High-Current and Generator Switchgear - Siemens Energy
High-Current and Generator Switchgear - Siemens Energy
High-Current and Generator Switchgear - Siemens Energy
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>High</strong>-<strong>Current</strong> <strong>and</strong><br />
<strong>Generator</strong> <strong>Switchgear</strong><br />
Reliable <strong>and</strong> cost-efficient – in every way<br />
Power Transmission <strong>and</strong> Distribution
2<br />
<strong>Siemens</strong> –<br />
Partner of the power plant sector<br />
The growing energy dem<strong>and</strong> calls for<br />
more <strong>and</strong> fail-safe power from the<br />
power plants – <strong>and</strong> the cost pressure<br />
on the market dem<strong>and</strong>s a higher efficiency<br />
in the provision of energy.<br />
As a pioneer for vacuum switching technology,<br />
<strong>Siemens</strong> has developed solutions<br />
<strong>and</strong> technologies for the reliable transmission<br />
<strong>and</strong> distribution of electrical<br />
power from power plants to consumers<br />
for more than 30 years. The resulting<br />
comprehensive know-how is reflected in<br />
our high-quality solutions <strong>and</strong> services.<br />
Be it availability, cost-efficiency or safety:<br />
As power plant builders or operators you<br />
are confronted with maximum requirements<br />
at all times. So, it is just reasonable<br />
to expect the same from crucial components<br />
such as the generator switchgear.<br />
More safety <strong>and</strong> reliability – from <strong>Siemens</strong><br />
Therefore, generator switchgear from<br />
<strong>Siemens</strong> offers maximum efficiency <strong>and</strong><br />
safety – on the whole as well as for every<br />
single component, e.g. especially for the<br />
centerpiece of the switchgear, the generator<br />
vacuum circuit-breaker: To guarantee<br />
availability <strong>and</strong> performance, high-current<br />
<strong>and</strong> generator switchgear assemblies are<br />
equipped with circuit-breakers that withst<strong>and</strong><br />
maximum stress.<br />
With our generator switchgear you are always on the safe side.<br />
Regardless of the switchgear type you decide for, you will obtain:<br />
<br />
<br />
<br />
<strong>High</strong> reliability due to the intelligent <strong>and</strong> proven switchgear design<br />
<strong>and</strong> the use of reliable components tested to the st<strong>and</strong>ards<br />
<strong>High</strong> security of operation due to clear switching operations<br />
<strong>High</strong> personal safety due to safety-oriented design of the switchgear<br />
<br />
<strong>High</strong> cost-efficiency due to maintenance-free or low-maintenance components
<strong>Switchgear</strong> details that pay off:<br />
Our high-current <strong>and</strong> generator switchgear<br />
with the proven vacuum switching<br />
technology from <strong>Siemens</strong> is designed to<br />
withst<strong>and</strong> maximum normal currents,<br />
featuring durable contact materials,<br />
an optimized design in respect of cooling<br />
as well as maximum mechanical<br />
stability. The generator circuit-breaker<br />
meets the severe requirements of the<br />
generator circuit-breaker st<strong>and</strong>ard<br />
IEEE C37.013, demonstrating its outst<strong>and</strong>ing<br />
qualities.<br />
This increases the performance, reliability,<br />
<strong>and</strong> cost-efficiency of the complete<br />
generator switchgear.<br />
More efficiency –<br />
with powerful circuit-breakers<br />
<br />
<br />
<br />
<br />
<strong>High</strong> mechanical stability<br />
Low fire load due to omission<br />
of solid insulation<br />
Without forced cooling up to maximum<br />
current ratings – thanks to the utilization<br />
of natural convection<br />
Ecological <strong>and</strong>, at the same time,<br />
operationally safe vacuum switching<br />
technology<br />
3
HIGS<br />
<strong>High</strong>ly integrated<br />
generator switchgear<br />
With the highly integrated generator<br />
switchgear, <strong>Siemens</strong> enables more functionality<br />
on less space. For the first time,<br />
the neutral treatment of the generator as<br />
well as the auxiliary feeder are integrated<br />
in a single generator switchgear. The<br />
switchgear can be installed both indoors<br />
<strong>and</strong> outdoors: close to the generator,<br />
without expensive cabling.<br />
All functions are therefore available out<br />
of one h<strong>and</strong> – without time-consuming<br />
coordination between different suppliers,<br />
which offers considerable cost savings<br />
due to ...<br />
... lower expenditure for:<br />
<br />
<br />
<br />
Planning<br />
Investment<br />
Installation<br />
… lower dem<strong>and</strong> for:<br />
<br />
<br />
<br />
Space<br />
Material (cabling)<br />
Service<br />
Technical data<br />
Air-insulated, metal-enclosed<br />
For indoor <strong>and</strong> outdoor installation<br />
Rated voltage: Max. 13.8 kV<br />
(110 kV BIL / 50 kV PFWV)<br />
Rated short-circuit-breaking current I SC :<br />
31.5 – 63 kA<br />
Rated normal current: 2,000 – 3,150 A<br />
Circuit-breaker:<br />
<strong>Generator</strong> circuit-breaker according<br />
to IEEE C37.013, or circuit-breaker<br />
according to IEC 62271-100<br />
Dimensions (L x W x H):<br />
3,430 x 1,200 x 2,500 mm<br />
Equipment (optional):<br />
<strong>Generator</strong> circuit-breaker in<br />
the main transformer feeder<br />
Disconnector in the main<br />
transformer feeder<br />
Earthing switch on generator<br />
<strong>and</strong> transformer side<br />
<strong>Current</strong> <strong>and</strong> voltage transformers<br />
Surge arresters<br />
Surge capacitors<br />
Options:<br />
Integrated auxiliary feeder with<br />
disconnector <strong>and</strong> generator circuitbreaker<br />
or with switch-disconnector<br />
<strong>and</strong> fuses<br />
8BK40<br />
Metal-enclosed generator switchgear<br />
with truck-type circuit-breaker<br />
Technical data<br />
Air-insulated, metal-enclosed<br />
For indoor installation<br />
Rated voltage: Max. 17.5 kV<br />
(95 kV BIL / 38 kV PFWV)<br />
Rated short-circuit-breaking current I SC :<br />
50 kA / 63 kA<br />
Rated normal currents:<br />
Rated normal current of the<br />
busbar, max. 5,000 A<br />
Rated normal current of the<br />
feeder, max. 5,000 A<br />
Circuit-breaker:<br />
<strong>Generator</strong> circuit-breaker according<br />
to IEEE C37.013, or circuit-breaker<br />
according to IEC 62271-100<br />
Dimensions (L x W x H):<br />
2,300 x 1,100 x 2,500 mm<br />
Equipment (optional):<br />
<br />
<br />
<br />
<br />
<br />
<br />
<strong>Generator</strong> circuit-breaker<br />
Disconnecting function by means<br />
of truck-type circuit-breaker<br />
Earthing switch on generator <strong>and</strong><br />
transformer side<br />
<strong>Current</strong> <strong>and</strong> voltage transformers<br />
Surge arresters<br />
Surge capacitors<br />
4
HB1<br />
Horizontal busbar switchgear –<br />
not phase-segregated<br />
Technical data<br />
Air-insulated, metal-enclosed<br />
For indoor installation<br />
Rated voltage: Max. 17.5 kV<br />
(110 kV BIL / 50 kV PFWV)<br />
Rated short-circuit-breaking current I SC :<br />
50 kA / 63 kA / 72 kA<br />
Rated normal current<br />
(with natural cooling):<br />
Max. 6,100 A<br />
Circuit-breaker:<br />
<strong>Generator</strong> circuit-breaker according<br />
to IEEE C37.013<br />
Dimensions (L x W x H):<br />
4,000 x 1,900 x 2,500 mm<br />
(can vary depending on the<br />
equipment)<br />
Equipment (optional):<br />
<br />
<br />
<br />
<br />
<br />
<br />
<strong>Generator</strong> circuit-breaker<br />
Disconnector<br />
Earthing switch on generator <strong>and</strong><br />
transformer side<br />
<strong>Current</strong> <strong>and</strong> voltage transformers<br />
Surge arresters<br />
Surge capacitors<br />
Options:<br />
<br />
<br />
<br />
<br />
Integrated SFC starter<br />
Integrated auxiliary feeder, with<br />
generator circuit-breaker or with<br />
switch-disconnector <strong>and</strong> fuses<br />
Integrated excitation feeder<br />
Brake switch<br />
HB1 Outdoor<br />
Horizontal busbar switchgear –<br />
not phase-segregated<br />
Technical data<br />
Air-insulated, metal-enclosed<br />
For outdoor installation<br />
Rated voltage: Max. 17.5 kV<br />
(110 kV BIL / 50 kV PFWV)<br />
Rated short-circuit-breaking current I SC :<br />
50 kA / 63 kA / 72 kA<br />
Rated normal current<br />
(with natural cooling):<br />
Max. 5,400 A<br />
Circuit-breaker:<br />
<strong>Generator</strong> circuit-breaker according<br />
to IEEE C37.013<br />
Dimensions (L x W x H):<br />
6,300 x 1,900 x 2,600 mm<br />
(can vary depending on the<br />
equipment)<br />
Equipment (optional):<br />
<br />
<br />
<br />
<br />
<br />
<br />
<strong>Generator</strong> circuit-breaker<br />
Disconnector<br />
Earthing switch on generator <strong>and</strong><br />
transformer side<br />
<strong>Current</strong> <strong>and</strong> voltage transformers<br />
Surge arresters<br />
Surge capacitors<br />
Options:<br />
<br />
<br />
<br />
<br />
Integrated SFC starter<br />
Integrated auxiliary feeder, with<br />
generator circuit-breaker or with<br />
switch-disconnector <strong>and</strong> fuses<br />
Integrated excitation feeder<br />
Brake switch<br />
HB3<br />
Horizontal busbar switchgear –<br />
phase-segregated<br />
Technical data<br />
Air-insulated, metal-enclosed<br />
For indoor <strong>and</strong> outdoor installation<br />
Rated voltage: Max. 17.5 kV<br />
(110 kV BIL / 50 kV PFWV)<br />
Rated short-circuit-breaking current I SC :<br />
50 kA / 63 kA / 72 kA<br />
Rated normal current<br />
(with natural cooling):<br />
Max. 10,000 A<br />
Circuit-breaker:<br />
<strong>Generator</strong> circuit-breaker according<br />
to IEEE C37.013<br />
Dimensions (L x W x H):<br />
2,900 x 4,040 x 2,400 mm<br />
(can vary depending on the<br />
equipment)<br />
Equipment (optional):<br />
<br />
<br />
<br />
<br />
<br />
<br />
<strong>Generator</strong> circuit-breaker<br />
Disconnector<br />
Earthing switch on generator <strong>and</strong><br />
transformer side<br />
<strong>Current</strong> <strong>and</strong> voltage transformers<br />
Surge arresters<br />
Surge capacitors<br />
Options:<br />
<br />
<br />
<br />
<br />
Integrated SFC starter<br />
Integrated auxiliary feeder, with<br />
generator circuit-breaker or with<br />
switch-disconnector <strong>and</strong> fuses<br />
Integrated excitation feeder<br />
Brake switch<br />
5
<strong>Siemens</strong> AG<br />
Power Transmission <strong>and</strong> Distribution<br />
Medium Voltage Division<br />
Mozartstraße 31 c<br />
D-91052 Erlangen<br />
Germany<br />
www.siemens.com/energy<br />
If you have any question about<br />
Power Transmission <strong>and</strong> Distribution,<br />
our Customer Support Center is<br />
available around the clock.<br />
Tel.: +49 180 / 524 70 00<br />
Fax: +49 180 / 524 24 71<br />
(Charges depending on provider)<br />
E-mail: support.energy@siemens.com<br />
www.siemens.com/energy-support<br />
The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.<br />
The required features should therefore be specified in each individual case at the time of closing the contract.<br />
Subject to change without prior notice<br />
Order no. E50001-U229-A262-X-7600<br />
Printed in Germany<br />
Dispo 40400<br />
GB 071139 101855 WS 1207