IECEx PTB 06.0029 U - R. Stahl
IECEx PTB 06.0029 U - R. Stahl
IECEx PTB 06.0029 U - R. Stahl
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>IECEx</strong> Certificate<br />
of Conformity<br />
INTERNATIONAL ELECTROTECHNICAL COMMISSION<br />
IEC Certification Scheme for Explosive Atmospheres<br />
for rules and details of the <strong>IECEx</strong> Scheme visit www.iecex.com<br />
Certificate No.: <strong>IECEx</strong> <strong>PTB</strong> <strong>06.0029</strong>U issue No.:1<br />
Status: Current<br />
Date of Issue: 2011-11-30 Page 1 of 4<br />
Applicant:<br />
Electrical Apparatus: Empty Enclosure type 8125/-***-***<br />
Optional accessory:<br />
Type of Protection: "e", "tb"<br />
Marking: Ex eb IIC or Ex e IIC Gb<br />
Ex tb IIIC IP66 or Ex tb IIIC Db IP66<br />
Approved for issue on behalf of the <strong>IECEx</strong><br />
Certification Body:<br />
Dr.-Ing. Uwe Klausmeyer<br />
Position: Head of Section "Flameproof Enclosure"<br />
Signature:<br />
(for printed version)<br />
Date:<br />
1. This certificate and schedule may only be reproduced in full.<br />
2. This certificate is not transferable and remains the property of the issuing body.<br />
3. The Status and authenticity of this certificate may be verified by visiting the Official <strong>IECEx</strong> Website.<br />
Certificate issued by:<br />
R. STAHL Schaltgeräte GmbH<br />
Am Bahnhof 30<br />
74638 Waldenburg (Württ.)<br />
Germany<br />
Physikalisch-Technische Bundesanstalt (<strong>PTB</strong>)<br />
Bundesallee 100<br />
38116 Braunschweig<br />
Germany<br />
Certificate history:<br />
Issue No. 1 (2011-11-<br />
30)<br />
Issue No. 0 (2006-4-5)
Certificate No.: <strong>IECEx</strong> <strong>PTB</strong> <strong>06.0029</strong>U<br />
<strong>IECEx</strong> Certificate<br />
of Conformity<br />
Date of Issue: 2011-11-30 Issue No.: 1<br />
Manufacturer:<br />
Manufacturing location(s):<br />
Page 2 of 4<br />
This certificate is issued as verification that a sample(s), representative of production, was assessed and tested and<br />
found to comply with the IEC Standard list below and that the manufacturer's quality system, relating to the Ex products<br />
covered by this certificate, was assessed and found to comply with the <strong>IECEx</strong> Quality system requirements. This<br />
certificate is granted subject to the conditions as set out in <strong>IECEx</strong> Scheme Rules, <strong>IECEx</strong> 02 and Operational Documents<br />
as amended.<br />
STANDARDS:<br />
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified<br />
documents, was found to comply with the following standards:<br />
IEC 60079-0 : 2011<br />
Edition: 6.0<br />
IEC 60079-31 : 2008<br />
Edition: 1<br />
IEC 60079-7 : 2006-07<br />
Edition: 4<br />
Explosive atmospheres - Part 0: General requirements<br />
Explosive atmospheres – Part 31: Equipment dust ignition protection by enclosure 't'<br />
Explosive atmospheres - Part 7: Equipment protection by increased safety "e"<br />
This Certificate does not indicate compliance with electrical safety and performance requirements other than those<br />
expressly included in the Standards listed above.<br />
TEST & ASSESSMENT REPORTS:<br />
A sample(s) of the equipment listed has successfully met the examination and test requirements as recorded in<br />
Test Report:<br />
DE/<strong>PTB</strong>/ExTR06.0034/01<br />
Quality Assessment Report:<br />
DE/BVS/QAR10.0002/01<br />
R. STAHL Schaltgeräte GmbH<br />
Am Bahnhof 30<br />
74638 Waldenburt (Württ.)<br />
Germany
Certificate No.: <strong>IECEx</strong> <strong>PTB</strong> <strong>06.0029</strong>U<br />
<strong>IECEx</strong> Certificate<br />
of Conformity<br />
Date of Issue: 2011-11-30 Issue No.: 1<br />
Schedule<br />
EQUIPMENT:<br />
Equipment and systems covered by this certificate are as follows:<br />
Page 3 of 4<br />
Description<br />
Empty enclosure, type 8125/-***-*** from sheet steel or stainless steel sheet for use in type of protection Increased<br />
Safety "e" and Protection by enclosure "tb" for stationary use, capability to assembly with different flange and enclosure<br />
sizes.<br />
Schedule of limitations<br />
The type of protection will be only safeguarded when due consideration is given to the instructions provided by the<br />
manufacturer. It also presupposes proper installation in the enclosure, the enclosure cover or in the control board.<br />
Installation of electrical components requires a further assessment by an ExCB.<br />
Technical data and Nomenclature see Annex.<br />
CONDITIONS OF CERTIFICATION: NO
Certificate No.: <strong>IECEx</strong> <strong>PTB</strong> <strong>06.0029</strong>U<br />
<strong>IECEx</strong> Certificate<br />
of Conformity<br />
Date of Issue: 2011-11-30 Issue No.: 1<br />
DETAILS OF CERTIFICATE CHANGES (for issues 1 and above):<br />
Annexe: Anhang zum IEC Ex Zertifikat.pdf<br />
Page 4 of 4<br />
Details of certificate changes<br />
1) New gasket<br />
2) The ambient temperature range is changed to -60 °C to +100 °C<br />
3) Changing of degree of protection to IP66<br />
4) New test according to IEC 60079-0:2011, IEC 60079-7:2006, IEC 60079-31:2008 and changing<br />
of the marking.