<strong>High</strong>-<strong>Current</strong> <strong>and</strong><br />

<strong>Generator</strong> <strong>Switchgear</strong><br />

Reliable <strong>and</strong> cost-efficient – in every way<br />

Power Transmission <strong>and</strong> Distribution


2<br />

<strong>Siemens</strong> –<br />

Partner of the power plant sector<br />

The growing energy dem<strong>and</strong> calls for<br />

more <strong>and</strong> fail-safe power from the<br />

power plants – <strong>and</strong> the cost pressure<br />

on the market dem<strong>and</strong>s a higher efficiency<br />

in the provision of energy.<br />

As a pioneer for vacuum switching technology,<br />

<strong>Siemens</strong> has developed solutions<br />

<strong>and</strong> technologies for the reliable transmission<br />

<strong>and</strong> distribution of electrical<br />

power from power plants to consumers<br />

for more than 30 years. The resulting<br />

comprehensive know-how is reflected in<br />

our high-quality solutions <strong>and</strong> services.<br />

Be it availability, cost-efficiency or safety:<br />

As power plant builders or operators you<br />

are confronted with maximum requirements<br />

at all times. So, it is just reasonable<br />

to expect the same from crucial components<br />

such as the generator switchgear.<br />

More safety <strong>and</strong> reliability – from <strong>Siemens</strong><br />

Therefore, generator switchgear from<br />

<strong>Siemens</strong> offers maximum efficiency <strong>and</strong><br />

safety – on the whole as well as for every<br />

single component, e.g. especially for the<br />

centerpiece of the switchgear, the generator<br />

vacuum circuit-breaker: To guarantee<br />

availability <strong>and</strong> performance, high-current<br />

<strong>and</strong> generator switchgear assemblies are<br />

equipped with circuit-breakers that withst<strong>and</strong><br />

maximum stress.<br />

With our generator switchgear you are always on the safe side.<br />

Regardless of the switchgear type you decide for, you will obtain:<br />

<br />

<br />

<br />

<strong>High</strong> reliability due to the intelligent <strong>and</strong> proven switchgear design<br />

<strong>and</strong> the use of reliable components tested to the st<strong>and</strong>ards<br />

<strong>High</strong> security of operation due to clear switching operations<br />

<strong>High</strong> personal safety due to safety-oriented design of the switchgear<br />

<br />

<strong>High</strong> cost-efficiency due to maintenance-free or low-maintenance components


<strong>Switchgear</strong> details that pay off:<br />

Our high-current <strong>and</strong> generator switchgear<br />

with the proven vacuum switching<br />

technology from <strong>Siemens</strong> is designed to<br />

withst<strong>and</strong> maximum normal currents,<br />

featuring durable contact materials,<br />

an optimized design in respect of cooling<br />

as well as maximum mechanical<br />

stability. The generator circuit-breaker<br />

meets the severe requirements of the<br />

generator circuit-breaker st<strong>and</strong>ard<br />

IEEE C37.013, demonstrating its outst<strong>and</strong>ing<br />

qualities.<br />

This increases the performance, reliability,<br />

<strong>and</strong> cost-efficiency of the complete<br />

generator switchgear.<br />

More efficiency –<br />

with powerful circuit-breakers<br />

<br />

<br />

<br />

<br />

<strong>High</strong> mechanical stability<br />

Low fire load due to omission<br />

of solid insulation<br />

Without forced cooling up to maximum<br />

current ratings – thanks to the utilization<br />

of natural convection<br />

Ecological <strong>and</strong>, at the same time,<br />

operationally safe vacuum switching<br />

technology<br />

3


HIGS<br />

<strong>High</strong>ly integrated<br />

generator switchgear<br />

With the highly integrated generator<br />

switchgear, <strong>Siemens</strong> enables more functionality<br />

on less space. For the first time,<br />

the neutral treatment of the generator as<br />

well as the auxiliary feeder are integrated<br />

in a single generator switchgear. The<br />

switchgear can be installed both indoors<br />

<strong>and</strong> outdoors: close to the generator,<br />

without expensive cabling.<br />

All functions are therefore available out<br />

of one h<strong>and</strong> – without time-consuming<br />

coordination between different suppliers,<br />

which offers considerable cost savings<br />

due to ...<br />

... lower expenditure for:<br />

<br />

<br />

<br />

Planning<br />

Investment<br />

Installation<br />

… lower dem<strong>and</strong> for:<br />

<br />

<br />

<br />

Space<br />

Material (cabling)<br />

Service<br />

Technical data<br />

Air-insulated, metal-enclosed<br />

For indoor <strong>and</strong> outdoor installation<br />

Rated voltage: Max. 13.8 kV<br />

(110 kV BIL / 50 kV PFWV)<br />

Rated short-circuit-breaking current I SC :<br />

31.5 – 63 kA<br />

Rated normal current: 2,000 – 3,150 A<br />

Circuit-breaker:<br />

<strong>Generator</strong> circuit-breaker according<br />

to IEEE C37.013, or circuit-breaker<br />

according to IEC 62271-100<br />

Dimensions (L x W x H):<br />

3,430 x 1,200 x 2,500 mm<br />

Equipment (optional):<br />

<strong>Generator</strong> circuit-breaker in<br />

the main transformer feeder<br />

Disconnector in the main<br />

transformer feeder<br />

Earthing switch on generator<br />

<strong>and</strong> transformer side<br />

<strong>Current</strong> <strong>and</strong> voltage transformers<br />

Surge arresters<br />

Surge capacitors<br />

Options:<br />

Integrated auxiliary feeder with<br />

disconnector <strong>and</strong> generator circuitbreaker<br />

or with switch-disconnector<br />

<strong>and</strong> fuses<br />

8BK40<br />

Metal-enclosed generator switchgear<br />

with truck-type circuit-breaker<br />

Technical data<br />

Air-insulated, metal-enclosed<br />

For indoor installation<br />

Rated voltage: Max. 17.5 kV<br />

(95 kV BIL / 38 kV PFWV)<br />

Rated short-circuit-breaking current I SC :<br />

50 kA / 63 kA<br />

Rated normal currents:<br />

Rated normal current of the<br />

busbar, max. 5,000 A<br />

Rated normal current of the<br />

feeder, max. 5,000 A<br />

Circuit-breaker:<br />

<strong>Generator</strong> circuit-breaker according<br />

to IEEE C37.013, or circuit-breaker<br />

according to IEC 62271-100<br />

Dimensions (L x W x H):<br />

2,300 x 1,100 x 2,500 mm<br />

Equipment (optional):<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>Generator</strong> circuit-breaker<br />

Disconnecting function by means<br />

of truck-type circuit-breaker<br />

Earthing switch on generator <strong>and</strong><br />

transformer side<br />

<strong>Current</strong> <strong>and</strong> voltage transformers<br />

Surge arresters<br />

Surge capacitors<br />

4


HB1<br />

Horizontal busbar switchgear –<br />

not phase-segregated<br />

Technical data<br />

Air-insulated, metal-enclosed<br />

For indoor installation<br />

Rated voltage: Max. 17.5 kV<br />

(110 kV BIL / 50 kV PFWV)<br />

Rated short-circuit-breaking current I SC :<br />

50 kA / 63 kA / 72 kA<br />

Rated normal current<br />

(with natural cooling):<br />

Max. 6,100 A<br />

Circuit-breaker:<br />

<strong>Generator</strong> circuit-breaker according<br />

to IEEE C37.013<br />

Dimensions (L x W x H):<br />

4,000 x 1,900 x 2,500 mm<br />

(can vary depending on the<br />

equipment)<br />

Equipment (optional):<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>Generator</strong> circuit-breaker<br />

Disconnector<br />

Earthing switch on generator <strong>and</strong><br />

transformer side<br />

<strong>Current</strong> <strong>and</strong> voltage transformers<br />

Surge arresters<br />

Surge capacitors<br />

Options:<br />

<br />

<br />

<br />

<br />

Integrated SFC starter<br />

Integrated auxiliary feeder, with<br />

generator circuit-breaker or with<br />

switch-disconnector <strong>and</strong> fuses<br />

Integrated excitation feeder<br />

Brake switch<br />

HB1 Outdoor<br />

Horizontal busbar switchgear –<br />

not phase-segregated<br />

Technical data<br />

Air-insulated, metal-enclosed<br />

For outdoor installation<br />

Rated voltage: Max. 17.5 kV<br />

(110 kV BIL / 50 kV PFWV)<br />

Rated short-circuit-breaking current I SC :<br />

50 kA / 63 kA / 72 kA<br />

Rated normal current<br />

(with natural cooling):<br />

Max. 5,400 A<br />

Circuit-breaker:<br />

<strong>Generator</strong> circuit-breaker according<br />

to IEEE C37.013<br />

Dimensions (L x W x H):<br />

6,300 x 1,900 x 2,600 mm<br />

(can vary depending on the<br />

equipment)<br />

Equipment (optional):<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>Generator</strong> circuit-breaker<br />

Disconnector<br />

Earthing switch on generator <strong>and</strong><br />

transformer side<br />

<strong>Current</strong> <strong>and</strong> voltage transformers<br />

Surge arresters<br />

Surge capacitors<br />

Options:<br />

<br />

<br />

<br />

<br />

Integrated SFC starter<br />

Integrated auxiliary feeder, with<br />

generator circuit-breaker or with<br />

switch-disconnector <strong>and</strong> fuses<br />

Integrated excitation feeder<br />

Brake switch<br />

HB3<br />

Horizontal busbar switchgear –<br />

phase-segregated<br />

Technical data<br />

Air-insulated, metal-enclosed<br />

For indoor <strong>and</strong> outdoor installation<br />

Rated voltage: Max. 17.5 kV<br />

(110 kV BIL / 50 kV PFWV)<br />

Rated short-circuit-breaking current I SC :<br />

50 kA / 63 kA / 72 kA<br />

Rated normal current<br />

(with natural cooling):<br />

Max. 10,000 A<br />

Circuit-breaker:<br />

<strong>Generator</strong> circuit-breaker according<br />

to IEEE C37.013<br />

Dimensions (L x W x H):<br />

2,900 x 4,040 x 2,400 mm<br />

(can vary depending on the<br />

equipment)<br />

Equipment (optional):<br />

<br />

<br />

<br />

<br />

<br />

<br />

<strong>Generator</strong> circuit-breaker<br />

Disconnector<br />

Earthing switch on generator <strong>and</strong><br />

transformer side<br />

<strong>Current</strong> <strong>and</strong> voltage transformers<br />

Surge arresters<br />

Surge capacitors<br />

Options:<br />

<br />

<br />

<br />

<br />

Integrated SFC starter<br />

Integrated auxiliary feeder, with<br />

generator circuit-breaker or with<br />

switch-disconnector <strong>and</strong> fuses<br />

Integrated excitation feeder<br />

Brake switch<br />

5


<strong>Siemens</strong> AG<br />

Power Transmission <strong>and</strong> Distribution<br />

Medium Voltage Division<br />

Mozartstraße 31 c<br />

D-91052 Erlangen<br />

Germany<br />

www.siemens.com/energy<br />

If you have any question about<br />

Power Transmission <strong>and</strong> Distribution,<br />

our Customer Support Center is<br />

available around the clock.<br />

Tel.: +49 180 / 524 70 00<br />

Fax: +49 180 / 524 24 71<br />

(Charges depending on provider)<br />

E-mail: support.energy@siemens.com<br />

www.siemens.com/energy-support<br />

The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.<br />

The required features should therefore be specified in each individual case at the time of closing the contract.<br />

Subject to change without prior notice<br />

Order no. E50001-U229-A262-X-7600<br />

Printed in Germany<br />

Dispo 40400<br />

GB 071139 101855 WS 1207