-MFT US 7 0.44 100% 27%<br />

7.5 0.47 100% 25%<br />

PICCV-20-008(-PT) + LF24-MFT US 8 0.50 100% 24%<br />

8.5 0.54 100% 22%<br />

PICCV-20-009(-PT) + LF24-MFT US 9 0.57 100% 19%<br />

9.5 0.60 100% 18%<br />

PICCV-20-010(-PT) + LF24-MFT US 10 0.63 100% 13%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

21


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with MFT, Spring Return Actuator, P/T Ports (Optional)<br />

1”, 12 – 18 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-25-016 (-PT) can be ordered in 11 GPM to 16 GPM<br />

flow increments, as stated in the table below.<br />

The PICCV-25-018 (-PT) can be ordered in 17 GPM to 19 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 14 GPM flow rate.<br />

Solution: Order the PICCV-25-014<br />

Example 2: The application requires a 15 GPM flow rate.<br />

Solution: Order the PICCV-25-016 and re-program to the<br />

below setting for 15 GPM. As a standard, the PICCV<br />

is available in flows of 14 GPM and 16 GPM. If you<br />

desire 15 GPM and have a Normally Closed (NC)<br />

valve, simply reprogram the maximum setting to<br />

83%, and minimum setting of 0% as indicated on<br />

the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

11 0.69 73% 0%<br />

PICCV-25-012(-PT) + LF24-MFT US 12 0.76 75% 0%<br />

13 0.82 77% 0%<br />

PICCV-25-014(-PT) + LF24-MFT US 14 0.88 80% 0%<br />

15 0.95 83% 0%<br />

PICCV-25-016(-PT) + LF24-MFT US† 16 1.01 100% 0%<br />

PICCV-25-018(-PT) + LF24-MFT US 17 1.07 78% 0%<br />

18 1.14 81% 0%<br />

19 1.20 92% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

11 0.69 100% 26%<br />

PICCV-25-012(-PT) + LF24-MFT US 12 0.76 100% 24%<br />

13 0.82 100% 20%<br />

PICCV-25-014(-PT) + LF24-MFT US 14 0.88 100% 16%<br />

15 0.95 100% 9%<br />

PICCV-25-016(-PT) + LF24-MFT US† 16 1.01 100% 0%<br />

PICCV-25-018(-PT) + LF24-MFT US 17 1.07 100% 22%<br />

18 1.14 100% 15%<br />

19 1.20 100% 11%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

† 1” valve has 2 disc sizes (11 to 16 GPM) (17 to 19 GPM)<br />

Multi-Function<br />

Technology<br />

22<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 14 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-25-014 + LF24-MFT US + P-10019.<br />

Engineering Note: The 1” PICCV utilizes two uniquely engineered<br />

valve bodies to achieve the listed flow rate offerings. Variable<br />

GPMs are further realized using Belimo’s registered Multi-Function<br />

Technology®. The PICCV-25-016 offers nominal flow rates that<br />

are adjustable from 11 to 16 GPM. The PICCV-25-018 offers nominal<br />

flow rates that are adjustable from 17 to 19 GPM range.<br />

Please follow MFT guideline settings when configuring the PICCV<br />

MFT actuators in the field.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: LF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

Valve Specifications<br />

®<br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 1-1/4”, 1-1/2”, 2”<br />

Type of end fitting<br />

Materials:<br />

female, NPT<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seat fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator stainless steel/brass/Delrin 500 AF<br />

Spring stainless steel<br />

Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Standard)<br />

<strong>Pressure</strong> rating 400 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 1-1/4” 18 GPM [1.14 l/s], 20 GPM [1.26 l/s],<br />

22 GPM [1.33 l/s], 24 GPM [1.51 l/s],<br />

26 GPM [1.64 l/s]<br />

Flow rate – 1-1/2” 26 GPM [1.64 l/s], 28 GPM [1.77 l/s],<br />

30 GPM [1.89 l/s], 33 GPM [2.08 l/s]<br />

Flow rate – 2” 33 GPM [2.08 l/s], 36 GPM [2.27 l/s],<br />

40 GPM [2.52 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure<br />

range<br />

5 to 50 PSI<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body 1-1/4” = 8.31 lbs<br />

1-1/2” = 7.70 lbs<br />

2” = 9.38 lbs<br />

*Consult page 51 and 52 for flow verification data.<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Non-Spring Return Actuator<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />

used in air handling units on heating and cooling coils, and fan coil<br />

unit heating or cooling coils. Some other common applications<br />

include unit ventilators and VAV re-heat coils. This valve is suitable<br />

for use in a hydronic system with constant or variable flow.<br />

This valve is designed with MFT functionality which facilitates<br />

the use of various control input.<br />

Actuator Specifications<br />

❏ ARX24-MFT<br />

Power Supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power Consumption 4 W (1.25 W)<br />

Transformer Sizing 6 VA (Class 2 power source)<br />

Electrical Connection 18 GA plenum rated cable<br />

1/2” conduit connector<br />

❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />

Overload Protection electronic throughout 0 to 95° rotation<br />

Operating Range Y 2 to 10 VDC, 4 to 20 mA (default)<br />

Variable (VDC, PWM, Floating Point,<br />

On/Off)<br />

Input Impedance 100 kΩ (0.1 mA), 500Ω<br />

1500 Ω (PWM, Floating Point, On/Off)<br />

Feedback Output U 2 to 10 VDC, 0.5 mA max<br />

VDC Variable<br />

Direction of Rotation reversible with switch<br />

Position Indication handle<br />

Manual Override external push button and handle<br />

Running Time Motor* 100 sec constant<br />

Humidity 5 to 95% RH non condensing<br />

(EN 60730-1)<br />

Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />

Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />

Housing NEMA 2/IP54<br />

Housing Material UL94-5VA<br />

Agency Listings cULus acc. to UL60730-1A/-2-14,<br />

CAN/CSA E60730-1, CSA C22.2<br />

No. 24-93, CE acc. to 89/336/EEC†<br />

Noise Level


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Non-Spring Return Actuator<br />

1-1/4”, 18 – 26 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-32-026-PT can be ordered in 26 GPM to 33 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 22 GPM flow rate.<br />

Solution: Order the PICCV-32-022-PT<br />

Example 2: The application requires a 25 GPM flow rate.<br />

Solution: Order the PICCV-32-026-PT and re-program to<br />

the below setting for 25 GPM. As a standard, the<br />

PICCV is available in flows of 18, 20, 22, 24 and<br />

26 GPM. If you desire 25 GPM and have a<br />

Normally Closed (NC) valve, simply reprogram<br />

the maximum setting to 87%, and minimum setting<br />

of 0% as indicated on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-32-018-PT + ARX24-MFT 18 1.14 78% 0%<br />

19 1.19 79% 0%<br />

PICCV-32-020-PT + ARX24-MFT 20 1.26 80% 0%<br />

21 1.32 82% 0%<br />

PICCV-32-022-PT + ARX24-MFT 22 1.33 83% 0%<br />

23 1.45 84% 0%<br />

PICCV-32-024-PT + ARX24-MFT 24 1.51 85% 0%<br />

25 1.58 87% 0%<br />

PICCV-32-026-PT + ARX24-MFT 26 1.64 92% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-32-018-PT + ARX24-MFT 18 1.14 100% 25%<br />

19 1.19 100% 24%<br />

PICCV-32-020-PT + ARX24-MFT 20 1.26 100% 23%<br />

21 1.32 100% 22%<br />

PICCV-32-022-PT + ARX24-MFT 22 1.33 100% 19%<br />

23 1.45 100% 18%<br />

PICCV-32-024-PT + ARX24-MFT 24 1.51 100% 17%<br />

25 1.58 100% 14%<br />

PICCV-32-026-PT + ARX24-MFT 26 1.64 100% 11%<br />

* Preprogrammed at factory<br />

** Customer reprogrammable using MFT PC tool / or can be factory set.<br />

Multi-Function<br />

Technology<br />

24<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 22 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-32-022-PT + ARX24-MFT + P-10019.<br />

Engineering Note: The 1-1/4” PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ® . Please follow MFT guideline settings<br />

when configuring the PICCV MFT actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-40-033-PT can be ordered in 26 GPM to 33 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 28 GPM flow rate.<br />

Solution: Order the PICCV-40-028-PT<br />

Example 2: The application requires a 31 GPM flow rate.<br />

Solution: Order the PICCV-40-033-PT and re-program to<br />

the below setting for 31 GPM. As a standard, the<br />

PICCV is available in flows of 26, 28, 30, and 33<br />

GPM. If you desire 31 GPM and have a Normally<br />

Closed (NC) valve, simply reprogram the maximum<br />

setting to 89%, and minimum setting of 0%<br />

as indicated on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-40-026-PT + ARX24-MFT 26 1.64 81% 0%<br />

27 1.70 82% 0%<br />

PICCV-40-028-PT + ARX24-MFT 28 1.77 87% 0%<br />

29 1.83 88% 0%<br />

PICCV-40-030-PT + ARX24-MFT 30 1.89 90% 0%<br />

31 1.96 89% 0%<br />

32 2.02 93% 0%<br />

PICCV-40-033-PT + ARX24-MFT 33 2.08 99% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-40-026-PT + ARX24-MFT 26 1.64 100% 25%<br />

27 1.70 100% 24%<br />

PICCV-40-028-PT + ARX24-MFT 28 1.77 100% 22%<br />

29 1.83 100% 20%<br />

PICCV-40-030-PT + ARX24-MFT 30 1.89 100% 16%<br />

31 1.96 100% 12%<br />

32 2.02 100% 10%<br />

PICCV-40-033-PT + ARX24-MFT 33 2.08 100% 6%<br />

* Preprogrammed at factory<br />

** Customer reprogrammable using MFT PC tool / or can be factory set.<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Non-Spring Return Actuator<br />

1-1/2”, 26 – 33 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Multi-Function<br />

Technology<br />

®<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 26 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-40-026-PT + ARX24-MFT + P-10019.<br />

Engineering Note: The 1-1/2” PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ® . Please follow MFT guideline settings<br />

when configuring the PICCV MFT actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

25


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Non-Spring Return Actuator<br />

2”, 33 – 40 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-50-040-PT can be ordered in 33 GPM to 40 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 33 GPM flow rate.<br />

Solution: Order the PICCV-50-033-PT<br />

Example 2: The application requires a 34 GPM flow rate.<br />

Solution: Order the PICCV-50-040-PT and re-program to the<br />

below setting for 34 GPM. As a standard, the<br />

PICCV is available in flows of 33 GPM and 36 GPM.<br />

If you desire 34 GPM and have a Normally Closed<br />

(NC) valve, simply re-program the maximum setting<br />

to 79%, and a minimum setting of 0% as indicated<br />

on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-033-PT + ARX24-MFT 33 2.08 78% 0%<br />

34 2.14 79% 0%<br />

35 2.21 80% 0%<br />

PICCV-50-036-PT + ARX24-MFT 36 2.27 81% 0%<br />

37 2.33 82% 0%<br />

38 2.40 84% 0%<br />

39 2.46 85% 0%<br />

PICCV-50-040-PT + ARX24-MFT 40 2.52 100% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-033-PT + ARX24-MFT 33 2.08 100% 23%<br />

34 2.14 100% 22%<br />

35 2.21 100% 20%<br />

PICCV-50-036-PT + ARX24-MFT 36 2.27 100% 19%<br />

37 2.33 100% 18%<br />

38 2.40 100% 17%<br />

39 2.46 100% 16%<br />

PICCV-50-040-PT + ARX24-MFT 40 2.52 100% 15%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

Multi-Function<br />

Technology<br />

26<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering,<br />

please specify NO or NC operation.<br />

Selecting the Proper Control Signal:<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 33 GPM, flow rate is required, non-spring<br />

return actuator, 2-10 VDC signal.<br />

Solution: PICCV-50-033-PT + ARX24-MFT + P-10019<br />

Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ®. The PICCV-50-040-PT offers<br />

nominal flow rates that are adjustable from 33 to 40 GPM.<br />

Please follow MFT guideline settings when configuring the<br />

PICCV MFT actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Valve Specifications<br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 1-1/4”, 1-1/2”, 2”<br />

Type of end fitting<br />

Materials:<br />

female, NPT<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seat fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator stainless steel/brass/Delrin 500 AF<br />

Spring stainless steel<br />

Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Standard)<br />

<strong>Pressure</strong> rating 400 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 1-1/4” 18 GPM [1.14 l/s], 20 GPM [1.26 l/s],<br />

22 GPM [1.33 l/s], 24 GPM [1.51 l/s],<br />

26 GPM [1.64 l/s]<br />

Flow rate – 1-1/2” 26 GPM [1.64 l/s], 28 GPM [1.77 l/s],<br />

30 GPM [1.89 l/s], 33 GPM [2.08 l/s]<br />

Flow rate – 2” 33 GPM [2.08 l/s], 36 GPM [2.27 l/s],<br />

40 GPM [2.52 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure<br />

range<br />

5 to 50 PSI<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body Weight of valve body<br />

1-1/4” = 8.31 lbs, 1-1/2” = 7.70 lbs<br />

2” = 9.38 lbs<br />

*Consult page 51 and 52 for flow verification data.<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Spring Return Actuator<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />

used in air handling units on heating and cooling coils, and fan coil<br />

unit heating or cooling coils. Some other common applications<br />

include unit ventilators and VAV re-heat coils. This valve is suitable<br />

for use in a hydronic system with constant or variable flow.<br />

This valve is designed with MFT functionality which facilitates<br />

the use of various control input.<br />

Actuator Specifications<br />

❏ AF24-MFT US<br />

Control MFT<br />

Control signal: 2 to 10 VDC,<br />

(4 to 20 mA with 500Ω resistor)<br />

Power supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power consumption: 6 W running,<br />

2.5 W holding<br />

Transformer sizing: 10 VA, class 2 power<br />

Electrical connection: 3 ft, 18 GA appl. cable, 1/2” conduit fit.<br />

Electrical protection: Aux. switches double insulated<br />

Overload protection: electronic throughout rotation<br />

Input impedance: 100 KΩ for 2 to 10 VDC (0.1 mA)<br />

500Ω for 4 to 20 mA<br />

750Ω for PWM<br />

1500Ω for on/off and floating point<br />

Feedback output: 2 to 10 VDC, 0.5 mA max<br />

Angle of rotation: 95°<br />

Direction of rotation: selected by switch:<br />

CW=CW with decrease signal<br />

CCW=CCW with decrease signal<br />

Spring return direction: CW/CCW mounting<br />

Position indication: visual indicator<br />

Manual override: hex crank<br />

Running time motor:* 100 sec constant<br />

Ambient temperature: -22° F to 122° F [-30° C to 50° C]<br />

Housing: NEMA 2 / IP54<br />

Agency listings: UL 873, CSA C22.2<br />

No. 24 certified, CE<br />

Noise level: max. 45 dB(A)<br />

AF24-MFT-S US<br />

Auxiliary switch 2 x SPDT 5° fixed/25° to 85°,<br />

7A (2.5A) @ 250 VAC<br />

Weight of actuator 6.28 lbs [2.85 Kg]<br />

*PICCV/AF24-MFT US must remain at 100 sec constant run time<br />

27


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Spring Return Actuator<br />

1-1/4”, 18 – 26 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-32-026-PT can be ordered in 18 GPM to 26 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 22 GPM flow rate.<br />

Solution: Order the PICCV-32-022-PT<br />

Example 2: The application requires a 25 GPM flow rate.<br />

Solution: Order the PICCV-32-026-PT and re-program to<br />

the below setting for 25 GPM. As a standard, the<br />

PICCV is available in flows of 18, 20, 22, 24 and<br />

26 GPM. If you desire 25 GPM and have a<br />

Normally Closed (NC) valve, simply reprogram<br />

the maximum setting to 87%, and minimum setting<br />

of 0% as indicated on the chart below.<br />

28<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 22 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-32-022-PT + AF24-MFT US + P-10019.<br />

Engineering Note: The 1-1/4” PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ® . Please follow MFT guideline settings<br />

when configuring the PICCV MFT actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-32-018-PT + AF24-MFT US 18 1.14 78% 0%<br />

19 1.19 79% 0%<br />

PICCV-32-020-PT + AF24-MFT US 20 1.26 80% 0%<br />

21 1.32 82% 0%<br />

PICCV-32-022-PT + AF24-MFT US 22 1.33 83% 0%<br />

23 1.45 84% 0%<br />

PICCV-32-024-PT + AF24-MFT US 24 1.51 85% 0%<br />

25 1.58 87% 0%<br />

PICCV-32-026-PT + AF24-MFT US 26 1.64 92% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-32-018-PT + AF24-MFT US 18 1.14 100% 25%<br />

19 1.19 100% 24%<br />

PICCV-32-020-PT + AF24-MFT US 20 1.26 100% 23%<br />

21 1.32 100% 22%<br />

PICCV-32-022-PT + AF24-MFT US 22 1.33 100% 19%<br />

23 1.45 100% 18%<br />

PICCV-32-024-PT + AF24-MFT US 24 1.51 100% 17%<br />

25 1.58 100% 14%<br />

PICCV-32-026-PT + AF24-MFT US 26 1.64 100% 11%<br />

* Preprogrammed at factory<br />

** Customer reprogrammable using MFT PC tool / or can be factory set.<br />

Multi-Function<br />

Technology<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Selecting the Proper Flow Rate:<br />

The PICCV-40-033-PT can be ordered in 26 GPM to 33 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 28 GPM flow rate.<br />

Solution: Order the PICCV-40-028-PT<br />

Example 2: The application requires a 31 GPM flow rate.<br />

Solution: Order the PICCV-40-033-PT and re-program to<br />

the below setting for 31 GPM. As a standard, the<br />

PICCV is available in flows of 26, 28, 30, and 33<br />

GPM. If you desire 31 GPM and have a Normally<br />

Closed (NC) valve, simply reprogram the maximum<br />

setting to 89%, and minimum setting of 0%<br />

as indicated on the chart below.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-40-026-PT + AF24-MFT US 26 1.64 81% 0%<br />

27 1.70 82% 0%<br />

PICCV-40-028-PT + AF24-MFT US 28 1.77 87% 0%<br />

29 1.83 88% 0%<br />

PICCV-40-030-PT + AF24-MFT US 30 1.89 90% 0%<br />

31 1.96 89% 0%<br />

32 2.02 93% 0%<br />

PICCV-40-033-PT + AF24-MFT US 33 2.08 99% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-40-026-PT + AF24-MFT US 26 1.64 100% 25%<br />

27 1.70 100% 24%<br />

PICCV-40-028-PT + AF24-MFT US 28 1.77 100% 22%<br />

29 1.83 100% 20%<br />

PICCV-40-030-PT + AF24-MFT US 30 1.89 100% 16%<br />

31 1.96 100% 12%<br />

32 2.02 100% 10%<br />

PICCV-40-033-PT + AF24-MFT US 33 2.08 100% 6%<br />

* Preprogrammed at factory<br />

** Customer reprogrammable using MFT PC tool / or can be factory set.<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Spring Return Actuator<br />

1-1/2”, 26 – 33 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Multi-Function<br />

Technology<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering, please<br />

specify NO or NC operation.<br />

Selecting the Proper Control Signal<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 26 GPM flow rate is required, non-spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-40-026-PT + AF24-MFT US + P-10019.<br />

Engineering Note: The 1-1/2” PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ® . Please follow MFT guideline settings<br />

when configuring the PICCV MFT actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

29


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve with<br />

P/T Ports and MFT, Spring Return Actuator<br />

2”, 33 – 40 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-50-040-PT can be ordered in 33 GPM to 40 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 33 GPM flow rate.<br />

Solution: Order the PICCV-50-033-PT<br />

Example 2: The application requires a 34 GPM flow rate.<br />

Solution: Order the PICCV-50-040-PT and re-program to<br />

the below setting for 34 GPM. As a standard, the<br />

PICCV is available in flows of 33 GPM and 36<br />

GPM. If you desire 34 GPM and have a Normally<br />

Closed (NC) valve, simply re-program the maximum<br />

setting to 79%, and a minimum setting of<br />

0% as indicated on the chart below.<br />

30<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering,<br />

please specify NO or NC operation.<br />

Selecting the Proper Control Signal:<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 33 GPM, flow rate is required, non-spring<br />

return actuator, 2-10 VDC signal.<br />

Solution: PICCV-50-033-PT + AF24-MFT US + P-10019<br />

Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ®. The PICCV-50-040-PT offers<br />

nominal flow rates that are adjustable from 33 to 40 GPM.<br />

Please follow MFT guideline settings when configuring the<br />

PICCV MFT actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-033-PT + AF24-MFT US 33 2.08 78% 0%<br />

34 2.14 79% 0%<br />

35 2.21 80% 0%<br />

PICCV-50-036-PT + AF24-MFT US 36 2.27 81% 0%<br />

37 2.33 82% 0%<br />

38 2.40 84% 0%<br />

39 2.46 85% 0%<br />

PICCV-50-040-PT + AF24-MFT US 40 2.52 100% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />

Default* Flow Adjustable**<br />

Flow rate Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-033-PT + AF24-MFT US 33 2.08 100% 23%<br />

34 2.14 100% 22%<br />

35 2.21 100% 20%<br />

PICCV-50-036-PT + AF24-MFT US 36 2.27 100% 19%<br />

37 2.33 100% 18%<br />

38 2.40 100% 17%<br />

39 2.46 100% 16%<br />

PICCV-50-040-PT + AF24-MFT US 40 2.52 100% 15%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

Multi-Function<br />

Technology<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example:AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

Valve Specifications<br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 2” (44 GPM to 100 GPM)<br />

Type of end fitting female, NPT<br />

Materials:<br />

®<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seats fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator components stainless steel/brass/Delrin 500 AF<br />

Spring stainless steel<br />

Pete’s Plugs* Qty (2) 1/4” brass/Nortel (Standard)<br />

Body pressure rating 400 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 2” 44 GPM [2.78 l/s], 48 GPM [3.03 l/s],<br />

52 GPM [3.28 l/s], 56 GPM [3.53 l/s],<br />

60 GPM [3.79 l/s], 65 GPM [4.10 l/s],<br />

70 GPM [4.42 l/s], 75 GPM [4.73 l/s],<br />

80 GPM [5.05 l/s], 90 GPM [5.68 l/s],<br />

100 GPM [6.31 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure 5 to 50 PSI<br />

range<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body 29.1 lbs<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

*Consult page 51 and 52 for flow verification data.<br />

2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with P/T Ports and MFT, Non-Spring Return Actuator<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />

used in air handling units on heating and cooling coils, and fan coil<br />

unit heating or cooling coils. Some other common applications<br />

include unit ventilators and VAV re-heat coils. This valve is suitable<br />

for use in a hydronic system with constant or variable flow.<br />

This valve is designed with MFT functionality which facilitates<br />

the use of various control input.<br />

Actuator Specifications<br />

❏ ARX24-MFT<br />

Power Supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power Consumption 4 W (1.25 W)<br />

Transformer Sizing 6 VA (Class 2 power source)<br />

Electrical Connection 18 GA plenum rated cable<br />

1/2” conduit connector<br />

❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />

Overload Protection electronic throughout 0 to 95° rotation<br />

Operating Range Y 2 to 10 VDC, 4 to 20 mA (default)<br />

Variable (VDC, PWM, Floating Point,<br />

On/Off)<br />

Input Impedance 100 kΩ (0.1 mA), 500Ω<br />

1500 Ω (PWM, Floating Point, On/Off)<br />

Feedback Output U 2 to 10 VDC, 0.5 mA max<br />

VDC Variable<br />

Direction of Rotation reversible with switch<br />

Position Indication handle<br />

Manual Override external push button and handle<br />

Running time motor* 100 sec constant<br />

Humidity 5 to 95% RH non condensing<br />

(EN 60730-1)<br />

Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />

Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />

Housing NEMA 2/IP54<br />

Housing Material UL94-5VA<br />

Agency Listings cULus acc. to UL60730-1A/-2-14,<br />

CAN/CSA E60730-1, CSA C22.2<br />

No. 24-93, CE acc. to 89/336/EEC†<br />

Noise Level


2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with P/T Ports and MFT, Non-Spring Return Actuator<br />

2”, 44 – 100 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-50-080-PT can be ordered in 44 GPM to 80 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 50 GPM flow rate, and a<br />

Normally Closed valve.<br />

Solution: Order the PICCV-50-052-PT<br />

Example 2: The application requires a 56 GPM flow rate.<br />

Solution: Order the PICCV-50-080-PT and re-program to a<br />

maximum setting of 87%, and a minimum setting of<br />

0% as indicated on the chart below.<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering,<br />

please specify NO or NC operation.<br />

32<br />

Selecting the Proper Control Signal:<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 50 GPM, flow rate is required, non-spring<br />

return actuator, 2-10 VDC signal.<br />

Solution: PICCV-50-052-PT + ARX24-MFT + P-10019<br />

Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ® . The PICCV-50-080-PT offers nominal<br />

flow rates that are adjustable from 44 to 80 GPM. Please<br />

follow MFT guideline settings when configuring the PICCV MFT<br />

actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on Y2<br />

Default*<br />

Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-044-PT + ARX24-MFT 44 2.78 82% 0%<br />

PICCV-50-048-PT + ARX24-MFT 48 3.03 84% 0%<br />

PICCV-50-052-PT + ARX24-MFT 52 3.28 85% 0%<br />

PICCV-50-056-PT + ARX24-MFT 56 3.53 87% 0%<br />

PICCV-50-060-PT + ARX24-MFT 60 3.79 89% 0%<br />

PICCV-50-065-PT + ARX24-MFT 65 4.10 91% 0%<br />

PICCV-50-070-PT + ARX24-MFT 70 4.42 94% 0%<br />

PICCV-50-075-PT + ARX24-MFT 75 4.73 97% 0%<br />

PICCV-50-080-PT + ARX24-MFT 80 5.05 99% 0%<br />

PICCV-50-090-PT + ARX24-MFT 90 5.68 94% 0%<br />

PICCV-50-100-PT + ARX24-MFT 100 6.31 100% 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on Y1<br />

Default*<br />

Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-044-PT + ARX24-MFT 44 2.78 100% 28%<br />

PICCV-50-048-PT + ARX24-MFT 48 3.03 100% 26%<br />

PICCV-50-052-PT + ARX24-MFT 52 3.28 100% 24%<br />

PICCV-50-056-PT + ARX24-MFT 56 3.53 100% 22%<br />

PICCV-50-060-PT + ARX24-MFT 60 3.79 100% 20%<br />

PICCV-50-065-PT + ARX24-MFT 65 4.10 100% 17%<br />

PICCV-50-070-PT + ARX24-MFT 70 4.42 100% 13%<br />

PICCV-50-075-PT + ARX24-MFT 75 4.73 100% 10%<br />

PICCV-50-080-PT + ARX24-MFT 80 5.05 100% 1%<br />

PICCV-50-090-PT + ARX24-MFT 90 5.68 100% 11%<br />

PICCV-50-100-PT + ARX24-MFT 100 6.31 100% 0%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

†Note: 2” valves has 2 disc sizes (44 GPM to 80 GPM) (90 GPM to 100 GPM)<br />

Multi-Function<br />

Technology<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: ARX24-MFT is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Valve Specifications<br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 2” (44 GPM - 100 GPM)<br />

Type of end fitting<br />

Materials:<br />

female, NPT<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seats fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator components stainless steel/brass/Delrin 500 AF<br />

Spring stainless steel<br />

Pete’s Plugs* (Qty 2) 1/4” brass/Nortel (Standard)<br />

Body pressure rating 400 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 2” 44 GPM [2.78 l/s], 48 GPM [3.03 l/s],<br />

52 GPM [3.28 l/s], 56 GPM [3.53 l/s],<br />

60 GPM [3.79 l/s], 65 GPM [4.10 l/s],<br />

70 GPM [4.42 l/s], 75 GPM [4.73 l/s],<br />

80 GPM [5.05 l/s], 90 GPM [5.68 l/s],<br />

100 GPM [6.31 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure<br />

range<br />

5 to 50 PSI<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body 29.1 lbs<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

*Consult page 51 and 52 for flow verification data.<br />

2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with P/T Ports and MFT, Spring Return Actuator<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve is typically<br />

used in air handling units on heating and cooling coils, and fan coil<br />

unit heating or cooling coils. Some other common applications<br />

include unit ventilators and VAV re-heat coils. This valve is suitable<br />

for use in a hydronic system with constant or variable flow.<br />

This valve is designed with MFT functionality which facilitates<br />

the use of various control input.<br />

Actuator Specifications<br />

❏ AF24-MFT US<br />

Control MFT<br />

Control signal: 2 to 10 VDC,<br />

(4 to 20 mA with 500Ω resistor)<br />

Power supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power consumption: 6 W running,<br />

2.5 W holding<br />

Transformer sizing: 10 VA, class 2 power<br />

Electrical connection: 3 ft, 18 GA appl. cable, 1/2” conduit fit.<br />

Electrical protection: Aux. switches double insulated<br />

Overload protection: electronic throughout rotation<br />

Input impedance: 100 KΩ for 2 to 10 VDC (0.1 mA)<br />

500Ω for 4 to 20 mA<br />

750Ω for PWM<br />

1500Ω for on/off and floating point<br />

Feedback output: 2 to 10 VDC, 0.5 mA max<br />

Angle of rotation: 95°<br />

Direction of rotation: selected by switch:<br />

CW=CW with decrease signal<br />

CCW=CCW with decrease signal<br />

Spring return direction: CW/CCW mounting<br />

Position indication: visual indicator<br />

Manual override: hex crank<br />

Auxiliary switches: 2 x SPDT. 5° fixed/25° to 85°(-S)<br />

Running time motor:* 100 sec constant<br />

Ambient temperature: -22° F to 122° F [-30° C to 50° C]<br />

Housing: NEMA 2 / IP54<br />

Agency listings: UL 873, CSA C22.2<br />

No. 24 certified, CE<br />

Noise level: max. 45 dB(A)<br />

AF24-MFT-S US<br />

Auxiliary switch 2 x SPDT 5° fixed/25° to 85°,<br />

7A (2.5A) @ 250 VAC<br />

Weight of actuator 6.28 lbs [2.85 Kg]<br />

*PICCV/AF24-MFT US must remain at 100 sec constant run time<br />

LISTED<br />

94D5<br />

TEMP. IND & UL ®<br />

REG. EQUIP.<br />

©<br />

MFT<br />

33


2” <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with P/T Ports and MFT, Spring Return Actuator<br />

2”, 44 – 100 GPM<br />

The PICCV has a unique feature in that the GPM can be adjusted by adjusting the minimum and maximum settings.<br />

Selecting the Proper Flow Rate:<br />

The PICCV-50-080-PT can be ordered in 44 GPM to 80 GPM<br />

flow rate increments, as stated in the table below.<br />

If you wish to re-program to the values listed in the table below:<br />

Example 1: The application requires a 50 GPM flow rate, and a<br />

Normally Closed valve.<br />

Solution: Order the PICCV-50-052-PT<br />

Example 2: The application requires a 56 GPM flow rate.<br />

Solution: Order the PICCV-50-080-PT and re-program to a<br />

maximum setting of 81%, and a minimum setting of<br />

0% as indicated on the chart below.<br />

Please note that the settings are different for Normally Closed<br />

(NC) and Normally Open (NO) operation. When ordering,<br />

please specify NO or NC operation.<br />

34<br />

MFT Adjustment Table NC will open as voltage increases (no flow at 0-2V) - actuator switch on CW<br />

Default*<br />

Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-044-PT + AF24-MFT US 44 2.78 75% 0%<br />

PICCV-50-048-PT + AF24-MFT US 48 3.03 77% 0%<br />

PICCV-50-052-PT + AF24-MFT US 52 3.28 78% 0%<br />

PICCV-50-056-PT + AF24-MFT US 56 3.53 81% 0%<br />

PICCV-50-060-PT + AF24-MFT US 60 3.79 83% 0%<br />

PICCV-50-065-PT + AF24-MFT US 65 4.10 85% 0%<br />

PICCV-50-070-PT + AF24-MFT US 70 4.42 88% 0%<br />

PICCV-50-075-PT + AF24-MFT US 75 4.73 92% 0%<br />

PICCV-50-080-PT + AF24-MFT US 80 5.05 100% 0%<br />

PICCV-50-090-PT + AF24-MFT US 90 5.68 FO 93%, FC 89% FO, FC 0%<br />

PICCV-50-100-PT + AF24-MFT US 100 6.31 FO, FC 100% FO, FC 0%<br />

MFT Adjustment Table NO will close as voltage increases (no flow at 10V) - actuator switch on CCW<br />

Default*<br />

Flow rate MFT angle of MFT angle of<br />

Product Range GPM l/s rotation max. setting rotation min. setting<br />

PICCV-50-044-PT + AF24-MFT US 44 2.78 100% 24%<br />

PICCV-50-048-PT + AF24-MFT US 48 3.03 100% 22%<br />

PICCV-50-052-PT + AF24-MFT US 52 3.28 100% 21%<br />

PICCV-50-056-PT + AF24-MFT US 56 3.53 100% 19%<br />

PICCV-50-060-PT + AF24-MFT US 60 3.79 100% 17%<br />

PICCV-50-065-PT + AF24-MFT US 65 4.10 100% 13%<br />

PICCV-50-070-PT + AF24-MFT US 70 4.42 100% 11%<br />

PICCV-50-075-PT + AF24-MFT US 75 4.73 100% 2%<br />

PICCV-50-080-PT + AF24-MFT US 80 5.05 100% 0%<br />

PICCV-50-090-PT + AF24-MFT US 90 5.68 FO, FC 100% FO 12%, FC 16%<br />

PICCV-50-100-PT + AF24-MFT US 100 6.31 FO, FC 100% FO, FC 0%<br />

*Preprogrammed at factory **Customer reprogrammable using MFT PC tool / or can be factory set.<br />

†Note: 2” valves has 2 disc sizes (44 GPM to 80 GPM) (90 GPM to 100 GPM)<br />

Multi-Function<br />

Technology<br />

Selecting the Proper Control Signal:<br />

Select one of the MFT codes below for the signal required.<br />

Example: A 50 GPM, flow rate is required, spring return<br />

actuator, 2-10 VDC signal.<br />

Solution: PICCV-50-052-PT + AF24-MFT US + P-10019<br />

Engineering Note: The 2" PICCV utilizes a uniquely engineered<br />

valve body to achieve the listed flow rate offerings.<br />

Variable GPMs are further realized using Belimo’s registered<br />

Multi-Function Technology ® . The PICCV-50-080-PT offers nominal<br />

flow rates that are adjustable from 44 to 80 GPM. Please<br />

follow MFT guideline settings when configuring the PICCV MFT<br />

actuators in the field.<br />

Note: Minimum and Maximum Settings differ for the<br />

ARX24-MFT and AF24-MFT US actuators.<br />

For complete technical information and list of configuration codes refer to<br />

Product <strong>Documentation</strong> Multi-Function Technology ® For Damper and Control Valve Applications<br />

Model Control Input Running Time Built-in Feedback List Price<br />

P-10019 2-10 VDC 100 2-10 VDC No Charge<br />

P-10028 0-10 VDC 100 0-10 VDC No Charge<br />

P-20031 0.02-5.00 sec. PWM 100 2-10 VDC No Charge<br />

P-20032 0.10-25.5 sec. PWM 100 2-10 VDC No Charge<br />

P-20034 0.59-2.93 sec. PWM 100 2-10 VDC No Charge<br />

P-30003 Floating Point 100 2-10 VDC No Charge<br />

P-10019* On/Off 100 2-10 VDC No Charge<br />

Example: AF24-MFT US is the basic model. Add the P… pre-set MFT configuration number and list price to the actuator when ordering, as needed.<br />

Note: Most popular configurations available at no additional cost. All other configurations carry a $30.00 list price.<br />

*Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

PICCV-15-0.50 (-PT) Normally Closed<br />

0.50<br />

0.45<br />

0.40<br />

0.35<br />

0.30<br />

0.25<br />

0.20<br />

0.15<br />

0.10<br />

0.05<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-15-001 (-PT) Normally Closed<br />

1.00<br />

0.90<br />

0.80<br />

0.70<br />

0.60<br />

0.50<br />

0.40<br />

0.30<br />

0.20<br />

0.10<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-15-0.50 (-PT) to PICCV-15-001 (-PT) (.5 to 1 GPM)<br />

NEW ♦<br />

NEW ♦<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

♦ Please use “NEW” if the order was placed after July 24, 2007.<br />

PICCV-15-0.50 (-PT) Normally Open<br />

0.50<br />

0.45<br />

0.40<br />

0.35<br />

0.30<br />

0.25<br />

0.20<br />

0.15<br />

0.10<br />

0.05<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-15-001 (-PT) Normally Open<br />

1.00<br />

0.90<br />

0.80<br />

0.70<br />

0.60<br />

0.50<br />

0.40<br />

0.30<br />

0.20<br />

0.10<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

NEW ♦<br />

NEW ♦<br />

35


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-15-1.50 (-PT) to PICCV-15-003 (-PT) (1.5 to 3 GPM)<br />

36<br />

1.50<br />

1.25<br />

1.00<br />

0.75<br />

0.50<br />

0.25<br />

2.00<br />

1.75<br />

1.50<br />

1.25<br />

1.00<br />

0.75<br />

0.50<br />

0.25<br />

PICCV-15-002 (-PT) Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

PICCV-15-1.50 (-PT) Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Feedback (Volts)<br />

PICCV-15-003 (-PT) Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

1.50<br />

1.25<br />

1.00<br />

0.75<br />

0.50<br />

0.25<br />

2.00<br />

1.75<br />

1.50<br />

1.25<br />

1.00<br />

0.75<br />

0.50<br />

0.25<br />

PICCV-15-002 (-PT) Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

PICCV-15-1.50 (-PT) Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Feedback (Volts)<br />

PICCV-15-003 (-PT) Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

®<br />

PICCV-15-004 (-PT) Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-15-005 (-PT) Normally Closed<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-15-004 (-PT) to PICCV-15-005 (-PT) (4 to 5 GPM)<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

PICCV-15-004 (-PT) Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-15-005 (-PT) Normally Open<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Feedback (Volts)<br />

37


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-20-006 (-PT) to PICCV-20-008 (-PT) (6 to 8 GPM)<br />

38<br />

PICCV-20-006 (-PT) Normally Closed<br />

6.00<br />

5.50<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-20-007 (-PT) Normally Closed<br />

7.00<br />

6.50<br />

6.00<br />

5.50<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-20-008 (-PT) Normally Closed<br />

8.00<br />

7.50<br />

7.00<br />

6.50<br />

6.00<br />

5.50<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-20-006 (-PT) Normally Open<br />

6.00<br />

5.50<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-20-007 (-PT) Normally Open<br />

7.00<br />

6.50<br />

6.00<br />

5.50<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-20-008 (-PT) Normally Open<br />

8.00<br />

7.50<br />

7.00<br />

6.50<br />

6.00<br />

5.50<br />

5.00<br />

4.50<br />

4.00<br />

3.50<br />

3.00<br />

2.50<br />

2.00<br />

1.50<br />

1.00<br />

0.50<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

®<br />

PICCV-20-009 (-PT) Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

0.00<br />

Feedback (Volts)<br />

PICCV-20-010 (-PT) Normally Closed<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-20-009 (-PT) to PICCV-20-010 (-PT) (9 to 10 GPM)<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

PICCV-20-009 (-PT) Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

Feedback (Volts)<br />

PICCV-20-010 (-PT) Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

39


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-25-012 (-PT) to PICCV-25-014 (-PT) (12 to 14 GPM)<br />

40<br />

PICCV-25-012 (-PT) Normally Closed<br />

12.00<br />

11.00<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-25-014 (-PT) Normally Closed<br />

14.00<br />

13.00<br />

12.00<br />

11.00<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-25-012 (-PT) Normally Open<br />

12.00<br />

11.00<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-25-014 (-PT) Normally Open<br />

14.00<br />

13.00<br />

12.00<br />

11.00<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® Feedback<br />

PICCV-25-016 (-PT) Normally Closed<br />

16.00<br />

15.00<br />

14.00<br />

13.00<br />

12.00<br />

11.00<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

0.00<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

Feedback (Volts)<br />

PICCV-25-018-PT Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Charts for PICCVs with MFT Actuator<br />

PICCV-25-016 (-PT) to PICCV-25-018 (-PT) (16 to 18 GPM)<br />

PICCV-25-016 (-PT) Normally Open<br />

16.00<br />

15.00<br />

14.00<br />

13.00<br />

12.00<br />

11.00<br />

10.00<br />

9.00<br />

8.00<br />

7.00<br />

6.00<br />

5.00<br />

4.00<br />

3.00<br />

2.00<br />

1.00<br />

0.00<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

Feedback (Volts)<br />

PICCV-25-018-PT Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

41


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-32-018-PT to PICCV-32-022-PT (18 to 22 GPM)<br />

42<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

PICCV-32-018-PT Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

Feedback (Volts)<br />

PICCV-32-020-PT Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-32-022-PT Normally Closed<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

PICCV-32-018-PT Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

Feedback (Volts)<br />

PICCV-32-020-PT Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-32-022-PT Normally Open<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® Feedback<br />

PICCV-32-024-PT Normally Closed<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-32-026-PT Normally Closed<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Charts for PICCVs with MFT Actuator<br />

PICCV-32-024-PT to PICCV-32-026-PT (24 to 26 GPM)<br />

PICCV-32-024-PT Normally Open<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-32-026-PT Normally Open<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

43


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-40-026-PT to PICCV-40-028-PT (26 to 28 GPM)<br />

44<br />

PICCV-40-026-PT Normally Closed<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-40-028-PT Normally Closed<br />

28.00<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-40-026-PT Normally Open<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

PICCV-40-028-PT Normally Open<br />

28.00<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

PICCV-40-030-PT Normally Closed<br />

30.00<br />

28.00<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-40-033-PT Normally Closed<br />

33.00<br />

30.00<br />

27.00<br />

24.00<br />

21.00<br />

18.00<br />

15.00<br />

12.00<br />

9.00<br />

6.00<br />

3.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-40-030-PT to PICCV-40-033-PT (30 to 33 GPM)<br />

PICCV-40-030-PT Normally Open<br />

30.00<br />

28.00<br />

26.00<br />

24.00<br />

22.00<br />

20.00<br />

18.00<br />

16.00<br />

14.00<br />

12.00<br />

10.00<br />

8.00<br />

6.00<br />

4.00<br />

2.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

PICCV-40-033-PT Normally Open<br />

33.00<br />

30.00<br />

27.00<br />

24.00<br />

21.00<br />

18.00<br />

15.00<br />

12.00<br />

9.00<br />

6.00<br />

3.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

45


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-50-033-PT to PICCV-50-040-PT (33 to 40 GPM)<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

46<br />

PICCV-50-033-PT Normally Closed<br />

33.00<br />

30.00<br />

27.00<br />

24.00<br />

21.00<br />

18.00<br />

15.00<br />

12.00<br />

9.00<br />

6.00<br />

3.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-50-036-PT Normally Closed<br />

36.00<br />

33.00<br />

30.00<br />

27.00<br />

24.00<br />

21.00<br />

18.00<br />

15.00<br />

12.00<br />

9.00<br />

6.00<br />

3.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

40.00<br />

36.00<br />

32.00<br />

28.00<br />

24.00<br />

20.00<br />

16.00<br />

12.00<br />

8.00<br />

4.00<br />

Feedback (Volts)<br />

PICCV-50-040-PT Normally Closed<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-50-033-PT Normally Open<br />

33.00<br />

30.00<br />

27.00<br />

24.00<br />

21.00<br />

18.00<br />

15.00<br />

12.00<br />

9.00<br />

6.00<br />

3.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-50-036-PT Normally Open<br />

36.00<br />

33.00<br />

30.00<br />

27.00<br />

24.00<br />

21.00<br />

18.00<br />

15.00<br />

12.00<br />

9.00<br />

6.00<br />

3.00<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

40.00<br />

36.00<br />

32.00<br />

28.00<br />

24.00<br />

20.00<br />

16.00<br />

12.00<br />

8.00<br />

4.00<br />

Feedback (Volts)<br />

PICCV-50-040-PT Normally Open<br />

0.00<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

®<br />

Feedback<br />

PICCV-50-044-PT Normally Closed<br />

0.0<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-50-048-PT Normally Closed<br />

48.0<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

0.0<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-50-052-PT Normally Closed<br />

52.0<br />

48.0<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

0.0<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

Charts for PICCVs with MFT Actuator<br />

PICCV-50-044-PT to PICCV-50-052-PT (44 to 52 GPM)<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

PICCV-50-044-PT Normally Open<br />

0.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Feedback (Volts)<br />

PICCV-50-048-PT Normally Open<br />

48.0<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

0.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Feedback (Volts)<br />

PICCV-50-052-PT Normally Open<br />

52.0<br />

48.0<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

0.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

47


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-50-056-PT to PICCV-50-065-PT (56 to 65 GPM)<br />

48<br />

PICCV-50-056-PT Normally Closed<br />

56.0<br />

52.0<br />

48.0<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

0.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Feedback (Volts)<br />

PICCV-50-060-PT Normally Closed<br />

60.0<br />

55.0<br />

50.0<br />

45.0<br />

40.0<br />

35.0<br />

30.0<br />

25.0<br />

20.0<br />

15.0<br />

10.0<br />

5.0<br />

0.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Feedback (Volts)<br />

PICCV-50-065-PT Normally Closed<br />

65.0<br />

60.0<br />

55.0<br />

50.0<br />

45.0<br />

40.0<br />

35.0<br />

30.0<br />

25.0<br />

20.0<br />

15.0<br />

10.0<br />

5.0<br />

0.0<br />

2 3 4 5 6 7 8 9 10<br />

Feedback (Volts)<br />

PICCV-50-056-PT Normally Open<br />

56.0<br />

52.0<br />

48.0<br />

44.0<br />

40.0<br />

36.0<br />

32.0<br />

28.0<br />

24.0<br />

20.0<br />

16.0<br />

12.0<br />

8.0<br />

4.0<br />

0.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Feedback (Volts)<br />

PICCV-50-060-PT Normally Open<br />

60.0<br />

55.0<br />

50.0<br />

45.0<br />

40.0<br />

35.0<br />

30.0<br />

25.0<br />

20.0<br />

15.0<br />

10.0<br />

5.0<br />

0.0<br />

2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />

Feedback (Volts)<br />

PICCV-50-065-PT Normally Open<br />

65.0<br />

60.0<br />

55.0<br />

50.0<br />

45.0<br />

40.0<br />

35.0<br />

30.0<br />

25.0<br />

20.0<br />

15.0<br />

10.0<br />

5.0<br />

0.0<br />

2 3 4 5 6 7 8 9 10<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

Feedback (Volts)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-50-070-PT to PICCV-50-080-PT (70 to 80 GPM)<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

49


Feedback Charts for PICCVs with MFT Actuator<br />

PICCV-50-090-PT to PICCV-50-100-PT (90 to 100 GPM)<br />

Note: Set point does not equal feedback on the TF24-MFT US, LF24-MFT US and AF24-MFT US.<br />

Set point does equal the feedback for the New Generation LRX24-MFT and ARX24-MFT.<br />

50<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Field Adjustable Flow Ranges<br />

with the LRB24-3 and FlowSetR<br />

Default<br />

Model # Flow Rate Field Adjustable<br />

Valve (GPM)* Design Flow (GPM)**<br />

PICCV-15-0.50 (-PT) 0.5<br />

PICCV-15-001 (-PT) 1<br />

PICCV-15-1.50 (-PT) 1.5<br />

PICCV-15-002 (-PT) 2<br />

0.5 to 1.3<br />

PICCV-15-003 (-PT) 3 0.5 to 5.5<br />

PICCV-15-004 (-PT) 4<br />

PICCV-15-005 (-PT) 5<br />

PICCV-20-006 (-PT) 6<br />

PICCV-20-007 (-PT) 7<br />

PICCV-20-008 (-PT) 8 2 to 10<br />

PICCV-20-009 (-PT) 9<br />

PICCV-20-010 (-PT) 10<br />

PICCV-25-012 (-PT) 12<br />

PICCV-25-014 (-PT) 14 2 to 16<br />

PICCV-25-016 (-PT) 16<br />

Procedure:<br />

(1) Adjust valve to its full<br />

rated GPM opening.<br />

(2) Measure pressure<br />

across P/T ports.<br />

(3) For default flow rate,<br />

compare DeltaP to<br />

chart value.<br />

P/T ports to<br />

verify flow<br />

PICCV-25-018 (-PT) 18 6 to 19<br />

*The indicated default flows are maximum flow values at 100%<br />

actuator travel. However, the PICCV maintains a steady flow<br />

at any degree of ball opening and balances the system<br />

dynamically from 0 to 100% of the heating or cooling load.<br />

**Specified accuracy not guaranteed.<br />

Field Adjustable Flow Ranges and<br />

P/T Port <strong>Pressure</strong> Flow Data<br />

P/T Port <strong>Pressure</strong> Flow Data<br />

Model # Flow Rate DeltaP across<br />

Valve (GPM) P/T Ports<br />

PICCV-15-0.50 (-PT) 0.5 3.0 - 3.9<br />

PICCV-15-001 (-PT) 1 2.95 - 3.4<br />

PICCV-15-0.50 (-PT) 0.5 3.3 - 4.7 NEW ♦<br />

PICCV-15-001 (-PT) 1 3.0 - 4.4 NEW ♦<br />

PICCV-15-1.50 (-PT) 1.5 2.5 - 5.5<br />

PICCV-15-002 (-PT) 2 2.5 - 5.5<br />

PICCV-15-003 (-PT) 3 2.0 - 3.2<br />

PICCV-15-004 (-PT) 4 1.9 - 2.7<br />

PICCV-15-005 (-PT) 5 1.5 - 2.4<br />

PICCV-20-006 (-PT) 6 2.5 - 3.0<br />

PICCV-20-007 (-PT) 7 2.5 - 2.8<br />

PICCV-20-008 (-PT) 8 2.2 - 2.6<br />

PICCV-20-009 (-PT) 9 1.6 - 2.4<br />

PICCV-20-010 (-PT) 10 0.0 - 2.3<br />

PICCV-25-012 (-PT) 12 2.75 - 3.2<br />

PICCV-25-014 (-PT) 14 2.4 - 2.8<br />

PICCV-25-016 (-PT) 16 1.45 - 1.75<br />

PICCV-25-018 (-PT) 18 1.20 - 1.70<br />

PICCV-32-018-PT 18 3.35 - 3.65<br />

PICCV-32-020-PT 20 3.0 - 3.5<br />

PICCV-32-022-PT 22 2.85 - 3.5<br />

PICCV-32-024-PT 24 2.85 - 3.65<br />

PICCV-32-026-PT 26 3.0 - 3.85<br />

PICCV-40-026-PT 26 3.1 - 3.9<br />

PICCV-40-028-PT 28 3.1 - 3.8<br />

PICCV-40-030-PT 30 3.0 - 3.4<br />

PICCV-40-033-PT 33 2.9 - 3.7<br />

PICCV-50-033-PT 33 2.1 - 2.95<br />

PICCV-50-036-PT 36 2.0 - 2.9<br />

PICCV-50-040-PT 40 2.0 - 2.85<br />

PICCV-50-044-PT 44 3.5 - 4.0<br />

PICCV-50-048-PT 48 2.0 - 4.0<br />

PICCV-50-052-PT 52 2.2 - 3.2<br />

PICCV-50-056-PT 56 1.2 - 3.0<br />

PICCV-50-060-PT 60 1.2 - 2.5<br />

PICCV-50-065-PT 65 1.0 - 3.0<br />

PICCV-50-070-PT 70 1.0 - 2.9<br />

PICCV-50-075-PT 75 1.0 - 2.5<br />

PICCV-50-080-PT 80 1.3 - 3.0<br />

PICCV-50-090-PT 90 2.6 - 3.8<br />

PICCV-50-100-PT 100 2.0 - 3.4<br />

♦ Please use “NEW” readings if order was placed after<br />

July 24, 2007.<br />

51


Field Adjustable Flow Ranges and<br />

P/T Port <strong>Pressure</strong> Flow Data for Customized Flows<br />

Field Adjustable Flow Ranges<br />

with the LRB24-3 and FlowSetR<br />

Default<br />

Model # Flow Rate Field Adjustable<br />

Valve (GPM)* Design Flow (GPM)**<br />

PICCV-15-2.50 (-PT) 2.5<br />

PICCV-15-3.50 (-PT)<br />

PICCV-15-4.50 (-PT)<br />

3.5<br />

4.5<br />

0.5 to 5.5<br />

PICCV-15-5.50 (-PT) 5.5<br />

PICCV-20-6.50 (-PT) 6.5<br />

PICCV-20-7.50 (-PT) 7.5<br />

PICCV-20-8.50 (-PT) 8.5<br />

PICCV-20-9.50 (-PT) 9.5<br />

52<br />

Procedure:<br />

(1) Adjust valve to its full<br />

rated GPM opening.<br />

(2) Measure pressure<br />

across P/T ports.<br />

(3) For default flow rate,<br />

compare DeltaP to<br />

chart value.<br />

P/T ports to<br />

verify flow<br />

2 to 10<br />

PICCV-25-011 (-PT) 11<br />

PICCV-25-013 (-PT) 13 2 to 16<br />

PICCV-25-015 (-PT) 15<br />

PICCV-25-017 (-PT) 17<br />

6 to 19<br />

PICCV-25-019 (-PT) 19<br />

*The indicated default flows are maximum flow values at 100%<br />

actuator travel. However, the PICCV maintains a steady flow<br />

at any degree of ball opening and balances the system<br />

dynamically from 0 to 100% of the heating or cooling load.<br />

**Specified accuracy not guaranteed.<br />

P/T Port <strong>Pressure</strong> Flow Data<br />

Model # Flow Rate DeltaP across<br />

Valve (GPM) P/T Ports<br />

PICCV-15-2.50 (-PT) 2.5 2.0 - 3.2<br />

PICCV-15-3.50 (-PT) 3.5 1.9 - 2.7<br />

PICCV-15-4.50 (-PT) 4.5 1.5 - 2.4<br />

PICCV-15-5.50 (-PT) 5.5 1.5 - 2.4<br />

PICCV-20-6.50 (-PT) 6.5 2.5 - 2.8<br />

PICCV-20-7.50 (-PT) 7.5 2.2 - 2.6<br />

PICCV-20-8.50 (-PT) 8.5 1.6 - 2.4<br />

PICCV-20-9.50 (-PT) 9.5 0.0 - 2.3<br />

PICCV-25-011 (-PT) 11 2.75 - 3.2<br />

PICCV-25-013 (-PT) 13 2.4 - 2.8<br />

PICCV-25-015 (-PT) 15 1.45 - 1.75<br />

PICCV-25-017 (-PT) 17 1.20 - 1.70<br />

PICCV-25-019 (-PT) 19 1.20 - 1.70<br />

PICCV-32-019-PT 19 3.0 - 3.5<br />

PICCV-32-021-PT 21 2.85 - 3.5<br />

PICCV-32-023-PT 23 2.85 - 3.65<br />

PICCV-32-025-PT 25 3.0 - 3.85<br />

PICCV-40-027-PT 27 3.1 - 3.8<br />

PICCV-40-029-PT 29 3.0 - 3.4<br />

PICCV-40-031-PT 31 2.9 - 3.7<br />

PICCV-40-032-PT 32 2.9 - 3.7<br />

PICCV-50-034-PT 34 2.0 - 2.9<br />

PICCV-50-035-PT 35 2.0 - 2.9<br />

PICCV-50-037-PT 37 2.0 - 2.9<br />

PICCV-50-038-PT 38 2.0 - 2.9<br />

PICCV-50-039-PT 39 2.0 - 2.9<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

Customized Flows*<br />

® Available<br />

PICCV’s are available in a wide variety of the standard maximum<br />

flow rates as listed. This allows you to match the design<br />

flow rate much more accurately then it was possible with the<br />

selection of Cv-value of a conventional valve. If you want to<br />

customize the maximum flow rate of a PICCV you can do so,<br />

as noted in the increments in the table below. In an additional<br />

process we will set the PICCV to a specific flow rate to match<br />

your design flow, as noted in the table below. The smallest<br />

available increment is 0.50 GPM and the smallest flow is<br />

0.50 GPM.<br />

Customized Flows and<br />

Certified Factory Calibrated Flows<br />

Certified Factory Calibrated Flows† (ZP-PICCV-CAL)<br />

Valve Size GPM Custom Flow Rates Actuator selections<br />

1/2” 2.5, 3.5, 4.5, 5.5<br />

LRB24-3, LRCX24-3, LRX24-MFT, ARX24-MFT<br />

TF24-MFT US, LF24-MFT US, AF24-MFT US<br />

3/4” 6.5, 7.5, 8.5, 9.5<br />

LRB24-3, LRCX24-3, LRX24-MFT, ARX24-MFT<br />

LF24-MFT US, AF24-MFT US<br />

1” 11, 13, 15, 17, 19<br />

LRB24-3, LRCX24-3, LRX24-MFT, ARX24-MFT<br />

LF24-MFT US, AF24-MFT US<br />

1-1/4” 19, 21, 23, 25 ARX24-MFT, AF24-MFT US<br />

1-1/2” 27, 29, 31, 32 ARX24-MFT, AF24-MFT US<br />

2” 34, 35, 37, 38, 39 ARX24-MFT, AF24-MFT US<br />

ORDERING EXAMPLE<br />

1<br />

2<br />

Available Customized Flows*<br />

Choose the desired valve/actuator combination<br />

based on valve ratings and actuator control<br />

parameters.<br />

PICCV-15-3.50-PT + LRX24-MFT<br />

Specify Configuration (important)<br />

• Multi-Function Technology: P-10019 (2-10 VDC input / 2-10 VDC feedback)<br />

• Set-up: NC (Normally Closed)<br />

• Tagging: AHU<br />

• Calibration Charge: ZP-PICCV-CAL<br />

Factory calibrated PICCV’s will be programmed to a customized<br />

flow setting as mentioned in the opposite paragraph.<br />

Additionally, each single valve will be installed in a calibration<br />

rig to verify the flow rate with a high quality flow measurement<br />

device, calibrated to the requirements of ANSI/ISA -75.02-<br />

1996, with traceability to NIST standards. For each PICCV<br />

calibrated you will receive a test certificate. Using this procedure<br />

allows for the highest flow accuracy in the field.<br />

†Operating pressure ranges are 5-10 psi,10-30 psi, 30-50 psi.<br />

Default pressure range is 5-30 psi.<br />

Expected flow accuracy ±5% (related to nominal valve flow).<br />

This service is available for the 1/2” to 1-1/4” PICCV15-0.50 (-PT)<br />

to PICCV-32-026-PT.<br />

*Part numbers for the<br />

valve body custom flows<br />

are noted in the charts<br />

on page 52. Actuator<br />

selections are the same<br />

as the standard offerings.<br />

PICCV-15-3.50+LRX24-MFT+P-10019+NC+AHU+ZP-PICCV-CAL<br />

53


PICCV Running Times<br />

All MFT actuators have constant running time of 100 seconds. Whether they are set for on/off, floating<br />

or proportional control, the running time remains constant.<br />

Note for Floating Point Control with LRB24-3: These actuators have a constant running time. The running<br />

time is dependent on the model number or FlowSetR position as indicated in the table below.<br />

Some DDC controllers need an adjustment of the running time, otherwise they lose the position information.<br />

In any case, we recommend a position reset once a day.<br />

Running Time (sec.) Running Time (sec.)<br />

Model # Flow Rate LRX24-MFT, ARX24-MFT<br />

Valve (GPM) LRB24-3 TF24-MFT US, LF24-MFT US, AF24-MFT US<br />

PICCV-15-0.50 (-PT) 0.5 36 100<br />

PICCV-15-001 (-PT) 1 60 100<br />

PICCV-15-1.50 (-PT) 1.5 45 100<br />

PICCV-15-002 (-PT) 2 51 100<br />

PICCV-15-003 (-PT) 3 56 100<br />

PICCV-15-004 (-PT) 4 63 100<br />

PICCV-15-005 (-PT) 5 68 100<br />

PICCV-20-006 (-PT) 6 61 100<br />

PICCV-20-007 (-PT) 7 64 100<br />

PICCV-20-008 (-PT) 8 67 100<br />

PICCV-20-009 (-PT) 9 69 100<br />

PICCV-20-010 (-PT) 10 76 100<br />

PICCV-25-012 (-PT) 12 62 100<br />

PICCV-25-014 (-PT) 14 67 100<br />

PICCV-25-016 (-PT) 16 86 100<br />

PICCV-25-018 (-PT) 18 67 100<br />

PICCV-32-018-PT 18 na 100<br />

PICCV-32-020-PT 20 na 100<br />

PICCV-32-022-PT 22 na 100<br />

PICCV-32-024-PT 24 na 100<br />

PICCV-32-026-PT 26 na 100<br />

PICCV-40-026-PT 26 na 100<br />

PICCV-40-028-PT 28 na 100<br />

PICCV-40-030-PT 30 na 100<br />

PICCV-40-033-PT 33 na 100<br />

PICCV-50-033-PT 33 na 100<br />

PICCV-50-036-PT 36 na 100<br />

PICCV-50-040-PT 40 na 100<br />

PICCV-50-044-PT 44 na 100<br />

PICCV-50-048-PT 48 na 100<br />

PICCV-50-052-PT 52 na 100<br />

PICCV-50-056-PT 56 na 100<br />

PICCV-50-060-PT 60 na 100<br />

PICCV-50-065-PT 65 na 100<br />

PICCV-50-070-PT 70 na 100<br />

PICCV-50-075-PT 75 na 100<br />

PICCV-50-080-PT 80 na 100<br />

PICCV-50-090-PT 90 na 100<br />

PICCV-50-100-PT 100 na 100<br />

54<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® PICCV<br />

Customized Flow Rate Running Times<br />

Running Time (sec.) Running Time (sec.)<br />

Model # Flow Rate LRX24-MFT, ARX24-MFT<br />

Valve (GPM) LRB24-3 TF24-MFT US, LF24-MFT US, AF24-MFT US<br />

PICCV-15-2.50 (-PT) 2.5 53 100<br />

PICCV-15-3.50 (-PT) 3.5 58 100<br />

PICCV-15-4.50 (-PT) 4.5 66 100<br />

PICCV-15-5.50 (-PT) 5.5 73 100<br />

PICCV-20-6.50 (-PT) 6.5 62 100<br />

PICCV-20-7.50 (-PT) 7.5 66 100<br />

PICCV-20-8.50 (-PT) 8.5 68 100<br />

PICCV-20-9.50 (-PT) 9.5 71 100<br />

PICCV-25-011 (-PT) 11 60 100<br />

PICCV-25-013 (-PT) 13 64 100<br />

PICCV-25-015 (-PT) 15 69 100<br />

PICCV-25-017 (-PT) 17 65 100<br />

PICCV-25-019 (-PT) 19 78 100<br />

PICCV-32-019-PT 19 na 100<br />

PICCV-32-021-PT 21 na 100<br />

PICCV-32-023-PT 23 na 100<br />

PICCV-32-025-PT 25 na 100<br />

PICCV-40-027-PT 27 na 100<br />

PICCV-40-029-PT 29 na 100<br />

PICCV-40-031-PT 31 na 100<br />

PICCV-40-032-PT 32 na 100<br />

PICCV-50-034-PT 34 na 100<br />

PICCV-50-035-PT 35 na 100<br />

PICCV-50-037-PT 37 na 100<br />

PICCV-50-038-PT 38 na 100<br />

PICCV-50-039-PT 39 na 100<br />

55


Instructions for Field Adjustment of Flow and<br />

Valve Sizing and Selection<br />

Instructions for Non-Spring Actuator Utilizing the FlowSetR<br />

Non-Spring Return Actuator: LRB24-3<br />

Default set-up:<br />

FlowSetR<br />

The factory setting corresponds to the ordered flow rate<br />

(selected from Belimo’s standard product range).<br />

The valves factory setting is in open position (valve always<br />

closes in CW direction).<br />

To set or adjust desired maximum flow (actuator,<br />

FlowSetR and valve are connected):<br />

1. Fully close the valve via actuator control signal or via manual<br />

override (press button and turn handle in clockwise direction).<br />

Note: The FlowSetR fixed clockwise end stop purposely<br />

prevents the actuator from returning to its full zero-degree<br />

position, eliminating excess rotation.<br />

2. Use the integrated hex tool in the actuator lever to turn adjustment<br />

screw in plus (+) or minus (-) direction in order to move<br />

scale indicator to desired flow rate. A standard hex tool (i.e.<br />

Allen wrench) size 5/32” or 4mm can also be used to turn<br />

adjustment screw.<br />

Sizing and Selection of PICCVs<br />

To select the proper flow rate and actuation for<br />

your application:<br />

Sizing of the <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control<br />

Valves is based on GPM, and there is no need to calculate Cv<br />

rating. <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves are<br />

2-way valves that operate between a 5-50 PSI operating range.<br />

For example: If an application requires 4 GPM:<br />

Select the valve rated for 4 GPM. In the catalog, this part<br />

number is the PICCV-15-004.<br />

For example: If you wish to narrow the flow to 3.5 GPM:<br />

Narrowing the flow to 3.5 GPM can be achieved with the use<br />

of the FlowSetR if you have the LRB24-3 actuator. With the<br />

use of a 5/32" or 4 mm hex tool, the flow can be adjusted in<br />

the field. For all other MFT actuators, you may reprogram to<br />

3.5 GPM using the PC software and following the MFT guidelines.<br />

Note: Please note that PICCV bodies have a range of flow.<br />

Consult page 51 and 52 for details.<br />

56<br />

PICCV flow can be field adjusted by using a hex tool.<br />

Therefore, the maximum flow can be increased or<br />

decreased within the valves adjustable flow range.<br />

Integrated<br />

Hex Tool<br />

FlowSetR<br />

Adjustable<br />

with hex tool<br />

size 5/32” [4mm]<br />

Avoid disconnecting FlowSetR from actuator or valve! If necessary, refer to instruction sheet<br />

on how to install FlowSetR to valve, and actuator to FlowSetR.<br />

GPM<br />

For example, the valve body PICCV-15-001 can maintain flows<br />

from 0.50 GPM to 1.0 GPM, and the PICCV-15-005 can maintain<br />

flows between 1.5 GPM to 5.5 GPM.<br />

There will be two <strong>Pressure</strong>/Temperature ports as a standard<br />

offering for the 1-1/4" valves and larger, and available as an<br />

option for the 1" valves and smaller. The <strong>Pressure</strong>/Temperature<br />

ports will be reflected in the part number as "PT".<br />

i.e PICCV-15-004-PT + LF24-MFT US.<br />

The remaining step is to select the type of actuation, based on<br />

your requirements.<br />

Prior to ordering, please provide whether you wish to have the<br />

valve normally open or normally closed, and if spring return<br />

actuation is required, please note whether the valve is to<br />

spring open or spring closed upon power loss.<br />

For example: If your application for the above valve requires<br />

spring return, 2-10 VDC input signal, 100 sec run time and 2-10<br />

VDC feedback signal, select LF24-MFT US and MFT programming<br />

code P-10019.<br />

0.5<br />

Sample scale<br />

PICCV-15-001<br />

On Floating Point actuators, the running time is constant but<br />

dependent on the overall angle of rotation.<br />

1<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

1. Verify that the system is purged and filled to the<br />

proper pressure.<br />

2. Verify pump rotation.<br />

® PICCV<br />

PICCV Test and Balance Procedure<br />

3. Open all valves through the building management<br />

system if the total connected load➀ matches the pump<br />

GPM. Systems with diversity must have a percent of<br />

the valves closed to match the pump GPM.<br />

4. Test total flow by accurate method.*<br />

5. Decrease the pump speed until a flow decrease occurs.<br />

6. Increase the pump speed until the original flow is<br />

reestablished.<br />

PICCV Troubleshooting<br />

1. Is the pump on and rotating properly?<br />

2. Is the pressure differential adequate to produce<br />

design GPM?<br />

3. Is the water temperature at the required level?<br />

4. Is the PICCV installed in the right direction?<br />

5. Is there too much diversity in the system?<br />

6. Does the valve tag GPM match the listed design GPM?<br />

7. Does the ATC signal stroke the valve in the<br />

right direction?<br />

8. Are strainers plugged?<br />

9. Is the coil installed counterflow?<br />

10. Discharge temperature not to required rating:<br />

A. Is reset temperature high enough?<br />

B. Is air by-passing the coil?<br />

C. Are all coil areas heating/cooling uniformly?<br />

11. Room cold complaints:<br />

A. Is there enough throw➁ to penetrate air to the<br />

occupancy level?<br />

➁Throw is the distance discharge air is propelled<br />

in order to reach the occupant level.<br />

B. Test discharge air temperature and stratification.<br />

C. Is the building under a negative pressure?<br />

D. Is the hot water temperature at design?<br />

Resets may not be effective for reheat coils.<br />

Test and Balance Procedure,<br />

Troubleshooting<br />

7. Record system ΔP and provide this value to the<br />

ATC contractor.<br />

8. Perform a “Practical Test” to verify that the designer’s<br />

intent has been met. Taking a leaving air temperature<br />

can quickly verify the operation.<br />

*Accurate Methods<br />

Calibrated circuit setters on main lines<br />

Orifice<br />

Venturi<br />

Equipment pressure drops if the components are clean<br />

Ultrasonic Flowmeter<br />

Pump curves and triple duty valves have less<br />

accuracy than the above listed items<br />

GOOD IDEAS:<br />

Install taps on at least one valve with the largest<br />

DP requirement, or near the end run or near<br />

the DP transmitter.<br />

➀Total connected load is the summation of all<br />

terminal GPM.<br />

Often, engineers will design a pumping system for the<br />

total GPM as listed for all of the coils.<br />

Some engineers will take advantage of diversity and<br />

realize that no more than ± 80% of the valves will be<br />

calling at any one time during normal operation.<br />

For instance, if you have 100 GPM of total<br />

connected load, a pump sized for 80 GPM could<br />

be installed. In this case, if all valves open after<br />

a weekend of being closed, none of the valves will<br />

handle the design flow rate. A requirement of 20%<br />

of the valves would have to be closed to match the<br />

pump to the total connected load.<br />

57


Parallel Piping the PICCV<br />

to Achieve an Increase in Flow Rate<br />

Typical Parallel Piping in Relation<br />

to The Input and Output (Scale: None)<br />

58<br />

H/C–COIL<br />

H/C–COIL<br />

AIR VENT<br />

FLOW<br />

FLOW<br />

DRAIN<br />

Typical Piping in Relation<br />

to The Input and Output (Scale: None)<br />

AIR VENT<br />

DRAIN<br />

P/T PORT<br />

P/T PORT<br />

FLOW<br />

P/T PORT<br />

BELIMO PICCV (TYP.)<br />

FLOW<br />

FLOW<br />

BELIMO PICCV (TYP.)<br />

UNION CONNECTION (TYP.)<br />

P/T PORT<br />

P/T PORT<br />

FLOW<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves can<br />

be be piped in a parallel orientation to achieve increased flow<br />

rates.<br />

Our PICCV valves are available in flows to 100 GPM. To<br />

achieve flows larger than this, it is recommended to connect<br />

two of these valves in parallel leading to a common manifold.<br />

To correctly operate these valves, the Belimo Multi Function<br />

Technology (MFT) will be employed to utilize one common<br />

control signal.<br />

For example, the first valve will be outfitted with an MFT actuator<br />

that will correspond to a 2-5 or 2.6 VDC signal. The second<br />

valve would be outfitted with an MFT actuator that would correspond<br />

to a 6-10 VDC signal. Therefore, through a single 2-10<br />

VDC output, the full flow range will be achieved. The actuators<br />

will be wired in a parallel arrangement. The established configured<br />

P Codes are P-10137 for 2-5 VDC, P-10118 for 2-6 VDC,<br />

and P-10119 for 6-10 VDC.<br />

This recommended application provides the control of flows up<br />

to 200 GPM by using two valves. The top diagram details<br />

valves piped in a parallel arrangement. The bottom diagram<br />

features a typical single piping arrangement.<br />

PARALLEL PIPING ARRANGEMENT<br />

FOR PICCV VALVES<br />

P/T PORT<br />

P/T PORT<br />

STRAINER<br />

P/T PORT P/T PORT<br />

FLOW<br />

FLOW<br />

FLOW FLOW<br />

STRAINER<br />

UNION CONNECTION (TYP.)<br />

FLOW<br />

FLOW<br />

TYPICAL PARALLEL PIPING IN RELATION<br />

TO THE INPUT AND OUTPUT<br />

SHUT–OFF<br />

VALVE<br />

SHUT–OFF<br />

VALVE<br />

TEE (TYP.)<br />

SHUT–OFF<br />

VALVE<br />

SHUT–OFF<br />

VALVE<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Dimension with LRB24-3, LRX24-3<br />

2.6"<br />

[66]<br />

E F<br />

3.22"<br />

[82]<br />

Dimensions with LRB24-3, LRX24-3 with P/T Ports<br />

Dimensions with ARX24-MFT with P/T ports<br />

D<br />

1.69"<br />

[42]<br />

Dimensions–<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with Non-Spring Return Actuator<br />

6.5" [165]<br />

B<br />

A<br />

0.78" [20]<br />

C<br />

2.34"<br />

[59.4]<br />

FlowSetR Dimensions<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />

3/4" NPT 5.25 [133] 5.03 [128] 4.22[107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />

1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />

2.6"<br />

[66]<br />

E F<br />

3.22"<br />

[82]<br />

D<br />

1.69"<br />

[42]<br />

6.5" [165]<br />

B<br />

A<br />

C<br />

2.34"<br />

[59.4]<br />

0.78" [20] FlowSetR Dimensions<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />

3.46"<br />

[88]<br />

2.5"<br />

[64]<br />

E F<br />

3.3"<br />

[84]<br />

D<br />

1.35"<br />

[35]<br />

8.0" [203]<br />

B<br />

A<br />

C<br />

2.49"<br />

[63.4]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1-1/4" NPT 8.75 [222] 8.75 [222] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />

1-1/2" NPT 8.00 [203] 8.00 [203] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />

2" NPT* 8.5 [216] 8.5 [216] 6.62 [168] 4.4 [112] 1.77 [45] 3.03 [77]<br />

*Flows to 40 GPM.<br />

D146<br />

D147<br />

D158<br />

Dimensions with LRX24-MFT<br />

2.6"<br />

[66] 7.5" [191]<br />

D127<br />

E F<br />

Dimensions with LRX24-MFT with P/T Ports<br />

2.6"<br />

[66] 7.5" [191]<br />

D129<br />

E F<br />

3.22"<br />

[82]<br />

3.22"<br />

[82]<br />

D<br />

1.69"<br />

[42]<br />

D<br />

1.69"<br />

[42]<br />

B<br />

A<br />

C<br />

2.34"<br />

[59.4]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />

B<br />

A<br />

C<br />

2.34"<br />

[59.4]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />

3/4" NPT 5.25 [133] 5.03 [128] 4.22 [107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />

1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />

Dimensions with ARX24-MFT with P/T ports<br />

3.46"<br />

[88]<br />

2.5"<br />

[64]<br />

E F<br />

2.49"<br />

[63.4]<br />

C<br />

D<br />

8.0" [203]<br />

H<br />

3.3"<br />

1.35"<br />

[84]<br />

[35]<br />

BELIMO<br />

DN 50<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve* A B C D E F G H<br />

2" NPT 16.39 [416.2] 15.6 [396.2] 9.38 [238.3] 6.31 [160.3] 2.65 [67.3] 3.05 [77.5] 13.27 [337.1] 20.6 [523.24]<br />

B<br />

A<br />

2<br />

G<br />

D159<br />

2" NPT with larger flows from 44 GPM to 100 GPM<br />

59


Dimensions–<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with Spring Return Actuator<br />

TF24-MFT US<br />

LF24-MFT US<br />

60<br />

3.0"<br />

[76.2]<br />

E F<br />

3.78"<br />

[96]<br />

E F<br />

4.49"<br />

[114]<br />

D<br />

B<br />

A<br />

7.64"<br />

[194]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />

3/4" NPT 5.25 [133] 5.03 [128] 4.22 [107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />

1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />

C<br />

2.28"<br />

[58]<br />

D128<br />

AF24-MFT US with P/T ports<br />

E F<br />

LF24-MFT US with P/T ports AF24-MFT US with P/T ports<br />

3.78"<br />

[96]<br />

E F<br />

2.93"<br />

[74.5]<br />

D<br />

4.49"<br />

[114]<br />

D<br />

B<br />

A<br />

6.28"<br />

[159.55]<br />

B<br />

A<br />

7.64"<br />

[194]<br />

C<br />

2.40"<br />

[61]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />

C<br />

2.28"<br />

[58]<br />

D189<br />

D130<br />

TF24-MFT US with P/T ports<br />

3.0"<br />

[76.2]<br />

E F<br />

3.86"<br />

[98]<br />

3.86"<br />

[98] 2.24"<br />

[57]<br />

E F<br />

2.93"<br />

[74.5]<br />

C<br />

D<br />

3.66"<br />

[93]<br />

D<br />

D<br />

10.47"<br />

[266]<br />

6.28"<br />

[159.55]<br />

B<br />

A<br />

H<br />

3.66"<br />

[93]<br />

10.47"<br />

[266]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1-1/4" NPT 8.75 [222] 8.75 [222] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />

1-1/2" NPT 8.0 [203] 8.0 [203] 6.62 [168] 4.33 [110] 1.77 [45] 3.03 [77]<br />

2" NPT 8.5 [216] 8.5 [216] 6.62 [168] 4.4 [112] 1.77 [45] 3.03 [77]<br />

*Flows to 40 GPM.<br />

BELIMO<br />

DN 50<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve* A B C D E F G H<br />

2" NPT 16.39 [416.2] 15.6 [396.2] 9.38 [238.3] 6.31 [160.3] 2.65 [67.3] 3.05 [77.5] 12.92 [328.2] 21.9 [556.3]<br />

2<br />

B<br />

A<br />

C<br />

2.40"<br />

[61]<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

B<br />

A<br />

C<br />

2.24"<br />

[57]<br />

G<br />

D190<br />

D132<br />

D125<br />

2" NPT with larger flows from 44 GPM to 100 GPM<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

W431<br />

On/Off<br />

1<br />

Line<br />

Volts<br />

1<br />

2<br />

®<br />

24 VAC Transformer<br />

a open<br />

a closed<br />

The indication of direction<br />

is valid for switch position 1.<br />

Notes:<br />

a<br />

2 3 4 5<br />

Blk (1) Common<br />

Red (2) +<br />

Wht (3) +<br />

1 0<br />

Provide overload protection and disconnect as required.<br />

3 Actuators may also be powered by 24 VDC.<br />

LRB24-3…<br />

Actuators may be connected in parallel. Power<br />

consumption and input impedance must be observed.<br />

Wiring Diagrams for LRB24-3 Actuator<br />

Floating Point<br />

5<br />

1<br />

Line<br />

Volts<br />

24 VAC Transformer<br />

The indication of direction<br />

is valid for switch position 1.<br />

2 3 4 5<br />

Blk (1) Common<br />

Red (2) +<br />

Wht (3) +<br />

1 0<br />

LRB_24-3…<br />

4 Meets cULus or UL and CSA requirements without<br />

the need of an electrical ground connection.<br />

Actuators with plenum rated cable do not have<br />

numbers on wires; use color codes instead.<br />

Actuators with appliance cables are numbered.<br />

61


Wiring Diagrams for LRX24-MFT and ARX24-MFT Actuators<br />

VDC/4-20 mA<br />

Floating Point<br />

PWM<br />

62<br />

Actuators: LMX, LRX, NMX, AMX, ARX, GMX24-MFT<br />

Hazard Identification<br />

Warnings and Cautions appear at appropriate sections throughout<br />

INSTALLATION NOTES<br />

this manual. Read these carefully.<br />

3 Actuators may also be powered by 24 VDC.<br />

CAUTION<br />

Indicates a potentially hazardous situation which, if not avoided,<br />

may result in minor or moderate injury. It may also be used to<br />

5<br />

alert against unsafe practices.<br />

8<br />

2<br />

Equipment damage!<br />

Actuators may be connected in parallel if not mechanically<br />

mounted to the same shaft. Power consumption and input<br />

impedance must be observed.<br />

WARNING<br />

Live Electrical Components!<br />

During installation, testing,<br />

servicing and troubleshooting<br />

of this product, it maybe<br />

necessary to work with live<br />

electrical components. Have a<br />

qualified licensed electrician or<br />

other individual who has been<br />

Line<br />

Volts<br />

Control Signal<br />

4 to 20 mA<br />

or<br />

2 to 10 VDC<br />

Line<br />

Volts<br />

24 VAC Transformer<br />

(–)<br />

(+)<br />

24 VAC Transformer (AC only)<br />

Position (–)<br />

Feedback VDC (+)<br />

Ω 500Ω<br />

1/4 watt<br />

properly trained in handling live electrical components perform these tasks.<br />

Failure to follow all electrical safety precautions when exposed<br />

to live electrical components could result in death or serious injury.<br />

WARNING<br />

Live Electrical Components!<br />

During installation, testing,<br />

servicing and troubleshooting<br />

of this product, it maybe<br />

necessary to work with live<br />

electrical components. Have a<br />

qualified licensed electrician or<br />

other individual who has been<br />

properly trained in handling live<br />

electrical components perform these<br />

tasks. Failure to follow all electrical safety<br />

precautions when exposed to live electrical<br />

components could result in death or serious injury.<br />

WARNING<br />

Live Electrical Components!<br />

During installation, testing,<br />

servicing and troubleshooting<br />

of this product, it maybe<br />

necessary to work with live<br />

electrical components. Have a<br />

qualified licensed electrician or<br />

other individual who has been<br />

Line<br />

Volts<br />

7<br />

24 VAC Transformer<br />

properly trained in handling live electrical components perform these tasks.<br />

Failure to follow all electrical safety precautions when exposed to live electrical<br />

components could result in death or serious injury.<br />

8<br />

2 to 10 VDC<br />

Feedback Signal<br />

A<br />

B<br />

9<br />

11<br />

Direction of rotation switch<br />

CCW<br />

CCW<br />

CW<br />

CW<br />

A B 5<br />

8<br />

A B 5<br />

2<br />

Blk (1) Common<br />

Red (2) + Hot<br />

Wht (3) Y1 Input, 2 to 10V<br />

Grn (5) U Output, 2 to 10V<br />

CCW CW<br />

2<br />

2<br />

3 5<br />

3<br />

Blk (1) Common –<br />

Red (2) Hot + 10<br />

Wht (3) Y1 Input<br />

Pnk (4) Y2 Input<br />

Org (5) U Output 2 to 10V<br />

Blk (1) Common<br />

Red (2) + Hot<br />

Wht (3) Y Input<br />

Org (5) U Output<br />

7<br />

9<br />

11<br />

10<br />

Two Position<br />

Actuators with plenum rated cable do not have numbers on<br />

wires; use color codes instead. Actuators with appliance<br />

cables are numbered.<br />

Control signal may be pulsed from either the Hot (Source)<br />

or Common (Sink) 24 VAC line.<br />

For triac sink the Common connection from the actuator<br />

must be connected to the Hot connection of the controller.<br />

APPLICATION NOTES<br />

Meets cULus or UL and CSA requirements without<br />

the need of an electrical ground connection.<br />

A 500Ω resistor converts the 4 to 20 mA control signal<br />

to 2 to 10 VDC.<br />

Contact closures A & B also can be triacs. A & B should<br />

both be closed for triac source and open for triac sink.<br />

Position feedback cannot be used with a Triac sink controller.<br />

The actuator internal common reference is not compatible.<br />

WARNING<br />

Live Electrical Components!<br />

During installation, testing,<br />

24 VAC/DC Transformer<br />

servicing and troubleshooting Line<br />

of this product, it maybe necessary<br />

to work with live electrical<br />

Volts<br />

components. Have a qualified<br />

licensed electrician or other<br />

Position (–)<br />

a<br />

individual who has been properly<br />

trained in handling live electrical<br />

Feedback VDC (+)<br />

components perform these tasks. Failure to<br />

follow all electrical safety precautions when<br />

exposed to live electrical components could<br />

result in death or serious injury.<br />

Override control to min, mid, max, positions<br />

WARNING<br />

24 VAC Transformer<br />

Live Electrical Components!<br />

During installation, testing,<br />

servicing and trouble<br />

Line<br />

Volts<br />

shooting of this product,<br />

it maybe necessary to<br />

Ω<br />

work with live electrical Control Signal (–)<br />

components. Have a<br />

qualified licensed electrician<br />

or other individual who has<br />

been properly trained in<br />

2-10 VDC or (+)<br />

4 to 20 mA 500Ω<br />

1/4 watt<br />

7<br />

handling live electrical<br />

Min*<br />

components perform these tasks.<br />

Mid*<br />

Failure to follow all electrical safety<br />

Max*<br />

precautions when exposed to live<br />

electrical components could result in<br />

death or serious injury.<br />

Normal**<br />

A<br />

B<br />

C<br />

Functions<br />

0%<br />

50%<br />

100%<br />

Control mode acc. to Y<br />

Blk (1) Common<br />

Red (2) Hot<br />

Wht (3) Y Input<br />

Org (5) U Output<br />

Blk (1) Common<br />

Red (2) + Hot<br />

Wht (3) Y 1 Input, 2 to 10V<br />

a b c<br />

* Default selectable 0-100%. See Configuration Data Sheet.<br />

** Customizable. See Configuration Data Sheet.<br />

3<br />

2 3<br />

®<br />

W400<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® Wiring<br />

Wiring Diagrams<br />

Standard Wiring<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

3<br />

Red (2) + Hot 3<br />

Control Signal (–) 2<br />

2 to 10 VDC (+)<br />

Wht (3) Y1 Input, 2 to 10V<br />

2 to 10 VDC Feedback Signal<br />

24 VAC Transformer<br />

1<br />

Line<br />

Volts<br />

3<br />

Control Signal (–) A 2<br />

2 to 10 VDC (+)<br />

A Open = 0 V Position<br />

A Closed = Normal Operation<br />

Override to zero position<br />

Ω<br />

Grn (5) U Output, 2 to 10V<br />

Blk (1) Common<br />

Red (2) + Hot<br />

Wht (3) Y 1 Input, 2 to 10V<br />

Override to 10 V position<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

Red (2) + Hot<br />

3<br />

Control Signal (–) B 2<br />

2 to 10 VDC<br />

(+)<br />

C<br />

Wht (3) Y1 Input, 2 to 10V<br />

B Closed = 10 V Position<br />

C Closed = Normal Operation<br />

1<br />

Line<br />

Volts<br />

3<br />

Override control to min, mid, max, positions<br />

24 VAC Transformer<br />

Control Signal (–)<br />

2-10 VDC or (+)<br />

4 to 20 mA 500Ω<br />

1/4 watt<br />

4<br />

A<br />

B<br />

C<br />

CCW(L) CW(R)<br />

Blk (1) Common<br />

Red (2) + Hot<br />

Wht (3) Y 1 Input, 2 to 10V<br />

Functions a b c<br />

Min* 0%<br />

Mid* 50%<br />

Max* 100%<br />

Normal** Control mode acc. to Y<br />

* Default selectable 0-100%. See Configuration Data Sheet.<br />

** Customizable. See Configuration Data Sheet.<br />

2 to 10 VDC Control Signal<br />

W024<br />

Diagrams for TF24-MFT US Actuators<br />

24 VAC Transformer<br />

1<br />

Line<br />

Volts<br />

3<br />

Ω 500Ω<br />

1/4 watt<br />

Control Signal<br />

4 to 20 mA<br />

(–)<br />

(+)<br />

4<br />

Standard Wiring<br />

2<br />

Blk (1) Common<br />

Red (2) + Hot<br />

3<br />

Wht (3) Y 1 Input, 2 to 10V<br />

Grn (5) U Output, 2 to 10V<br />

Override to zero position<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

Red (2) + Hot<br />

3<br />

Control Signal (–)<br />

Ω 2<br />

4 to 20 mA (+)<br />

4<br />

A<br />

Wht (3) Y1 Input, 2 to 10V<br />

A Open = 4 mA Position<br />

A Closed = Normal Operation<br />

500Ω<br />

1/4 watt<br />

Override to 20 mA position<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

Red (2) + Hot<br />

3<br />

Control Signal<br />

(–)<br />

4 to 20 mA<br />

(+)<br />

4<br />

Ω<br />

500Ω<br />

1/4 watt<br />

B<br />

C<br />

2<br />

Wht (3) Y1 Input, 2 to 10V<br />

B Closed = 20 mA Position<br />

C Closed = Normal Operation<br />

4 to 20 mA Control Signal<br />

Notes<br />

1<br />

2<br />

3<br />

4<br />

CCW(L) CW(R)<br />

With a 4-20 mA Input, up to 4 actuators may<br />

be wired in parallel. A 2% shift in the signal<br />

is seen when using a 500Ω resistor. Power<br />

consumption must be observed.<br />

Provide overload protection and disconnect as required.<br />

Actuators may be connected in parallel if not mechanically mounted<br />

to the same shaft. Power consumption and input impedance must<br />

be observed.<br />

Actuator may also be powered by 24 VDC.<br />

ZG-R01 may be used.<br />

W025<br />

63


Wiring Diagrams for LF24-MFT US<br />

and AF24-MFT US Actuators<br />

64<br />

Standard Wiring<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

3<br />

Red (2) + Hot 3<br />

Control Signal (–) 2<br />

2 to 10 VDC (+)<br />

Wht (3) Y1 Input, 2 to 10V<br />

2 to 10 VDC Feedback Signal<br />

24 VAC Transformer<br />

1<br />

Line<br />

Volts<br />

3<br />

Control Signal (–) A 2<br />

2 to 10 VDC (+)<br />

A Open = 0 V Position<br />

A Closed = Normal Operation<br />

Override to zero position<br />

Ω<br />

Wht (5) U Output, 2 to 10V<br />

CCW(L) CW(R)<br />

Blk (1) Common<br />

Red (2) + Hot<br />

Wht (3) Y 1 Input, 2 to 10V<br />

Override to 10 V position<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

Red (2) + Hot<br />

3<br />

Control Signal (–) B 2<br />

2 to 10 VDC<br />

(+)<br />

C<br />

Wht (3) Y1 Input, 2 to 10V<br />

B Closed = 10 V Position<br />

C Closed = Normal Operation<br />

1<br />

Line<br />

Volts<br />

3<br />

Override control to min, mid, max, positions<br />

24 VAC Transformer<br />

Control Signal (–)<br />

2-10 VDC or<br />

4 to 20 mA<br />

(+)<br />

500Ω<br />

4<br />

1/4 watt<br />

Min*<br />

Mid*<br />

Functions<br />

0%<br />

50%<br />

A<br />

B<br />

C<br />

Blk (1) Common<br />

Red (2) + Hot<br />

Wht (3) Y 1 Input, 2 to 10V<br />

a b c<br />

Max* 100%<br />

Normal** Control mode acc. to Y<br />

* Default selectable 0-100%. See Configuration Data Sheet.<br />

** Customizable. See Configuration Data Sheet.<br />

2 to 10 VDC Control Signal<br />

W012<br />

24 VAC Transformer<br />

1<br />

Line<br />

Volts<br />

3<br />

Ω 500Ω<br />

1/4 watt<br />

Control Signal<br />

4 to 20 mA<br />

(–)<br />

(+)<br />

4<br />

Standard Wiring<br />

2<br />

Blk (1) Common<br />

Red (2) + Hot<br />

3<br />

Wht (3) Y 1 Input, 2 to 10V<br />

Wht (5) U Output, 2 to 10V<br />

Override to zero position<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

Red (2) + Hot<br />

3<br />

Control Signal (–)<br />

Ω 2<br />

4 to 20 mA (+)<br />

4<br />

A<br />

Wht (3) Y1 Input, 2 to 10V<br />

A Open = 4 mA Position<br />

A Closed = Normal Operation<br />

500Ω<br />

1/4 watt<br />

Override to 20 mA position<br />

24 VAC Transformer<br />

1<br />

Line<br />

Blk (1) Common<br />

Volts<br />

Red (2) + Hot<br />

3<br />

Control Signal<br />

(–)<br />

4 to 20 mA<br />

(+)<br />

4<br />

Ω<br />

500Ω<br />

1/4 watt<br />

B<br />

C<br />

2<br />

Wht (3) Y1 Input, 2 to 10V<br />

B Closed = 20 mA Position<br />

C Closed = Normal Operation<br />

4 to 20 mA Control Signal<br />

CCW(L) CW(R)<br />

With a 4-20 mA Input, up to 4 actuators may<br />

be wired in parallel. A 2% shift in the signal<br />

is seen when using a 500Ω resistor. Power<br />

consumption must be observed.<br />

Notes<br />

Provide overload protection and disconnect as required.<br />

1<br />

Actuators may be connected in parallel if not mechanically mounted<br />

2 to the same shaft. Power consumption and input impedance must<br />

be observed.<br />

3<br />

5<br />

6<br />

S1<br />

S2<br />

S3<br />

S4<br />

S5<br />

S6<br />

NC<br />

NO<br />

NC<br />

NO<br />

5°<br />

5<br />

6<br />

25° to 85°<br />

Auxiliary Switch AF24-MFT-S US<br />

4<br />

Actuator may also be powered by 24 VDC.<br />

ZG-R01 may be used.<br />

W014<br />

S1<br />

NC<br />

S2<br />

S3<br />

NO<br />

For end position indication, interlock control, fan startup, etc.,<br />

AF24-MFT-S US incorporates two built-in auxiliary switches:<br />

2 x SPDT, 7A (2.5A) @250 VAC, UL listed, one switch is fixed at +5°,<br />

one is adjustable 25° to 85°.<br />

LF24-MFT-S US incorporates one built-in auxiliary switch:<br />

1 x SPDT, 6A (1.5A) @250 VAC, UL listed, adjustable 0° to 95°.<br />

Meets UL and CSA requirements without the need of an electrical<br />

ground connection.<br />

5<br />

0° to 95°<br />

Auxiliary Switch LF24-MFT-S US<br />

6<br />

®<br />

W013<br />

W026<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® <strong>Pressure</strong><br />

Optimize<br />

Your Heat<br />

Pump<br />

Application<br />

by Using a <strong>Pressure</strong><br />

<strong>Independent</strong><br />

<strong>Characterized</strong><br />

Control Valve<br />

What are the benefits?<br />

A balanced system is achieved<br />

without the need for a balancer to<br />

manually balance each circuit.<br />

Because the system is dynamic<br />

and the PICCV performs dynamic<br />

balancing, Differential <strong>Pressure</strong>s<br />

are no longer an issue to be<br />

concerned with. The PICCV will<br />

maintain a constant flow at part<br />

load and during morning warm-up<br />

when all loops become critical.<br />

With the PICCV, each terminal<br />

gets the required flow, no over-flow<br />

or under-flow at this critical time.<br />

The PICCV allows a mechanic<br />

to easily commission additional<br />

circuits after the initial system is<br />

up and running, again thanks to<br />

dynamic balancing capability. The<br />

PICCV is available in flow rates<br />

from .5 GPM to 19 GPM. Choosing<br />

the right PICCV is as easy as<br />

determining the appropriate flow<br />

for your heat pump and then<br />

choosing the valve that satisfies<br />

the flow requirement.<br />

<strong>Independent</strong> <strong>Characterized</strong> Control Valve <br />

How does it work?<br />

Heat Pump Applications<br />

Keep with the same idea of a conventional heat pump system,<br />

then add the Belimo PICCV (2-way <strong>Pressure</strong> <strong>Independent</strong><br />

<strong>Characterized</strong> Control Valve). Think savings, and not necessarily first<br />

cost of equipment. Add a VFD (with its known and accepted benefits)<br />

and a Belimo PICCV as your flow control valve, and you have now<br />

optimized your system flow for very little additional cost.<br />

expansion<br />

device<br />

expansion<br />

device<br />

refrigerant-to-air<br />

heat exchanger<br />

refrigerant-to-air<br />

heat exchanger<br />

Heat Pump in Heating Mode<br />

refrigerant-to-water<br />

heat exchanger<br />

pump<br />

Heat Pump in Cooling Mode<br />

refrigerant-to-water<br />

heat exchanger<br />

compressor<br />

reversing<br />

valve<br />

pump<br />

compressor<br />

reversing<br />

valve<br />

water<br />

loop<br />

water<br />

loop<br />

65


P2 Series PICCV for Water Source Heat Pumps for Fast Running Time<br />

with Switch Options and On/Off, Non-Spring Return Actuator<br />

Two-way Valve with Chrome Plated Brass Ball and Brass Stem<br />

Service: chilled or hot water, 60% glycol<br />

Flow Characteristic: equal percentage<br />

Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />

Ambient Temp Range:<br />

Differential <strong>Pressure</strong><br />

-22°F to 122°F [-30°C to 50°C]<br />

Across Valve Range (ΔP): 5 to 50 psid<br />

Actuator:<br />

Running Time: 40 sec<br />

Power Supply 24 VAC/VDC<br />

P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem<br />

Valve Non-Spring Return Actuator<br />

66<br />

Model Valve On/Off<br />

# Flow Rate Nominal Size Close-<br />

PICCV Liter/ DN Off<br />

Valve GPM sec Inches mm psi LRCB24-3<br />

PICCV-15-0.50* 0.5 0.03 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-001* 1 0.06 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-1.50* 1.5 0.09 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-002* 2 0.13 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-003* 3 0.19 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-004* 4 0.25 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-005* 5 0.32 1/2” 15 200 ❑ Pg 66<br />

PICCV-20-006 6 0.38 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-007 7 0.44 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-008 8 0.50 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-009 9 0.57 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-010 10 0.63 3/4” 20 200 ❑ Pg 66<br />

PICCV-25-012** 12 0.76 1” 25 200 ❑ Pg 66**<br />

PICCV-25-014** 14 0.88 1” 25 200 ❑ Pg 66<br />

PICCV-25-016** 16 1.01 1” 25 200 ❑ Pg 66<br />

PICCV-25-018** 18 1.14 1” 25 200 ❑ Pg 66<br />

Electrical 3 ft cable<br />

Connection 1/2” conduit fitting<br />

LRCB24-3<br />

LRCB…<br />

Note: Other actuator options including switch options are available. Please contact your Belimo Account Manager or call 877-833-1609 for assistance.<br />

Options (add to list price) LRCB24-3-S<br />

Built-in aux. switch (-S) ❑ Pg 68<br />

*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />

**1” body has two different disc sizes (12 GPM to 16 GPM) (17 GPM to 19 GPM)<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

P2 Series PICCV for Water Source Heat Pumps for Fast Running Time<br />

with Switch Option and On/Off, Non-Spring Return Actuator<br />

Service: chilled or hot water, 60% glycol<br />

Flow Characteristic: equal percentage<br />

Media Temp Range: 0°F to 212°F [-18°C to 100°C]<br />

Ambient Temp Range:<br />

Differential <strong>Pressure</strong><br />

-22°F to 122°F [-30°C to 50°C]<br />

Across Valve Range (ΔP): 5 to 50 psid<br />

Actuator:<br />

Running Time: 40 sec<br />

Power Supply 24 VAC/VDC<br />

Two-way Valve with Chrome Plated Brass Ball and Brass Stem with P/T Ports, NPT Female Ends<br />

P2… <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve, Chrome Plated Brass Ball and Brass Stem, P/T Ports<br />

Valve Non-Spring Return Actuator<br />

Model Valve On/Off<br />

# Flow Rate Nominal Size Close-<br />

PICCV Liter/ DN Off<br />

Valve GPM sec Inches mm psi LRCB24-3<br />

PICCV-15-0.50-PT* 0.5 0.03 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-001-PT* 1 0.06 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-1.50-PT* 1.5 0.09 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-002-PT* 2 0.13 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-003-PT* 3 0.19 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-004-PT* 4 0.25 1/2” 15 200 ❑ Pg 66<br />

PICCV-15-005-PT* 5 0.32 1/2” 15 200 ❑ Pg 66<br />

PICCV-20-006-PT 6 0.38 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-007-PT 7 0.44 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-008-PT 8 0.50 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-009-PT 9 0.57 3/4” 20 200 ❑ Pg 66<br />

PICCV-20-010-PT 10 0.63 3/4” 20 200 ❑ Pg 66<br />

PICCV-25-012-PT** 12 0.76 1” 25 200 ❑ Pg 66<br />

PICCV-25-014-PT** 14 0.88 1” 25 200 ❑ Pg 66<br />

PICCV-25-016-PT** 16 1.01 1” 25 200 ❑ Pg 66<br />

PICCV-25-018-PT** 18 1.14 1” 25 200 ❑ Pg 66<br />

Electrical 3 ft cable<br />

Connection 1/2” conduit fitting<br />

Options (add to list price) LRCB24-3-S<br />

Built-in aux. switch (-S) ❑ Pg 68<br />

*1/2” body has two different disc sizes (.50 GPM to 1 GPM) (1.5 GPM to 5.5 GPM)<br />

**1” body has two different disc sizes (12 GPM to 16 GPM) (17 GPM to 19 GPM)<br />

LRCB24-3<br />

LRCB…<br />

67


<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with On/Off, Non-Spring Return Actuator, P/T Ports (Optional)<br />

Valve Specifications<br />

Service chilled or hot water, 60% glycol<br />

Flow characteristic equal percentage<br />

Size 1/2”, 3/4”, 1”<br />

Type of end fitting<br />

Materials:<br />

female, NPT<br />

Body forged brass, nickel plated<br />

Ball chrome plated brass<br />

Stem chrome plated brass<br />

Seat O-rings Viton<br />

Seat fiberglass reinforced teflon® PTFE<br />

Characterizing disc TEFZEL®<br />

Packing 2 EPDM O-rings, lubricated<br />

Diaphragm polyester reinforced silicone<br />

Regulator components stainless steel/brass/Delrin 500 AF<br />

Spring stainless Steel<br />

Pete’s Plug* (Qty 2) 1/4” brass/Nortel (Optional P/T)<br />

Body pressure rating 600 PSI<br />

Media temp. range 0°F to 212°F [-18°C to 100°C]<br />

Close off pressure 200 PSI<br />

Leakage ANSI Class IV (0.01% of rated valve<br />

capacity at 50 psi differential)<br />

Flow rate – 1/2” 0.5 GPM [.03 l/s], 1 GPM [.06 l/s],<br />

1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],<br />

3 GPM [.19 l/s], 4 GPM [.25 l/s],<br />

5 GPM [.32 l/s]<br />

Flow rate – 3/4” 6 GPM [0.37 l/s], 7 GPM [0.44 l/s],<br />

8 GPM [0.50 l/s], 9 GPM [0.57 l/s],<br />

10 GPM [0.63 l/s]<br />

Flow rate – 1” 12 GPM [0.76 l/s], 14 GPM [0.88 l/s],<br />

16 GPM [1.01 l/s], 18 GPM [1.14 l/s]<br />

Rangeability 100 : 1<br />

Differential pressure<br />

operating range<br />

5 to 50 PSI<br />

Flow accuracy (absolute) ≤ ± 5% (5 to 50 PSI)<br />

Variation due to<br />

manufacturing tolerances<br />

≤ ± 5% (5 to 50 PSI)<br />

Hysteresis (absolute) ≤ 1%<br />

Weight of valve body 1/2” = 2.52 lbs, 3/4” = 3.05 lbs<br />

1” = 4.98 lbs<br />

Tefzel® and Teflon® are registered trademarks of Dupont<br />

*Pete’s Plugs offered as an option on 1/2”, 3/4” and 1” valves.<br />

68<br />

Application:<br />

The <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve along with<br />

the LRCB24-3 is paired together specifically for use in Heat<br />

Pump applications to precisely control the flow of condenser<br />

water. This assembly is suitable for use in a hydronic system<br />

with constant or variable flow.<br />

Actuator Specifications<br />

❏ LRCB24-3… On/Off<br />

Power Supply 24 VAC ± 20% 50/60 Hz<br />

24 VDC ± 10%<br />

Power Consumption 1.5 W (0.2 W)<br />

Transformer Sizing 3 VA (Class 2 power source)<br />

Electrical Connection 18 GA plenum rated cable<br />

1/2” conduit connector<br />

❑ 3 ft [1m] ❑ 10 ft [3m] ❑ 16 ft [5m]<br />

Overload Protection electronic throughout 0 to 95° rotation<br />

Control On/Off<br />

Input Impedance 600Ω<br />

Angle of Rotation 95°<br />

Direction of Rotation reversible with protected switch<br />

Position Indication handle<br />

Manual Override external push button and handle<br />

Running Time 40 second constant independent of load<br />

Humidity 5 to 95% RH non condensing<br />

(EN 60730-1)<br />

Ambient Temperature -22°F to +122°F [-30°C to +50°C]<br />

Storage Temperature -40°F to +176°F [-40°C to +80°C]<br />

Housing NEMA 2/IP54<br />

Housing Material UL94-5VA<br />

Agency Listings cULus acc. to UL60730-1A/-2-14,<br />

CAN/CSA E60730-1, CSA C22.2<br />

No. 24-93, CE acc. to 89/336/EEC and<br />

(-S Models) 2006/95/EC†<br />

Noise Level


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

Dimensions<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valve<br />

with On/Off, Non-Spring Return Actuator<br />

LRCB24-3 LRCB24-3 with P/T Ports<br />

Line<br />

Volts<br />

WARNING<br />

Live Electrical Components!<br />

During installation, testing, servicing and troubleshooting of this product, it maybe<br />

necessary to work with live electrical components. Have a qualified licensed electrician<br />

or other individual who has been properly trained in handling live electrical components<br />

perform these tasks. Failure to follow all electrical safety precautions when exposed<br />

to live electrical components could result in death or serious injury.<br />

1<br />

2.6"<br />

[66]<br />

E F<br />

Wiring Diagram<br />

24 VAC Transformer<br />

a open<br />

a closed<br />

3.22"<br />

[82]<br />

The indication of direction<br />

is valid for switch position 1.<br />

D<br />

1.69"<br />

[42]<br />

a<br />

6.5" [165]<br />

B<br />

A<br />

3<br />

0.78" [20]<br />

Blk (1) Common –<br />

Red (2) +<br />

Wht (3) +<br />

1 0<br />

C<br />

2.34"<br />

[59.4]<br />

FlowSetR Dimensions<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 4.80 [122] 4.6 [117] 4.02 [102] 2.28 [58] 1.04 [24.4] 1.3 [33]<br />

3/4" NPT 5.25 [133] 5.03 [128] 4.22[107] 2.38 [61] 1.04 [24.4] 1.3 [33]<br />

1" NPT 7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [40.6] 1.60 [40.6]<br />

3<br />

®<br />

LRCX24-3<br />

Notes:<br />

1 Provide overload protection and disconnect as required.<br />

Actuators may also be powered by 24 VDC.<br />

Meets cULus requirements without the<br />

need of an electrical ground connection.<br />

LRCB24-3 On/Off<br />

D146<br />

W569<br />

2.6"<br />

[66]<br />

E F<br />

3.22"<br />

[82]<br />

D<br />

1.69"<br />

[42]<br />

6.5" [165]<br />

B<br />

A<br />

C<br />

2.34"<br />

[59.4]<br />

0.78" [20] FlowSetR Dimensions<br />

Dimensions (All ratings in brackets are in millimeters.)<br />

Valve A B C D E F<br />

1/2" NPT 5.3 [135] 4.6 [117] 5.4 [137] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

3/4" NPT 5.8 [147] 5.03 [128] 5.7 [145] 3.69 [94] 1.04 [24.4] 2.60 [66]<br />

1" NPT 7.05 [179] 6.85 [174] 6.05 [154] 4.0 [102] 1.60 [40.6] 2.90 [73.65]<br />

D147<br />

69


ZS-CCV… New Control Valve Weather Shield<br />

Installation Instructions<br />

Weather shield for PICCV/CCV to provide protection for<br />

actuators in outdoor applications.<br />

Specifications<br />

Cover PETG with UV resistant smoke tint<br />

Perimeter Gasket Silicon Rubber<br />

Rubber Gasket Silicon Rubber<br />

Spring Clips Stainless Steel<br />

Temperature limitations: -22˚F to 122˚F (-30˚C to 50˚C)<br />

Plate (ZS-CCV-100) Aluminum<br />

Plate Galvaneal w/black powder coat<br />

WEATHER SHIELDS*<br />

ZS-CCV-60<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />

70<br />

ZS-CCV-90<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />

ZS-CCV-100<br />

<strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves (PICCV)<br />

*Designed for NEMA 4 specifications<br />

PARTS LIST<br />

Cover including Rubber Perimeter Gasket, Rubber Gasket<br />

Back Plate<br />

Anti-Rotation Post with screw and lock washer<br />

Valve Gasket<br />

APPLICATION<br />

The ZS-CCV… weather shield provides moderate protection<br />

for valves which are mounted outdoors. This product is<br />

designed as a water tight enclosure. The housing allows<br />

easy mounting over the actuator, while allowing easy viewing<br />

of the actuator in operation.<br />

Part Number L W H<br />

ZS - CCV - 60 10” [254] 7.75” [197] 4”[100]<br />

ZS - CCV - 90 16.25” [413] 8.75” [222] 4.5” [114]<br />

ZS - CCV-100 15.67” [398] 7.61” [193] 4.0” [102]<br />

LR (B) (X) (CX) AR (X) (CX) LF AF List Price<br />

●<br />

●<br />

with CCV EXT-KIT<br />

● ●<br />

Assorted Cap plugs for unused holes<br />

Screws: LF - 2 screws provided<br />

AF - 2 bolts with nylon insert locking nuts<br />

LR(B)(X)(CX), AR(X)(CX) - 1 screw, 1 washer<br />

● ●<br />

●<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Flexible Products – Introduction<br />

Table of Contents<br />

Flexible Section<br />

Introduction ............................................73<br />

Ordering..................................................74<br />

Non-Spring Return<br />

“At A Glance”..........................................75<br />

MFT Programming Codes ......................76<br />

Non-Spring Return<br />

Base Actuator Table................................76<br />

Multi-Functional Technology<br />

Belimo damper actuators and control valves with Multi-Function Technology ® (MFT) include standard 2<br />

to 10 VDC proportional control functions, plus they can be re-programmed. Parameters can be<br />

changed on-site to optimize/enable application. Parameters can be set for voltage control (VDC), time<br />

proportional control (PWM), floating point, on-off or feedback signal. You can also set, modify or read<br />

position, running time, mechanical working range, address, status, and diagnostics. MFT allows you to<br />

adapt the actuator to your system for service replacement and to improve system functionality.<br />

71


Flexible Products – Ordering<br />

72<br />

Ordering example – Non-Spring Return<br />

The ordering process for the new Flexible non-spring return actuators is very simple. First select<br />

a base actuator that meets the needs of the application and then simply add the desired options.<br />

1. Valve Assembly PICCV-50-040-PT+ARX24-MFT (AR100) OC1 A19 ●<br />

Flexible list add<br />

Select a valve assembly<br />

●<br />

• Torque or linear force, control input, position feedback, power supply…<br />

2. Clamp option Default valve linkage (O) ●<br />

3. Electrical Connection option 16 ft. [5m] 18 GA, plenum rated cable (C5) ●<br />

• Default connection is a 3 ft. [1m] long cable. 10 ft [3m] or 16ft [5m] cables are also available.<br />

4. Programming P-10019 (A19) ●<br />

• For –MFT type actuators refer to page 79 for available configurations.<br />

5. Total PICCV-50-040-PT+ARX24-MFT (AR100 OC5 A19) ●<br />

Ordering example – Spring Return<br />

1. Valve Assembly PICCV-50-040-PT+AF24-MFT-S US ●<br />

Select a base actuator<br />

2. Programming P-10019 (A19) ●<br />

2 – 10 VDC input / 2 – 10 VDC feedback<br />

Select pre-set programming code<br />

● P-100xx (Axx) Control voltage applications<br />

● P-200xx (Wxx) Pulse width modulation applications<br />

● P-300xx (Fxx) Floating point applications<br />

● Or create custom MFT configuration codes, see page 82<br />

● Or create custom MFT configurations in the field with MFT-Actuate PC software.<br />

3. Total PICCV-50-040-PT+AF24-MFT-S US+P10019 (A19) ●<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

®<br />

Base product nomenclature<br />

Actuator Torque<br />

LR… 45 in-lb<br />

AR… 180 in-lb<br />

Flexible Valve/Actuator Selection At A Glance<br />

PICCV + Non-Spring Return MFT, Multi-Functional Technology<br />

Model Description Reorder for actuator<br />

PICCV-50-040-PT ARX 24 –MFT AR 100 O C1 A19<br />

VALVE SIZES<br />

Valve Designation Sizes<br />

PICCV Valve 15 – 50 = 1/2”– 2”<br />

TYPE OF VALVE<br />

PRESSURE INDEPENDENT<br />

CHARACTERIZED<br />

CONTROL VALVE (CCV)<br />

P2… 2-way Stainless<br />

Steel Ball & Stem<br />

Actuator family and<br />

torque/force output<br />

Electrical Connection<br />

blank 3 ft cable<br />

Reorder number break-down<br />

Base Actuator Linkage Electrical connector options Programming codes<br />

AR 100 O C1 A19<br />

See Base Actuators<br />

Page 74<br />

Power Supply<br />

24 24 VAC/DC<br />

Electrical connector options<br />

Code Description*<br />

C1 Default, 3 ft [1m] cable<br />

C3 10 ft [3m] cable<br />

C5 16 ft [5m] cable<br />

*24V actuators supplied with 18GA plenum<br />

rated cable.<br />

Control Type<br />

–MFT Multi-Function technology<br />

–3 On/Off-Floating Point<br />

The reorder#<br />

is a complete<br />

description of the<br />

flexible actuator,<br />

including all<br />

custom options.<br />

Options<br />

Codes Description (MFT Only)<br />

A19 P-10019*<br />

A28 P-10028<br />

AAJ P-10118<br />

AAK P-10119<br />

AD5 P-10137<br />

W31 P-20031<br />

W32 P-20032<br />

W34 P-20034<br />

F03 P-30003<br />

*For On/Off control input, please order<br />

P-10019 and wire as on/off.<br />

73


Flexible Products – MFT Programming Codes<br />

PRODUCTS<br />

Base Actuator Running Angle of Power VA Weight Built-in<br />

Model Codes Control Input Feedback Time Rotation/Stroke Supply Rating (lb) Aux. Switch<br />

180 in-lb [20 Nm]<br />

LRX24-3 LR000 Floating Point 2-10 VDC 90 (Default) 95 deg 24 VAC/DC 3 1.10<br />

LRX24-3-S LR020 Floating Point 2-10 VDC 90 (Default) 95 deg 24 VAC/DC 3 1.10 Yes<br />

LRX120-3 LR060 Floating Point 2-10 VDC 95 (Default) 95 deg 120 VAC 4 1.10<br />

LRX24-MFT LR100 2-10 VDC (Default) 2-10 VDC 100 (Default) 95 deg 24 VAC/DC 3.5 1.10<br />

LRCB24-3 LR000 on/off 2-10 VDC 40 95 deg 24 VAC/DC 3 1.08<br />

LRCB24-3-S LR020 on/off 2-10 VDC 40 95 deg 24 VAC/DC 3 1.08 Yes<br />

ARX24-MFT AR100 2-10 VDC (Default) 2-10 VDC 100 (Default) 95 deg 24 VAC/DC 6 2.02<br />

† For correct code please call Belimo Customer Service 800-543-9038<br />

Multi-Function Technology<br />

74<br />

Description Code Control Input Built-in Feedback Running Time<br />

DC Voltage<br />

P-10019* A19 2-10 VDC 2-10 VDC 100<br />

P-10028 A28 0-10 VDC 0-10 VDC 100<br />

P-10118 AAJ 2-6 VDC 2-10 VDC 100<br />

P-10119 AAK 6-10 VDC 2-10 VDC 100<br />

P-10137 AD5 2-5 VDC 2-10 VDC 100<br />

Pulse Width Modulation<br />

P-20031 W31 0.02-5.00 sec. PWM 2-10 VDC 100<br />

P-20032 W32 0.10-25.5 sec. PWM 2-10 VDC 100<br />

P-20034 W34 0.59-2.93 sec. PWM 2-10 VDC 100<br />

Floating Point<br />

On/Off<br />

P-30003 F03 Floating Point 2-10 VDC 100<br />

P-10019* J13 On/Off 2-10 VDC 100<br />

**Please Note: For On/Off control input, please order P-10019 and wire as on/off.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

2.16 CONTROL VALVES<br />

®<br />

A. Control Valves: Factory fabricated of type, body<br />

material, and pressure class based on maximum<br />

pressure and temperature rating of the piping<br />

system, unless otherwise indicated.<br />

B. <strong>Pressure</strong> <strong>Independent</strong> Control Valves<br />

a. Manufacturers:<br />

i. BELIMO AIRCONTROLS (USA), INC.<br />

b. The modulating control valves shall be<br />

pressure independent.<br />

c. The control valves shall accurately control the flow<br />

from 0 to 100% full rated flow with an equal<br />

percentage flow characteristic. The flow shall not<br />

vary more than +/- 5% due to system pressure<br />

fluctuations across the valve with a minimum of<br />

5 PSID across the valve.<br />

d. Forged brass body rated at no less than 400 PSI,<br />

chrome plated brass ball and stem, female NPT<br />

union ends, dual EPDM lubricated O-rings and<br />

TEFZEL characterizing disc.<br />

e. Combination of actuator and valve shall provide a<br />

minimum close-off pressure rating of 200 PSID.<br />

f. The control valve shall require no maintenance<br />

and shall not include replaceable cartridges.<br />

g. All actuators shall be electronically programmed<br />

by use of a handheld programming device or<br />

external computer software. Programming using<br />

actuator mounted switches or multi-turn actuators<br />

are NOT acceptable. [Actuators for 3-wire<br />

floating (tri-state) on 1/2” – 1” pressure<br />

independent control valves shall fail in place<br />

and have a mechanical device inserted<br />

between the valve and the actuator for the<br />

adjustment of flow.] [Actuators for two-position<br />

1/2” – 1” pressure independent control<br />

valves shall fail in place and have a mechanical<br />

device inserted between the valve and the<br />

actuator for the adjustment of flow.] [Actuators<br />

shall be provided with an auxiliary switch to<br />

prove valve position.]<br />

h. The actuator shall be of the same manufacturer<br />

as the valve, integrally mounted to the valve at the<br />

factory via a single screw on a four-way DIN<br />

mounting-base.<br />

i. The control valve shall require no maintenance<br />

and shall not include replaceable cartridges.<br />

j. The manufacturer shall warrant all components<br />

for a period 5 years from the date of production,<br />

with the first two years unconditional.<br />

k. The use of pressure independent valves piped in<br />

parallel to achieve the rated coil flow shall be<br />

permitted. Actuators shall be electronically<br />

programmed to permit sequencing the flow with a<br />

single control output point. The use of external<br />

devices to permit sequencing is NOT acceptable.<br />

Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong><br />

Control Valves (1/2” – 2”)<br />

Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves Master Format<br />

To be inserted into Section 15900 – HVAC Instrumentation and Controls<br />

To be inserted into Section 15181 – HYDRONIC PIPING<br />

2.6 CONTROL VALVES<br />

K. Calibrated Balancing Valves and Automatic<br />

Flow-Control Valves shall not be required on devices<br />

where pressure independent control valves are<br />

installed.<br />

NOTE TO BE ADDED TO THE PIPING DETAIL:<br />

Strainers shall not be required in front of each pressure<br />

independent control valve. A Type 20 strainer (or<br />

equivalent) should be installed in the system, in<br />

additional to other system strainers.<br />

To be inserted into Section 15950 – TESTING,<br />

ADJUSTING, AND BALANCING<br />

3.11 PROCEDURE FOR HYDRONIC SYSTEMS<br />

[CHOOSE ONE OF THE FOLLOWING TWO PARAGRAPHS]<br />

H. Systems installed with pressure independent control<br />

valves shall not require hydronic system balancing.<br />

H. Systems installed with pressure independent valves<br />

shall require verification of flow for [10%] [20%]<br />

[25%] of the total<br />

installed product. Exact locations of tested product<br />

to be coordinated with the design engineer.<br />

75


Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong><br />

Control Valves (1/2” – 2”)<br />

Specifying <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves - Master Format<br />

To be inserted into Section 230900 – INSTRUMENTATION AND CONTROL FOR HVAC<br />

2.16 CONTROL VALVES<br />

76<br />

A. Control Valves: Factory fabricated of type, body<br />

material, and pressure class based on maximum<br />

pressure and temperature rating of the piping<br />

system, unless otherwise indicated.<br />

B. <strong>Pressure</strong> <strong>Independent</strong> Control Valves<br />

a. Manufacturers:<br />

i. BELIMO AIRCONTROLS (USA), INC.<br />

b. The modulating control valves shall be pressure<br />

independent.<br />

c. The control valves shall accurately control the flow<br />

from 0 to 100% full rated flow with an equal<br />

percentage flow characteristic. The flow shall not<br />

vary more than +/- 5% due to system pressure<br />

fluctuations across the valve with a minimum of<br />

5 PSID across the valve.<br />

d. Forged brass body rated at no less than 400 PSI,<br />

chrome plated brass ball and stem, female NPT<br />

union ends, dual EPDM lubricated O-rings and<br />

TEFZEL characterizing disc.<br />

e. Combination of actuator and valve shall provide a<br />

minimum close-off pressure rating of 200 PSID.<br />

f. The control valve shall require no maintenance<br />

and shall not include replaceable cartridges.<br />

g. All actuators shall be electronically programmed<br />

by use of a handheld programming device or<br />

external computer software. Programming using<br />

actuator mounted switches or multi-turn actuators<br />

is NOT acceptable. [Actuators for 3-wire floating<br />

(tri-state) on 1/2” – 1” pressure independent<br />

control valves shall fail in place and have a<br />

mechanical device inserted between the valve<br />

and the actuator for the adjustment of flow.]<br />

[Actuators for two-position 1/2” – 1” pressure<br />

independent control valves shall fail in place<br />

and have a mechanical device inserted<br />

between the valve and the actuator for the<br />

adjustment of flow.] [Actuators shall be provided<br />

with an auxiliary switch to prove valve<br />

position.]<br />

h. The actuator shall be of the same manufacturer<br />

as the valve, integrally mounted to the valve at the<br />

factory via a single screw on a four-way DIN<br />

mounting-base.<br />

i. The control valve shall require no maintenance<br />

and shall not include replaceable cartridges.<br />

j. The manufacturer shall warrant all components for<br />

a period of 5 years from the date of production,<br />

with the first two years unconditional.<br />

k. The use of pressure independent valves piped in<br />

parallel to achieve the rated coil flow shall be<br />

permitted. Actuators shall be electronically<br />

programmed to permit sequencing the flow with<br />

a single control output point. The use of external<br />

devices to permit sequencing is NOT acceptable.<br />

To be inserted into Section 232113 – HYDRONIC PIPING<br />

2.6 CONTROL VALVES<br />

K. Calibrated Balancing Valves and Automatic<br />

Flow-Control Valves shall not be required on<br />

devices where pressure independent control<br />

valves are installed.<br />

NOTE TO BE ADDED TO THE PIPING DETAIL:<br />

Strainers shall not be required in front of each pressure<br />

independent control valve. A Type 20 strainer (or<br />

equivalent) should be installed in the system, in<br />

additional to other system strainers.<br />

To be inserted into Section 230593 – TESTING,<br />

ADJUSTING, AND BALANCING FOR HVAC<br />

3.11 PROCEDURE FOR HYDRONIC SYSTEMS<br />

[CHOOSE ONE OF THE FOLLOWING TWO PARAGRAPHS]<br />

H. Systems installed with pressure independent control<br />

valves shall not require hydronic system balancing.<br />

H. Systems installed with pressure independent valves<br />

shall require verification of flow for [10%] [20%]<br />

[25%] of the total<br />

installed product. Exact locations of tested product<br />

to be coordinated with the design engineer.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® ®<br />

I. GENERAL<br />

A. Warranty all actuators for a period of two or five years from the production<br />

date as stated in the Terms and Conditions of Sale and Warranty.<br />

B. Electronic valve and damper actuators shall be as manufactured, brand<br />

labeled, or distributed by Belimo.<br />

C. Electronic control valves, as specified, shall be Belimo or other brands<br />

manufactured, brand labeled or distributed by Belimo.<br />

D. Other manufacturers must be approved, in writing, 10 days prior to the<br />

bid date.<br />

II. PRODUCTS<br />

A. Electronic Damper Actuators<br />

1. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO<br />

9001 quality certification and be cULus listed under standard 60730-1 or<br />

UL listed under standard 873, CSA C22.2 No. 24 and have CE certification.<br />

2. Electronic actuators used on dampers shall be designed to directly couple<br />

and mount to a stem, shaft or ISO style-mounting pad. Actuator<br />

mounting clamps shall be a V-bolt with a toothed V-clamp creating a cold<br />

weld, positive grip effect. Single point, bolt, or single screw actuator type<br />

fastening techniques or direct-coupled actuators requiring field assembly<br />

of the universal clamp is not acceptable.<br />

3. Actuators shall be fully modulating/proportional, pulse width,floating/tristate,<br />

or two position as required and be factory or field selectable.<br />

Actuators shall have visual position indicators and shall operate in<br />

sequence with other devices if required.<br />

4. Optional auxiliary switches shall be available.<br />

5. Actuators shall have an operating range of –22° to 122°F.<br />

6. Proportional actuators shall accept a 0-10 VDC or 0-20 mA input signal and<br />

provide a 2-10 VDC or 4-20 mA (with a 500 W load resistor) operating range.<br />

7. Actuators shall be capable of operating on 24, 120 or 230VAC, or 24VDC<br />

and Class 2 wiring as dictated by the application. Power consumption<br />

shall not exceed 10 VA for AC, including 120VAC actuators, and 8 watts<br />

per actuator for DC applications.<br />

8. NEMA 2 rated actuators shall be provided with a three foot (minimum),<br />

pre-wired, electrical cable. Actuators requiring removal of the actuator<br />

cover for access to wiring terminals, exposing electronic, printed circuit<br />

boards to damage, are unacceptable.<br />

9. Actuators shall have electronic overload protection or digital rotation<br />

sensing circuitry to prevent actuator damage throughout the entire rotation.<br />

End switches to deactivate the actuator at the end rotation or magnetic<br />

clutches are not acceptable.<br />

10. For power-failure/safety applications, an internal mechanical spring return<br />

mechanism shall be built into the actuator housing. Spring return actuators<br />

shall be capable of CW or CCW mounting orientation. Spring return<br />

models > 60 in-lbs. and non-spring return models > 90 in-lbs. will be<br />

capable of mounting on shafts up to 1.05"in diameter. Spring return actuators<br />

with more than 60 in-lb. of torque shall have a metal, manual override<br />

crank.<br />

11. Actuators using "on-board" chemical storage systems, capacitors, or other<br />

"on-board" non-mechanical forms of fail-safe operation are unacceptable.<br />

12. Upon loss of control signal, a proportional actuator shall fail open or<br />

closed based on the minimum control signal. Upon loss of power, a nonspring<br />

return actuator shall maintain the last position.<br />

13. Actuators shall be capable of being mechanically and electrically paralleled<br />

to increase torque if required. Valves and dampers requiring greater torque<br />

or higher close off may be assembled with multiple low torque actuators.<br />

14. Dual mounted actuators using additional anti-rotation strap mechanical<br />

linkages, or special factory wiring to function are not acceptable.<br />

Actuators in a tandem pair must be "off the shelf," standard actuators<br />

ready for field wiring.<br />

15. Damper and valve actuators will not produce more than 62 dB (A) when<br />

furnished with a mechanical fail-safe spring. Non-spring return actuators<br />

shall conform to a maximum noise rating of 45 dB(A) with power on or in<br />

the running or driving mode.<br />

16. Proportional actuators shall be fully programmable. Control input, position<br />

feedback and running time shall be factory or field programmable.<br />

Diagnostic feedback shall provide indications of hunting or oscillation,<br />

mechanical overload, mechanical travel and mechanical load limit. The<br />

actuators shall also provide actuator service data, at minimum, number of<br />

hours powered and number of hours in motion.<br />

17. Proportional actuators shall be capable of digital communication, as built.<br />

Actuator/Valve Specification<br />

Download specifications at www.belimo.com<br />

B. Smoke and Combination Fire and Smoke Actuators<br />

In Section 15820 or equivalent<br />

1. All smoke and combination fire and smoke dampers shall be<br />

provided with Belimo Aircontrols FSLF (30 in-#), FSNF (70 in-#),<br />

or FSAF (133 in-#) actuators.<br />

2. Equals shall be approved 10 days prior to submission of bid.<br />

3. Actuator shall carry a manufacturer’s 5-year warranty and be manufactured<br />

under ISO 9001 quality control.<br />

4. Actuator shall have microprocessor or electronic based motor controller<br />

providing:<br />

a. Electronic cut off at full open so that no noise can be generated while<br />

holding open. Holding noise level shall be inaudible.<br />

b. Protection so that actuator shall be incapable of burning out if stalled<br />

before full rotation is reached.<br />

5. Housing shall be steel and gears shall be permanently lubricated.<br />

6. The actuators shall be direct coupled and employ a steel toothed coldweld<br />

clamp for connecting to damper or jack shafts. Aluminum clamps or<br />

set-screw attachment are not acceptable.<br />

7. Actuator shall have UL555S Listing by the damper manufacturer for 250°F.<br />

8. FSLF shall be applied on dampers up to 6 sq. ft. Current draw shall be<br />

no more than .15A at 120V running, or .06A holding at 120V (5 VA and<br />

3.5 VA respectively for 24V power).FSNF shall be applied on dampers up<br />

to 16 sq.ft. Current draw shall be no more than .23A at 120V running, or<br />

.1A holding at 120V (27 VA and 10 VA respectively for 24V power).<br />

9. FSAF shall be applied on dampers up to 20 sq.ft. Current draw shall be<br />

no more than .1A at 120V running, or .05A holding at 120V (10 VA and<br />

3 VA respectively for 24V power).<br />

10. Dampers shall be installed straight and true, level in all planes, and<br />

square in all dimensions. Dampers shall move freely without undue<br />

stress due to twisting, racking, bowing, or other installation error.<br />

11. Do not install in area where moisture can penetrate damper or actuator<br />

nor where actuator temperature exceeds 120°F.<br />

Note: FSLF and FSNF are 350°F actuators, 15 seconds open and<br />

close. UBC and UL555S<br />

FSAF is a 250F actuator, 75 seconds open, 20 seconds close.<br />

UL555S.<br />

C. Electronic Valve Actuators<br />

1. Electronic actuators, less than 600 in-lb. of rated torque, shall have ISO<br />

9001 quality certification and be cULus listed under standard 60730-1 or<br />

UL listed under standard 873, CSA C22.2 No. 24 and have CE certification.<br />

2. Electronic actuators used on valves shall be designed to directly couple<br />

and mount to a stem, shaft or ISO style-mounting pad.<br />

3. Actuators shall be fully modulating/proportional, floating/tri-state, or two<br />

position as required and be factory or field selectable.<br />

4. Optional auxiliary switches shall be available.<br />

5. Actuators shall have an operating range of –22° to 122°F.<br />

6. Proportional actuators shall accept a 0-10 VDC or 0-20 mA input signal<br />

and provide a 2-10 VDC or 4-20 mA (with a load resistor) operating range.<br />

7. Actuators shall be capable of operating on 24VAC, 120VAC or 230VAC,<br />

or 24VDC and Class 2 wiring as dictated by the application. Power consumption<br />

shall not exceed 10 VA for AC, including 120VAC actuators, and<br />

8 watts per actuator for DC applications.<br />

8. NEMA 2 rated actuators shall be provided with either a covered terminal<br />

strip, or a three, six, or ten foot pre-wired, electrical cable.<br />

9. For power-failure/safety applications, an internal mechanical spring return<br />

mechanism shall be built into the actuator housing. Spring return actuators<br />

shall be capable of CW or CCW mounting orientation. Spring return<br />

actuators with more than 60 in-lb. of torque shall have a metal, manual<br />

override crank.<br />

10. Actuators using "on-board" chemical storage systems, capacitors, or other<br />

"on-board" non-mechanical forms of fail-safe operation are unacceptable.<br />

11. Upon loss of control signal, a proportional actuator shall fail open or<br />

closed based on the minimum control signal. Upon loss of power, a nonspring<br />

return actuator shall maintain the last position.<br />

12. Actuators utilizing brushless DC technology shall be capable of being<br />

mechanically and electrically paralleled to increase torque if required.<br />

Valves requiring greater torque or higher close off may be assembled<br />

with two low torque actuators.<br />

77


Actuator/Valve Specification<br />

78<br />

13. Dual mounted actuators using additional anti-rotation strap mechanical<br />

linkages, or special factory wiring to function are not acceptable.<br />

Actuators in a tandem pair must be "off the shelf," standard actuators<br />

ready for field wiring.<br />

14. Valve actuators will not produce more than 62 dB (A) when furnished<br />

with a mechanical fail-safe spring. Non-spring return actuators shall conform<br />

to a maximum noise rating of 45 dB(A) with power on or in the running<br />

or driving mode.<br />

15. Proportional actuators shall be fully programmable. Control input, position<br />

feedback and running time shall be factory or field programmable.<br />

Diagnostic feedback shall provide indications of hunting or oscillation,<br />

mechanical overload, mechanical travel and mechanical load limit. The<br />

actuators shall also provide actuator service data, at minimum, number of<br />

hours powered and number of hours in motion.<br />

16. Proportional actuators shall be capable of digital communication, as built.<br />

D. Industrial Actuators<br />

1. Belimo SY Series Industrial Electric Actuators<br />

a. The valve actuator shall consist of a thermally protected capacitor-type<br />

reversible electric motor, a patented planetary worm combination drive,<br />

heater, limit switches and wiring termination blocks, all contained in a die<br />

cast aluminum enclosure. The drive system will provide continuous,<br />

smooth torque transmission throughout a 90 degree travel. Adjustable<br />

stops provide mechanical adjustment of end-of-travel. The transmission<br />

shall allow continuous duty operation of a manual override handwheel<br />

without the need to remove power, or de-clutch the manual system.<br />

b. Enclosure shall be designed to meet NEMA 4, 4X (weatherproof) requirements,<br />

or CSA approved for non-hazardous locations.<br />

c. The actuator shall employ ISO5211 mounting standards to provide for a<br />

wide range of international applications.<br />

d. The enclosure will have an industrial quality coating.<br />

e. Actuator shall have a motor rated for a minimum of 25% duty cycle in<br />

modulating applications.<br />

f. Actuator shall be suitable for operation in ambient temperature ranging<br />

from -4°F to +150°F [-20°C to +65°C].<br />

g. The motor shall be fractional horsepower; permanent split capacitor type<br />

designed to operate on 24 VAC, 110 VAC or 220 VAC, 1 pH, 50/60 Hz<br />

supply. A self resetting thermal switch shall be imbedded in the motor for<br />

overload protection.<br />

h. Internal terminal blocks shall be clearly marked for field wiring. A wiring<br />

diagram shall be permanently attached to the OUTSIDE of the actuator<br />

housing.<br />

i. Actuator will have a suitable sized NPT entry for external connections.<br />

j. Gears shall be hardened alloy steel, permanently lubricated. The worm<br />

drive system negates the need for a brake.<br />

k. Two adjustable cam actuated end travel limit switches shall be provided<br />

to control electrical movement of the actuator.<br />

l. 2 SPDT auxiliary switches, rated 10A at 250 VAC shall be included. The<br />

switches are factory pre-set at 3 degrees and 87 degrees rotation, and<br />

may be field adjusted.<br />

m. Actuator shall be equipped with a hand wheel or shaft for manual override<br />

to permit operation of the actuator in the event of electrical power failure<br />

or system malfunction. Hand wheel, where applicable, must be permanently<br />

attached to the actuator. (SY2 and larger)<br />

n. The handwheel override shall be continuously operational regardless of<br />

the powered state of the actuator, without the need to remove electrical<br />

power if present during the override phase. (SY2 and larger)<br />

o. The hand wheel will not rotate while the actuator is electrically driven.<br />

p. The actuator shall provide a visual indicator beacon on the top of the<br />

housing for position status of the actuator and attached devices.<br />

q. Actuator shall have an internal heater and thermostat to minimize the<br />

build-up of moisture inside the sealed enclosure.<br />

r. Modulating units shall operate under 2-10 VDC, 4-20mA, and 1-5 VDC<br />

control modes. The default shall be 2-10 VDC control.<br />

E. Electronic Control Valves<br />

1. General<br />

a. The manufacturer shall be capable of providing individual valve identification<br />

tagging on each printed valve label. Valve tag identification shall be<br />

documented on the approved, submitted valve schedule.<br />

b. Valves shall be designed and provided with the proper actuators to provide<br />

the rated valve close-off.<br />

2. <strong>Pressure</strong> <strong>Independent</strong> <strong>Characterized</strong> Control Valves<br />

a. Control valves shall be pressure independent. Balancing valves and<br />

associated balancing shall not be required on devices where pressure<br />

independent control valves are installed. Balancing valves and balancing<br />

are required if self-contained pressure independent control valves are not<br />

installed.<br />

b. The absolute flow accuracy through the valve shall be +/- 5 % due to system<br />

pressure fluctuations across the valve in the selected operating<br />

range, and +/- 5% variation due to manufacturing tolerances.<br />

c. The control valves shall be available with floating or proportional actuators.<br />

The actuator shall be directly coupled to the valve at the factory.<br />

Proportional actuators shall be Multi Function Technology as manufactured<br />

by Belimo. Multi-turn actuators are not acceptable.<br />

d. The valve shall have an equal percentage characteristic and shall accurately<br />

control the flow from 0 to 100% full rated flow.<br />

e. A minimum of 5 PSI shall be required to operate the valve pressure independently.<br />

f. Valves shall require no maintenance and shall not include replaceable<br />

cartridges.<br />

g. Valves shall be available with optional pressure/temperature ports to<br />

allow flow verification.<br />

h. Control valves shall be by Belimo.<br />

3. <strong>Characterized</strong> Control Valves<br />

a. Control valves shall be of the <strong>Characterized</strong> Control Valve type provided<br />

by Belimo.<br />

b. <strong>Characterized</strong> Control Valves shall be used for all water applications<br />

requiring equal percentage characteristics.<br />

c. A TEFZEL‚ flow-characterizing disc shall be installed in the inlet of Twoway<br />

characterized control valves and in the control port of Three-way<br />

valves. The valve trim shall utilize a stainless steel ball and stem for all<br />

water or glycol solutions up to 60%. For water applications, an optional<br />

chrome plated brass ball and brass stem may be used for sizes 3/4’’ and<br />

smaller.<br />

d. Valve bodies shall be nickel-plated, forged brass with female NPT<br />

threads. Bodies to 1-1/4" shall be rated at 600 psi and sizes 1-1/2" to 3"<br />

at 400 psi.<br />

e. <strong>Characterized</strong> Control Valves shall have a self-aligning, blowout proof,<br />

brass stem with a dual EPDM O-ring packing design. Fiberglass reinforced<br />

Teflon seats shall be used.<br />

f. The valves shall have a four bolt mounting flange to provide a 4 position,<br />

field changeable, electronic actuator mounting arrangement.<br />

g. A non-metallic coupling, constructed of high temperature, continual use<br />

material shall provide a direct, mechanical connection between the valve<br />

body and actuator. The coupling shall be designed to provide thermal<br />

isolation and eliminate lateral and rotational stem forces. Vent hole shall<br />

be provided to reduce condensation build-up.<br />

4. Globe Valves<br />

a. Globe valves, as specified, shall be by Belimo.<br />

b. Two-way and Three-way globe valves may be used only if characterized<br />

control valves do not fit the sizing criteria or application.<br />

c. Globe valves may be used for chilled or hot water, steam, or glycol solutions<br />

to 60%. Screwed and flanged water valves shall have equal percentage<br />

or linear flow characteristics for Two-way or Three-way valves,<br />

respectively. All stems shall be stainless steel.<br />

d. Screwed globe valves 1/2" through 2" shall have bronze bodies rated at<br />

ANSI Class 250. For water up to 35 psi or steam up to 15 psi, trim shall<br />

include a brass plug, a spring-loaded TFE packing, and a bronze seat.<br />

The maximum differential shall be 35 psi for water and 15 psi for steam.<br />

e. Two-way and Three-way flanged globe valves 2-1/2" to 6" shall have cast<br />

iron bodies rated for ANSI Class 125 or ANSI 250. The maximum differential<br />

shall be 25 psi for water and 10 psi for steam. Trim shall include stainless<br />

steel stems, bronze plugs, bronze seats, and a NLP packaging or a<br />

complete stainless steel trim and a TFE V-ring packaging.<br />

f. For steam inlet pressures higher than those stated above, furnish globe<br />

valves with stainless steel trim specifically rated for the application.<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® ®<br />

5. Direct Coupled Globe Valve Actuator and Adaptor Bracket<br />

a. Actuator shall be designed with an integrated adaptor bracket that will<br />

direct mount to the valve.<br />

b. Actuator shall provide a linear force capable of fulfilling the required<br />

close-off of the valve.<br />

c. Actuator shall include an automatic valve coupling device that shall lock<br />

securely to the valve stem.<br />

d. Proportional and spring return actuators shall adapt upon powering the<br />

actuator. This adaptation will determine stroke length and enable the<br />

actuator to set the minimum and maximum limits of the supplied control<br />

signal, thereby utilizing the entire control signal range. Feedback, running<br />

time and other parameters are automatically adjusted to the effective<br />

stroke.<br />

e. Actuator shall have a manual override equipped with an interlocking<br />

device to protect the actuator from over-torque of the manual override.<br />

6. Butterfly Valves – Resilient Seat<br />

a. Butterfly valves, as specified, shall be by Belimo.<br />

b. Butterfly valves 2" to 12" shall have a fully lugged, drilled and tapped,<br />

cast iron body, rated to 200 psi body pressure, with 14" and larger valves<br />

having a body pressure rating of 150 psi. Flanges shall meet ANSI<br />

125/150 standards. The one-piece body shall feature an extended neck<br />

allowing sufficient clearance for flanges and 2" of piping insulation. The<br />

disc shall be 304 stainless steel and provide bi-directional bubble-tight<br />

close off in either direction for chilled or hot water or 50% glycol applications.<br />

The disc shall be polished and contoured to minimize torque and<br />

wear. Shaft shall be mechanically retained in valve body using split-thrust<br />

washer and internal retaining-ring design for ease of service. The valve<br />

body shall employ ISO5211 actuator mounting and shaft connection<br />

standards.<br />

c. The disc shall have full 360-degree concentric seating. Valves up through<br />

12" shall utilize an internal spline for the disc-to-stem connection. External<br />

mechanical methods to achieve this mechanical connection, such as pins<br />

or screws, shall not be employed. Valves 14" and larger will utilize a dualpin<br />

method to prevent the heavy disc from settling onto the liner, causing<br />

distortion. A phenolic backed, non-collapsing, EPDM seat shall be field<br />

replaceable and shall create a positive seal between flange face and<br />

valve body. No gaskets shall be required between the valve and flange<br />

faces. The shaft shall be supported at four locations by RPTFE bushings.<br />

d. The flow characteristic shall be modified equal percentage for Two-way<br />

valves and linear for Three-way valves. Valves 2" through 12" shall be<br />

rated for standard HVAC service of up to 50 psi close-off, or for heavy<br />

commercial service of up to 200 psi close-off. Valves 14" and larger shall<br />

be rated for up to 150 psi close-off.<br />

e. A permanent metal tag shall designate manufacturer, series number and<br />

materials of construction.<br />

f. Butterfly valves may be used in all two-position applications and modulating<br />

applications larger than 2", or where the close off rating of other valve<br />

styles does not meet the design requirements.<br />

g. Butterfly valves shall be sized primarily by using velocity calculations to<br />

prevent fluid velocities from exceeding 12 feet per second. For modulating<br />

applications, CV factors at sixty (60) degrees shall be used for determining<br />

delta P once size has been determined by the velocity calculations.<br />

h. High torque industrial valve actuators, >300 in-lb. of rated torque, may be<br />

used where low torque actuators are not suitable. High torque actuators<br />

shall be as manufactured or provided by Belimo.<br />

Actuator/Valve Specification<br />

7. Butterfly Valves – High Performance<br />

a. Butterfly valves, as specified, shall be by Belimo.<br />

b. Butterfly valves 2" to 30" shall have a fully lugged, drilled and tapped,<br />

carbon steel body conforming to ANSI class 150 or class 300 standards.<br />

Flanges shall meet ANSI 150 or ANSI 300 standards. The one-piece<br />

body shall feature an extended neck allowing sufficient clearance for<br />

flanges and 2" of piping insulation.<br />

c. The disc shall be 316 stainless steel and provide bi-directional bubbletight<br />

close off in either direction for chilled or hot water, 50% glycol applications<br />

or steam applications up to the ANSI class limits. The disc shall<br />

employ a 360 degree uninterrupted spherical edge for sealing. The disc<br />

profile shall be designed for maximum flow and equal percentage control.<br />

d. Shaft shall be mechanically retained in the valve body using an<br />

adjustable gland flange. This flange also serves to prevent leakage out<br />

the valve neck by applying a load against TFE Chevron design washers.<br />

These washers provide full ANSI hydrostatic seal to 150% of CWP rating.<br />

e. The RTFE bi-directional seat shall employ an encapsulated elastomeric<br />

o-ring core for resiliency. The seat is retained in the valve body by use of<br />

a retaining ring. The outside diameter of the retaining ring is recessed<br />

within the gasket sealing surface to prevent external leakage. The retaining<br />

ring is held in place by means of a stainless wedge ring.<br />

f. A permanent metal tag shall designate manufacturer, recommended flow<br />

direction, series number and materials of construction.<br />

g. Butterfly valves may be used in all two-position applications and modulating<br />

applications larger than 2", or where the close off rating of other valve<br />

styles does not meet the design requirements.<br />

h. Butterfly valves shall be sized primarily by using velocity calculations to<br />

prevent fluid velocities from exceeding 32 feet per second. For modulating<br />

applications, CV factors at sixty (60) degrees shall be used for determining<br />

delta P once size has been determined by the velocity calculations.<br />

i. High torque industrial valve actuators, >300 in-lb. of rated torque, may be<br />

used where low torque actuators are not suitable. High torque actuators<br />

shall be as manufactured or provided by Belimo.<br />

8. Zone Valves<br />

a. Zone valves, as specified, shall be by Belimo.<br />

b. Zone valves shall be used in terminal unit water applications requiring a<br />

Two-way or Three-way diverting valve in sizes 1’’ and smaller.<br />

c. Zone valves shall have brass bodies with female NPT or sweat ends and<br />

a stainless steel stem.<br />

d. Zone valve actuators shall on/off and shall be available in 24VAC or<br />

120VAC.<br />

e. Zone valve actuators shall have a minimum of 20 psi close-off rating.<br />

f. Zone valves shall have push button for quick removal of actuator.<br />

g. Zone valves shall have a leakage rate of 0.1% or lower<br />

9. Industrial Ball Valves<br />

a. Ball valves, as specified, shall be by Belimo.<br />

b. Two-way and three-way ball valves may be used only if characterized<br />

control valves do not fit the sizing criteria or application.<br />

c. Ball valves may be used for chilled or hot water, steam, or glycol solutions<br />

to 50%. Screwed or flanged water valves shall have modified equal<br />

percentage or modified linear flow characteristics for two-way and threeway<br />

valves, respectively. The ball and stem shall be stainless steel, and<br />

seats will be RPTFE.<br />

d. VS Series screwed ball valves 1/2" through 3" shall have bronze bodies<br />

rated to at least 400 WOG. Flanged ball valves 2" through 10" shall have<br />

cast iron bodies rated to at least 200 WOG. The maximum differential rating<br />

will match the respective valve close-off rating.<br />

e. VSS Series screwed ball valves 1/2" through 3" shall have stainless steel<br />

bodies rated to at least 600 WOG. The maximum differential rating will<br />

match the respective valve close-off rating.<br />

f. VS and VSS series ball valves shall provide bubble-tight close-off capabilities<br />

on all ports up to the specified close-off rating.<br />

79


Terms and Conditions of Sale and Warranty<br />

I. General<br />

1.1. The following Terms and Conditions of Sale (“Terms”) apply<br />

to the sale of products described in this Product Guide<br />

(“Products”). As used herein, “Seller” or “Belimo” refers to<br />

Belimo Aircontrols (USA) Inc. or Belimo Aircontrols (CAN) Inc., as<br />

applicable, and “Client” refers to the individual or business entity<br />

that purchases the Products from Seller. These Terms shall apply<br />

unless the parties mutually agree to different terms and memorialize<br />

such agreement in a writing signed by both Client and Seller.<br />

II. Price<br />

2.1. The Seller’s price for Products (the “Price”) is net, F.O.B.<br />

Point of Origin, and is calculated in US currency for sales made<br />

by Belimo Aircontrols (USA), Inc. and calculated in Canadian<br />

currency for sales made by Belimo Aircontrols (CAN) Inc.<br />

2.1.The Price, unless otherwise agreed upon, does not include<br />

freight and packaging (wooden crates, pallets, etc), the costs<br />

of which will be charged to Client at cost for each shipment and<br />

shall be payable with payment of the Price.<br />

2.3. Orders for Products with a net value of less than US$300<br />

(CAN$450) will be subject to a US$20 (CAN$35) handling fee<br />

(the “Handling Fee”). The Handling Fee will not be charged for<br />

orders of Products with a net value equal to or greater than<br />

US$300 (CAN$450) or for Products ordered through Seller’s<br />

internet ordering system at: www.belimo.com.<br />

2.4. Seller reserves the right to make partial deliveries of orders<br />

of Products, each of which deliveries may be invoiced separately<br />

by Seller.<br />

2.5.The Price does include charges for wiring diagrams, installation,<br />

and commissioning, which will be charged to Client separately<br />

and will be payable on demand.<br />

III. Payment<br />

3.1. Invoices are payable in US currency for sales made by<br />

Belimo Aircontrols (USA), Inc. and in Canadian currency<br />

for sales made by Belimo Aircontrols (CAN) Inc. and are due<br />

no later than 30 days from the date of invoice, without any<br />

deductions.<br />

3.2. If Client fails to pay the entire invoice balance within 60<br />

days from the date of the invoice, Client will be subject to an<br />

interest charge of 2% per month (or the maximum rate permitted<br />

by law, whichever is less) on the outstanding unpaid balance<br />

due to Seller.<br />

3.3. Clients who maintain outstanding balances for 45 days or<br />

more after the date of invoice may be subject to restricted shipments<br />

of Products or may be required to pay for all future deliveries<br />

of Products on a cash-on-delivery basis.<br />

IV. Title and Risk<br />

4.1. Title to all Products shall remain with Seller and shall not<br />

pass to Client until Seller has received full payment for the<br />

Products.<br />

V. Damage or Loss in Transit<br />

5.1. Seller assumes no liability for damage or loss of shipment<br />

of Products, which risk shall at all times remain with the carrier.<br />

All shipments must be unpacked and examined by Client immediately<br />

upon receipt. Any external evidence of loss or damage<br />

must be noted on the freight bill accompanying the shipment of<br />

Products or carrier’s receipt and signed by the carrier’s agent at<br />

the time of delivery. Failure to do so will result in the carrier’s<br />

refusal to honor any claim relating to damage of Products.<br />

Client must also notify Seller of such damage by providing<br />

Seller with a copy of the freight bill or damage report so that<br />

80<br />

Seller can file a claim for loss or damage in transit with the carrier.<br />

If the damage does not become apparent until the shipment<br />

is unpacked, customer must make a request for inspection<br />

by the carrier’s agent and file with the carrier within 15 days<br />

after receipt of product and notify Seller of the same. Seller is<br />

not liable for consequential damage to Client’s property or a<br />

third-party’s property resulting from the installation of damaged<br />

Products.<br />

VI. Delivery<br />

6.1. Seller undertakes to make every attempt to adhere to its<br />

stated delivery parameters and to make a timely delivery of the<br />

Products but does not guarantee any delivery specifications.<br />

Each contract entered into for the purchase of Products is not<br />

cancelable nor is Seller liable for any direct or indirect losses<br />

that may arise, for any reason whatsoever, due to Seller’s failure<br />

to meet any stated or assumed delivery schedules.<br />

VII. Return of Goods<br />

7.1. Products received by Client cannot be returned unless: (i)<br />

Client alerts Seller that it intends to return such Products, (ii)<br />

Seller agrees to accept the return of such Products, (iii) Client<br />

obtains a Return Material Authorization (“RMA”) number from<br />

Seller for the return of such Products, and (iv) Client follows all<br />

return instructions provided by the Seller. The RMA number<br />

must be clearly written on the outside of all packaging for any<br />

returned Products. Only Products returned to proper the location<br />

as instructed by Seller and identified with an RMA number<br />

will be considered for credit.<br />

7.2. Only Products that are returned in original packaging may<br />

be accepted for return. Such returned Products must be<br />

received in good condition, adequate for resale as new<br />

Products to qualify for credit. Client will be responsible for payment<br />

of a restocking charge for all returned Products in an<br />

amount no less than 20% of the invoice value of the Products<br />

(“Restocking Charges”). All return Products must be shipped<br />

to Seller at Client’s cost.<br />

7.3. Returns that result from Seller errors will be credited in full<br />

and will not be subject to Restocking Charges.<br />

VIII. Warranty<br />

VIII.A 5-year Warranty<br />

8.1. Products that are listed in this Product Guide as carrying a<br />

5-year warranty and shipped after May 1, 2000 to a location in<br />

the United States or Canada shall carry a 5-year warranty. The<br />

5-year warranty is unconditional for the first two years from the<br />

date of production of the Products. After the first two years<br />

from the date of Production, the warranty shall be conditional<br />

and the warranty coverage shall not apply to damage to<br />

Products caused by ordinary wear and tear, negligence or<br />

improper use by Client, or other causes beyond the control of<br />

the Seller. Product -specific terms of warranty with regard to<br />

warranty period or conditions of warranty may apply to certain<br />

specified Products as stated in the documentation for those<br />

Products.<br />

VIII.B 2-year Conditional Warranty<br />

8.2. Products that are listed in this Product Guide as carrying a<br />

2-year warranty and shipped after May 1, 2005 to a location in<br />

the United States or Canada shall carry a 2-year warranty. The<br />

2-year warranty is conditional and the warranty coverage shall<br />

not apply to damage to Products caused by ordinary wear and<br />

tear, negligence or improper use by Client, or other causes<br />

beyond the control of the Seller. Product -specific terms of warranty<br />

with regard to warranty period or conditions of warranty<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

® ®<br />

may apply to certain specified Products as stated in the documentation<br />

for those Products.<br />

VIII.C General Warranty Terms<br />

8.3. Seller’s warranty may be null and void in the event of any:<br />

(a) modification or unauthorized repairs of Products by Client,<br />

(b) unauthorized incorporation or integration of Products into<br />

or with Client’s equipment, (c) use of Products in an unauthorized<br />

manner, or (d) damage to Products not caused by Seller.<br />

8.4. Client must promptly notify Seller of Products’ alleged<br />

defect and provide Seller with other evidence and documentation<br />

reasonably requested by Seller. Before removing<br />

Products from service, Client should contact a Seller-authorized<br />

support technician by calling Belimo customer service.<br />

The contact information for Belimo customer service is listed<br />

on the back page of Belimo’s Product Guide and Price List<br />

(“PGPL”) or may be found at www.belimo.com. Belimo customer<br />

service will work with field technicians to troubleshoot<br />

problems. Many problems can be resolved over the phone.<br />

8.5. If a problem cannot be resolved over the phone, an RMA<br />

number will be issued by Seller for return of the Products. Prior<br />

to returning any Products under a warranty, Client must obtain<br />

an RMA number from Seller, along with shipping instructions for<br />

the return. The RMA number must be clearly written on the outside<br />

of the box containing the returned Products. Only Products<br />

returned to the proper location and identified with an RMA number<br />

will be accepted by the Seller.<br />

8.6. All returned Products should be packaged appropriately to<br />

prevent further damage. Seller reserves the right to refuse any<br />

returned material if improperly packaged or labeled (without<br />

an RMA number). Products returned without proper RMA<br />

documentation will void Seller’s warranty.<br />

8.7. Products found to be defective for which a warranty is<br />

applicable will either be replaced or repaired at the Seller’s discretion.<br />

Seller is not responsible for charges that Client may<br />

incur as a result of the removal or replacement of Products.<br />

8.8. Repaired or replacement Products are shipped from<br />

Seller via ground shipment. Other shipping methods are available<br />

at the sole expense of the Client.<br />

8.9. Repaired, replaced or exchanged Products will carry a<br />

warranty for a period of time equal to the greater of: (i) the<br />

remainder of the original 5-year warranty or 2-year warranty<br />

that was applicable to the repaired, replaced or exchanged<br />

Products, or (ii) six months, effective from the date the<br />

repaired, exchanged or replaced Products are shipped by<br />

Seller (the “Replacement Warranty Period”).<br />

8.10. Advanced replacement Products for Products covered<br />

under warranty may be obtained from Seller after the Belimo<br />

customer service troubleshooting process has been completed.<br />

For industrial products (such as butterfly valves), a purchase<br />

order is required. The purchase order will be credited<br />

upon the receipt and verification by Seller of the returned<br />

defective Products. For non-industrial products, an invoice will<br />

be issued and shall be due and payable is the returned<br />

Products are not received by Seller within 60 days from the<br />

date of that the replacement Products are shipped. Additional<br />

charges may apply if the nature of the problem has been misrepresented<br />

by Client.<br />

8.11. Both the conditional and unconditional warranties cover<br />

the Products only, and do NOT cover labor associated with the<br />

troubleshooting, removal or replacement of such Products.<br />

8.12. New Products ordered in an attempt to circumvent the<br />

warranty process may NOT be reimbursed if, upon receipt of<br />

returned Products, it is determined that the defect in the<br />

returned Products is actually field related, or the Products<br />

Terms and Conditions of Sale and Warranty<br />

have been returned for cosmetic reasons only.<br />

8.13. Advanced replacement Products for butterfly valve actuators<br />

may not be new, but have been verified by the Seller for<br />

electrical and mechanical operation. Such Products carry the<br />

full warranty for the entire Replacement Warranty Period.<br />

IX. No Warranty for Non-HVAC Application<br />

9.1. All Seller warranties shall extend only to HVAC use of the<br />

Products. If Products are used in non-HVAC application (e.g.,<br />

aircraft, industrial processes, etc.), Seller’s warranties shall not<br />

cover such Products. Client will be solely responsible for any<br />

damage to or malfunction of Products or for any damage<br />

resulting from such use of Products.<br />

X. Liability Disclaimer<br />

10.1. These Terms constitute the entire understanding and<br />

agreement between Seller and Client regarding the warranties<br />

that cover Products and supersedes all previous understandings,<br />

agreements, communications and representations.<br />

Seller shall not be responsible for and Client does not have<br />

any right to make any claim for, damage that occurs to any<br />

property other than Products. Seller shall in no way be<br />

responsible for any costs incurred by Client in the determination<br />

of the causes of damage to any of Client’s property, for<br />

expert opinions, or for any punitive or special, incidental or<br />

consequential damages of any kind whatsoever.<br />

10.2. Seller shall not be liable for any damage resulting from or<br />

contributed by Client or third parties acting within the scope of<br />

responsibility of Client or such third party when:<br />

1. Products are used for non-HVAC applications, such as in<br />

aircrafts, industrial processes, etc.;<br />

2. Client uses the Products without complying with applicable<br />

law or institutional regulations or Belimo data and installation<br />

sheets or Client uses the Products without following<br />

good industry practice;<br />

3. Products are used by personnel who have not received<br />

suitable instruction; or<br />

4. Products are modified or repaired without the written<br />

approval of Seller.<br />

When requested to do so, Client shall immediately release<br />

Seller in full from any possible third party claims resulting in<br />

connection with the circumstances listed above. This also<br />

applies to claims in connection with product liability.<br />

10.3. If Client becomes aware that any third party has made or<br />

appears likely to make any claim regarding Products (including,<br />

without limitation, regarding Product defects or rights infringed<br />

by Products), then Client shall immediately inform Seller and<br />

afford to Seller all assistance that Seller may require to enforce<br />

its rights and defend such claim.<br />

XI. Proper Law and Jurisdiction<br />

11.1. All sales of Products under these Terms and the warranties<br />

described herein shall be governed by the laws of the<br />

State of Connecticut, and the parties agree to submit to the<br />

exclusive jurisdiction of the Federal and state courts located in<br />

the State of Connecticut with respect to any dispute arising<br />

from the subject matter hereof. The parties hereby waive all<br />

rights to a jury trial in connection with any claims relating to the<br />

subject matter hereof.<br />

81


®<br />

Custom MFT Configuration Order Form<br />

FAX: USA Toll Free 1-800-228-8283<br />

#1 Select an Actuator<br />

(use one sheet for each unique actuator/configuration)<br />

❑ AF24-MFT US<br />

❑ AF24-MFT-S US<br />

❑ NF24-MFT US<br />

❑ LF24-MFT US<br />

❑ LF24-MFT-S US<br />

❑ AF24-MFT95 US<br />

❑ NV24-MFT US<br />

❑ NVF24-MFT US<br />

❑ NVF24-MFT-E US<br />

❑ NVFD24-MFT US<br />

❑ NVFD24-MFT-E US<br />

Control Types<br />

➁<br />

Feedback signals U 5<br />

➂<br />

Running time<br />

➃<br />

82<br />

Quantity<br />

Override control and<br />

electronic angle of rotation<br />

limiting<br />

➄<br />

❑ GMX24-MFT<br />

❑ AMX24-MFT<br />

❑ NMX24-MFT<br />

❑ LMX24-MFT<br />

❑ LRX24-MFT<br />

❑ GMX24-MFT95<br />

❑ AMX24-MFT95<br />

❑ NMX24-MFT95<br />

❑ LMX24-MFT95<br />

(-S=Auxiliary Switch)<br />

#2 Create a Custom Configuration<br />

Quantity<br />

Angle of rotation setting<br />

Deactivated (Default)<br />

➀ Activated<br />

VDC PWM Floating On/Off<br />

2 – 10 0.2 to 5.0 sec.<br />

0 – 10 0.1 to 25.5 sec.<br />

Variable 0.59 to 2.93 sec.<br />

Start .<br />

Manual triggering by pressing the pushbutton twice<br />

Automatic triggering each time the unit is powered up<br />

or by pressing the pushbutton twice.<br />

Variable<br />

Stop . Start .<br />

Stop .<br />

Position Feedback U DC 2...10 V (Default)<br />

Position Feedback U DC 0...10 V<br />

Position Feedback U<br />

150 s (Default)<br />

Name ____________________________________________________________________________________<br />

Company__________________________________________________________________________________<br />

Address __________________________________________________________________________________<br />

City ________________________________________________________ State ____ Zip________________<br />

Phone ____________________________________ Fax __________________________________________<br />

Email ____________________________________<br />

Field Labeling: LBL-MFT<br />

❑ Custom configuration labels required<br />

1-3/8” X 1-1/4” orange labels preprinted to your specifications<br />

12 label sets per sheet. Includes configuration code and wiring labels.<br />

Start DC . V (0...8 V)<br />

Finish DC . V (2...10 V)<br />

Running time s (75...300 s) (in 5 sec. increments)<br />

Note: The sound power level [dB(A)] increases<br />

when the running time is below 150 s.<br />

➁ ➄<br />

The following settings - refer to the full angle of<br />

rotation of 95º.<br />

The following settings ➁ - ➄ are automatically adapted<br />

to the effective mechanical angle of rotation.<br />

LM 35…150 s<br />

NM 45…170 s<br />

AM 90…300 s<br />

GM 90…300 s<br />

Others 75…300 s<br />

The finish must<br />

be at least 2 V<br />

above the start!<br />

Min. (min. position) = % (0...100%) (beginning of working range) default 0<br />

ZS (intermediate position) = % (0...100%) (0% = Min.; 100% = Max.) default 50<br />

Max.(max. position) = % (0...100%) (end of working range) default 100<br />

®<br />

J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.


J20728 - 04/07 - Subject to change. © Belimo Aircontrols (USA), Inc.<br />

USA<br />

ACR Supply Company Inc.<br />

2719 Hillsborough Road<br />

Durham, NC 27705<br />

Phone: 919-286-2228<br />

With branches in NC<br />

Aireco Supply<br />

9120 Washington Boulevard<br />

Savage, MD 20763-0414<br />

Phone: 301-953-8800<br />

With branches in MD, VA<br />

Amcon Controls, Inc.<br />

11906 Warfield Street<br />

San Antonio,TX 78216<br />

Phone: 210-349-6161<br />

With branch in Houston, TX<br />

Applied Automation<br />

A Wilson Mohr Company<br />

3186 South Washington Street, #230<br />

Salt Lake City, UT 84115<br />

Phone: 801-486-6454<br />

Boston Aircontrols, Inc.<br />

8 Blanchard Road<br />

Burlington, MA 01803<br />

Phone: 781-272-5800<br />

Charles D. Jones Co.<br />

445 Bryant Street, Unit #1<br />

Denver, CO. 80204-4800<br />

Phone: 800-777-0910<br />

With branches in CO, MO, KS<br />

Climatic Control Co., Inc.<br />

5061 W. State Street<br />

Milwaukee, WI 53208<br />

Phone: 800-242-1656<br />

With branches in WI, IL<br />

Cochrane Supply and Engineering, Inc.<br />

30303 Stephenson Highway<br />

Madison Heights, MI 48071-1633<br />

Phone: 800-482-4894<br />

With branches in MI<br />

Columbus Temperature Control<br />

1053 E. 5th Avenue<br />

Columbus, OH 43201<br />

Phone: 800-837-1837<br />

Controlco<br />

5600 Imhoff Drive, Suite G<br />

Concord, CA 94520<br />

Phone: 925-602-7728<br />

With branches in CA<br />

Edward C. Smyers & Co.<br />

223 Fort Pitt Boulevard<br />

Pittsburgh, PA 15222-1505<br />

Phone: 412-471-3222<br />

First Source Distributors, LLC<br />

710 Peninsula Lane, Suite E<br />

Charlotte, NC 28273<br />

Phone: 800-670-5977<br />

G & O Thermal Supply<br />

5435 N. Northwest Highway<br />

Chicago, IL 60630<br />

Phone: 773-763-1300<br />

With branches in IL<br />

Industrial Controls Distributors LLC<br />

1776 Bloomsbury Avenue<br />

Wanamassa, NJ 07712<br />

Phone: 800-631-2112<br />

With branches in<br />

KY, ME, NC, NY, OH, PA, TN, MA, GA, WI, IL<br />

Interstate HVAC Controls<br />

30 Vineland Street<br />

Brighton, MA 02135<br />

Phone: 617-782-9000<br />

Jackson Controls<br />

1708 E. 10th Street<br />

Indianapolis, IN 46201<br />

Phone: 317-231-2200<br />

M & M Controls<br />

9E West Aylesbury Road<br />

Timonium, MD 21093<br />

Phone: 410-252-1221<br />

Meier Supply<br />

123 Brown Street<br />

Johnson City, NY 13790<br />

Phone: 607-797-7700<br />

With branches in NY, PA<br />

MICONTROLS, Inc.<br />

6516 5th Place South<br />

Seattle, WA 98124<br />

Phone: 800-877-8026<br />

With branches in WA, OR<br />

Minvalco, Inc.<br />

3340 Gorham Avenue<br />

Minneapolis, MN 55426-4267<br />

Phone: 952-920-0131<br />

With branches in MN<br />

RSD/Total Control<br />

26021 Atlantic Ocean Drive<br />

Lake Forest, CA 92630<br />

Phone: 949-380-7878<br />

With branches in<br />

CA, NV, OR, AK, AZ, ID, UT, WA<br />

Saint Louis Boiler Supply, Co.<br />

617 Hanley Industrial Court<br />

St. Louis, MO 63144<br />

Phone: 314-962-9242<br />

South Side Control Supply, Co.<br />

488 N. Milwaukee Avenue<br />

Chicago, IL 60610-3923<br />

Phone: 312-226-4900<br />

With branches in IL, IN<br />

Stromquist and Company<br />

4620 Atlanta Road<br />

Smyrna, GA 30080<br />

Phone: 404-794-3440<br />

With branch in FL<br />

Temperature Control Systems<br />

10315 Brockwood Road<br />

Dallas, TX 75238<br />

Phone: 214-343-1444<br />

With branches in OK, TX<br />

Tower Equipment Co., Inc.<br />

1320 West Broad Street<br />

Stratford, CT 06615<br />

Phone: 800-346-4647<br />

Twinco Supply Corporation<br />

55 Craven Street<br />

Huntington Station, NY 11746-2143<br />

Phone: 800-794-3188<br />

With branches in NY<br />

Belimo Platinum Distributors<br />

Airex<br />

C - 5 Sandhill Court<br />

Brampton, ON, L6T 5J5<br />

Phone: 905-790-8667<br />

Baymar Supply Co.<br />

3200 Jefferson Boulevard<br />

Windsor, ON, N8T 2W8<br />

Phone: 519-974-5800<br />

With branch in London, ON<br />

Le Groupe Master<br />

1675 de Montarville<br />

Boucherville, QC, J4B 7W4<br />

Phone: 514-527-2301<br />

With branches across Eastern Canada<br />

O’Dell Associates Inc.<br />

#3 - 1038 Cooke Boulevard<br />

Burlington, ON, L7T 4A8<br />

Phone: 905-681-3901<br />

Prokontrol<br />

1989 Michelin<br />

Laval, QC, H7L 5B7<br />

Phone: 450-973-7765<br />

With branches in Ville Vanier and Ontario<br />

Refrigerative Supply<br />

3958 Myrtle Street, Burnaby, BC, V5C 4G2<br />

Phone: 604-435-7151<br />

With branches in British Columbia,<br />

Alberta, Saskatchewan,Manitoba<br />

Regal Controls<br />

1156 Kingsway<br />

Vancouver, BC V5V 3C8<br />

Phone: 604-879-6357<br />

With branch in Langley<br />

Regulvar Laval<br />

1985 Boul Industriel Laval, QC, H7S-1P6<br />

Phone: 450-629-0435<br />

With branches in Sherbrooke,<br />

St. Hubert, Lachine, Quebec City<br />

Regulvar Ottawa Inc.<br />

170 Laurier Ax West Suite 714<br />

Ottawa, Ontario, K1P-5V6<br />

Phone: 613-565-2129<br />

With branch in Gatineau<br />

Sinclair Supply<br />

10914 - 120 Street<br />

Edmonton, AB, T5H 3P7<br />

Phone: 780-452-3110<br />

With branches in British Columbia,<br />

Alberta, Saskatchewan<br />

SCI<br />

3311 Boul Industriel<br />

Laval, QC, H7L 4S3<br />

Phone: 450-668-8866<br />

Wiles & Legault<br />

#5 - 505 Industriel Avenue<br />

Ottawa, ON, K1G 0Z1<br />

Phone: 613-747-1867<br />

Yorkland Controls<br />

2689 Steeles Avenue, W.<br />

Downsview, ON, M3J 2Z8<br />

Phone: 416-661-3306<br />

With branch in Mississauga<br />

800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA<br />

CANADA


HVAC Division<br />

t. (81) 8333-7738 · (81) 8333-7717<br />

e. info@duralitte.com.mx<br />

www.duralitte.com.mx


Belimo worldwide: www.belimo.com<br />

BELIMO Americas<br />

USA Locations, 43 Old Ridgebury Road, Danbury, CT 06810<br />

Tel. 800-543-9038, Fax 800-228-8283, marketing@us.belimo.com<br />

1675 East Prater Way, Suite 101, Sparks, NV 89434<br />

Tel. 800 987-9042, Fax 800-987-8875, marketing@us.belimo.com<br />

Canada Locations, 14/16 – 5716 Coopers Avenue, Mississauga, Ontario L4Z 2E8<br />

Tel. 866-805-7089, Fax 905-712-3124, marketing@us.belimo.com<br />

Latin America Customer Service, Tel. 203-791-8396, Fax 203-791-9139, marketing@us.belimo.com