4.2 UL compliant installation<br />

<strong>System</strong> <strong>Manual</strong> – DOP11A <strong>Operator</strong> <strong>Terminal</strong>s<br />

Installation<br />

UL compliant installation<br />

Note the following points for UL compliant installation:<br />

Use only copper conductors with a temperature range of 60 / 75 °C as connection<br />

cables.<br />

4.3 Connection of basic unit DOP11A-10 to DOP11A-50<br />

Voltage supply<br />

Electrical connection according to the methods described in class 1, paragraph 2 (article<br />

501-4(b) according to National Electric Code NFPA70).<br />

Use only tested units with a limited output voltage (V max = DC 30 V) limited output<br />

current (I ≤ 8 A) as an external DC 24 V voltage source.<br />

UL certification does not apply to operation in voltage supply systems with a nonearthed<br />

star point (IT systems).<br />

Ensure correct polarity when connecting the terminal. Incorrect polarity will damage the<br />

unit.<br />

Make sure that the operator terminal and the controller system have the same electrical<br />

grounding (reference voltage value). Communication errors may occur if this is not the<br />

case.<br />