4P APJ/NPJ and DP Arktite Plugs with Cable Grip and Neoprene ...

quebec.nedco.ca

4P APJ/NPJ and DP Arktite Plugs with Cable Grip and Neoprene ...

4P APJ/NPJ and DP Arktite ®

Plugs with Cable Grip and

Neoprene Bushing

1026 Copyright © 2002 Cooper Industries, Inc.

Cl. I, Div. 1 and 2, Groups C,D

Cl. II, Div. 1 and 2, Groups F,G

Cl. III

NEMA/EFC 3,7CD,9FG,12

Explosionproof

APJ Plug

APJ/NPJ and DP Arktite Plugs

NPJ Plug DP Plug

600VAC/250VDC with Cable Grip and Neoprene Bushing – Style 2

Cable

2-wire, 3-pole 3-wire, 4-pole

Amps O.D. Range Cat. # Cat. #

0.60 to 1.20 APJ3385 APJ3485

30 0.55 to 0.70 NPJ3383 NPJ3483

0.70 to 0.85 NPJ3384 NPJ3484

0.75 to 1.45 APJ6385 APJ6485

60 0.75 to 1.07 NPJ6384 NPJ6484

1.07 to 1.35 NPJ6385 NPJ6485

1.00 to 1.70 APJ10387 APJ10487

100 0.93 to 1.21 NPJ10386 NPJ10486

1.21 to 1.50 NPJ10387 NPJ10487

200 1.875 to 2.50 DP20468 Solder Only DP Wire Size

Dimensions

APJ NPJ

Dust-Ignitionproof

Raintight

Wet Locations

Pressure connectors are supplied as standard. To

specify crimp/solder type terminations add the suffix ‘‘T’’ to

the catalog number. For example: APJ3385-T (Plug).

.56 Wire Well Building Extra Flex

#1 – 4/0 #1 – 3/0

Recept. Breaker a b c d e f g h hh j k l m

30 Amp. 20-50 Amp. 24 10 5 ⁄8 14 3 ⁄8 9 3 ⁄8 7 11 ⁄16 11 3 ⁄4 4 9 ⁄16 4 13 ⁄16 7 20 3 ⁄4 7 3 ⁄8 2 1 ⁄16

60 Amp. 50 Amp. 24 1 ⁄2 10 5 ⁄8 14 3 ⁄8 9 3 ⁄8 7 11 ⁄16 11 3 ⁄4 5 1 ⁄16 5 13 ⁄16 6 13 ⁄16 20 3 ⁄4 7 3 ⁄8 2 1 ⁄16

60 Amp. 70-100 Amp. 24 1 ⁄2 12 13 ⁄16 14 3 ⁄8 9 3 ⁄8 7 11 ⁄16 11 3 ⁄4 5 1 ⁄16 5 13 ⁄16 6 13 ⁄16 20 3 ⁄4 9 1 ⁄4 2 5 ⁄8

100 Amp. 70-100 Amp. 25 1 ⁄4 12 13 ⁄16 14 3 ⁄8 9 3 ⁄8 7 11 ⁄16 11 3 ⁄4 5 13 ⁄16 6 5 ⁄8 7 3 ⁄4 20 3 ⁄4 9 1 ⁄4 2 5 ⁄8

200 Amp. 125-225 Amp. 36 18 27 13 1 ⁄2 34 1 ⁄4 5 1 ⁄2

Dim. ‘‘h’’ and ‘‘hh’’ are exposed portion of plug when engaged with receptacle.


FSQC Arktite ® Dead Front

Interlocked Receptacles

and Switches

APJ/NPJ Arktite Plugs

Applications:

FSQC dead front switched interlock

receptacles are used:

to supply power to portable electrical

equipment such as hand lamps, lighting

systems, power tools, conveyors, welders

and similar equipment.

in areas which are hazardous due to the

presence of flammable vapors or gases and

combustible dusts.

in damp, wet or corrosive locations.

indoors or outdoors at petroleum refineries,

chemical and petrochemical plants and

facilities for processing and handling grain,

flour and starch.

Product Features:

Compatible with Arktite ® APJ aluminum and

NPJ Krydon ® plugs

Switch cannot be turned ‘‘ON’’ until plug is

fully inserted and rotated.

Plug cannot be withdrawn under load

Cover cannot be removed when switch is

‘‘ON’’

Satisfies OSHA lockout tagout requirement.

Smallest mounting footprint for interlocks

Ordering Information:

Cl. I, Div. 1 and 2, Groups B,C,D

Cl. II, Div. 1 and 2, Groups F,G

Cl. III

NEMA/EEMAC 3,7BCD,9FG,12

Materials:

Enclosure – Feraloy ® iron alloy or copperfree

aluminum

Cover and spring door – copper-free

aluminum

Insulator – Krydon ®

Contacts – brass

Certifications and

Compliances:

NEMA 3, 7BCD, 9FG, 12

NEC/CEC: Class I, Division 1 & 2, Groups

B, C & D

Class I, Zone 1, Group IIB+Hydrogen

Class II, Division 1 & 2, Groups F, G

Class III

ANSI/UL Standards 1010 UL Listed

CSA Standard C22.2 No. 30 cUL Listed &

C22.2 No. 159

Options:

Description Suffix

Special polarity, receptacle interior

rotated 22 1 ⁄2° S4

Copper-free aluminum enclosure –

60A only SA

Amps Hub Config. Description Catalog Number

30A

3 ⁄4

1

60A 1 1 ⁄2

2W3P 2 Pole Switch FSQC2320

3W4P 3 Pole Switch FSQC2430

2W3P 2 Pole Switch FSQC3320

3W4P 3 Pole Switch FSQC3430

2W3P 2 Pole Switch FSQC5630

3W4P 3 Pole Switch FSQC5640

FSQC for Use with Magnetic Motor Starters or Contactors

FSQC units listed below operate in the same way as standard units but are intended only for

use with magnetic motor starters or contactors. (Wiring diagram 1)

Receptacles have leads for splicing to conductors from the load side of contactor. The switch

actuated by the plug is wired into the starter or contactor coil circuit and controls only this

circuit. The starter or contactor is energized only when the plug is fully inserted and rotated to

close the switch. Since the plug is inserted or withdrawn only when the switch is open, the

circuit cannot be made or broken under the load.

Plugs used are standard APJ units and special polarity units listed are recommended where

interchange with devices for other wiring systems is possible.

FSQC

APJ/NPJ Plugs

Receptacles

With Spring Door

(Through Feed Hubs)

30 Amperes, 250 VAC or VDC; 20 Amperes, 600 VAC

No. of Hub Receptacle Cable Plug

Poles Size Cat. # Dia. Cat. #

3-wire

4-pole

3 ⁄4

3 ⁄4

1

1

FSQC2390

}

FSQC2390-S4

FSQC3390

FSQC3390-S4

0.60 to 1.20

0.55 to 0.70

0.70 to 0.85

APJ3485

{ APJ3485-S4

NPJ3483

{ NPJ3483-S4

NPJ3484

{ NPJ3484-S4

Copyright © 2002 Cooper Industries, Inc.

Explosionproof

Dust-Ignitionproof

Raintight

Wet Locations

FSQC

Receptacles

With Spring Door

(Through Feed Hubs)

Horsepower Rating:

4P

Single Phase

Amps 120V 240V 480V 600V

30A 2 5 71 ⁄2 71 ⁄2

60A — 10 25 30

Three Phase

Amps 120V 240V 480V 600V

30A 3 71 ⁄2 15 15

60A — 10 25 30

Wiring Diagram 1

(FSQC2390 and 3390 only)

1011


DBR Interlocked Arktite ®

Receptacles With Enclosed

Circuit Breakers

APJ/NPJ Arktite Plugs

Application:

DBR interlocked Arktite receptacles with

enclosed circuit breakers and APJ/NPJ

Arktite plugs are used:

to supply power to portable electrical

equipment such as motor-generator sets,

compressors, heating and cooling units,

conveyors, and similar equipment

in locations where hazardous dusts are

present, as in grain processing and handling

plants, chemical plants and certain food

processing industries

indoors or outdoors in damp, wet or

corrosive locations

Features:

Receptacles are mechanically interlocked

with circuit breakers to provide disconnect

means, short circuit protection and thermal

time delay overload protection.

Enclosures are compact and rectangular in

shape permitting close spacing.

For maximum safety, the spring door

receptacle at the bottom is mechanically

interlocked with the circuit breaker operating

mechanism. The circuit breaker cannot be

closed until the plug is fully inserted and the

plug cannot be withdrawn unless the breaker

is open.

Operating handles can be padlocked in

either ‘‘ON’’ or ‘‘OFF’’ positions. Breakers are

trip-free of the handles and will open under

short circuit or overload even if the handle is

locked in the ‘‘ON’’ position.

Enclosure is provided with a drilled and

tapped conduit opening at top center,

equipped with a threaded-in bushing. The

size furnished is 1 1 ⁄2, and removing the

bushing permits the use of a 2 conduit.

Interchangeability of Plugs

with Other Hazardous and

Non-Hazardous Location

Receptacles:

Plugs listed for use with DBR assemblies

are standard Arktite APJ/NPJ plugs. Other

standard APJ/NPJ and CPH plugs of the

same rating, style and number of poles may

be used with DBR receptacles, as well as with

DR receptacles listed in Section 2P and with

EBBR, EPC and EPCB receptacles listed in

Section 4P.

As a result, portable equipment suitable for

the locations and equipped with the proper

plug can be used with AR receptacles for

non-hazardous locations, with EBBR, EPC

and EPCB receptacles for Class I hazardous

locations, and with DR and DBR interlocked

receptacles for Class II hazardous locations.

Cl. II, Div. 1 and 2, Groups F,G

Cl. III

NEMA/EEMAC 3,9FG,12

Dust-Ignitionproof

Raintight

Standard Materials:

Bodies, covers and operating handles –

copper-free aluminum

Operating shafts – stainless steel

Receptacle housings and plug exteriors –

copper-free aluminum

Insulation: plugs and receptacles –

fiberglass-reinforced polyester

Pressure contacts – brass

Crimp/solder contacts – leaded red brass

Standard Finishes:

Copper-free aluminum – plug exterior,

enclosure and receptacle housing – natural

Stainless steel – natural

Brass – natural

Fiberglass-reinforced polyester – natural

(red)

Leaded red brass – electro-tin-plate

Options:

The following special options are available by

adding suffix to Cat. No.

Suffix to be

Added to

Description Cat. #

Special polarity – for use where two or more

receptacles of the same ampere rating, style

and number of poles are to be installed in the

same area for use on different voltages.

Available as follows:

Receptacle interior rotated 221 ⁄2

degrees clockwise when viewed

from receptacle face and plug

changed to match .....................S4

Breather (drain furnished as

standard) ...........................S219

Conduit arrangements other than

standard can be supplied . Details on request

Certifications and

Compliances:

NEC: Class II, Division 1 and 2, Groups F,G

Class III

NEMA/EEMAC: 3, 9FG, 12

UL Standard: 698, 1010

CEC: Class II, Division 1 and 2, Group G

Class III

Encl.: 3,5

Electrical Rating Ranges:

Receptacle ratings: 30, 60 and 100

amperes

Circuit breakers – 100 ampere frame size

Amps a b bb

30 213 ⁄4 61 ⁄2 7

60 223 ⁄4 81 ⁄2 613 ⁄16

100 231 ⁄2 101 ⁄8 73 ⁄4

Dim. ‘‘b’’ and ‘‘bb’’ are exposed portion of

plug when engaged with receptacle.

Copyright © 2002 Cooper Industries, Inc.

4P

CAUTION: To reduce the risk of ignition of

hazardous atmospheres, do not use plugs or

receptacles in Class II, Group F locations that

contain electrically conductive dusts.

Pressure connectors are standard. Crimp/solder type

terminators are optionally available for 3 and 4-pole, 30, 60

and 100 ampere. For details, see table on page 938. To

specify, add the suffix ‘‘T’’ to the catalog number. For

example: AP3375-T (Plug)

Dimensions:

APJ NPJ

1029


4P DBR Interlocked Arktite ®

Receptacles With Enclosed

Circuit Breakers

100 Ampere Frame Size with

Non-Interchangeable Thermal Trip and Non-Adjustable Magnetic Trip

Receptacle Circuit

Enclosure

Ckt. With Circuit

With Spring Breaker Hub Bkr. Without Circuit Breaker Cat. #

Door Housing† Rating Size Amps Breaker Cat. # Cutler-Hammer ‘‘FDB’’

30 amp., 3-pole 11 ⁄2 20 DBR53731 DBR53731-WT20-3

3-wire, 600VAC 30 DBR53731-WT30-3

3-pole, 40 DBR53731-WT40-3*

Style 1 50 DBR53731-WT50-3*

30 amp., 2-pole 11 ⁄2 20 DBR53732 DBR53732-WT20-2

2-wire, 600VAC 30 DBR53732-WT30-2

3-pole, or 40 DBR53732-WT40-2*

Style 2 250VDC 50 DBR53732-WT50-2*

30 amp., 3-pole 11 ⁄2 20 DBR53742 DBR53742-WT20-3

3-wire, 600VAC 30 DBR53742-WT30-3

4-pole, 40 DBR53742-WT40-3*

Style 2 50 DBR53742-WT50-3*

60 amp., 3-pole 11 ⁄2 50 DBR56731 DBR56731-WT50-3

3-wire, 600VAC 60 DBR56731-WT60-3

3-pole, 70 DBR56731-WT70-3*

Style 1 90 DBR56731-WT90-3*

100 DBR56731-WT100-3*

60 amp., 2-pole 11 ⁄2 50 DBR56732 DBR56732-WT50-2

2-wire, 600VAC 60 DBR56732-WT60-2

3-pole, or 70 DBR56732-WT70-2*

Style 2 250VDC 90 DBR56732-WT90-2*

100 DBR56732-WT100-2*

60 amp., 3-pole 11 ⁄2 50 DBR56742 DBR56742-WT50-3

3-wire, 600VAC 60 DBR56742-WT60-3

4-pole, 70 DBR56742-WT70-3*

Style 2 90 DBR56742-WT90-3*

100 DBR56742-WT100-3*

100 amp., 3-pole 11 ⁄2 60 DBR51731 DBR51731-WT60-3

3-wire, 600VAC 70 DBR51731-WT70-3

3-pole, 90 DBR51731-WT90-3

Style 1 100 DBR51731-WT100-3

100 amp., 2-pole 11 ⁄2 60 DBR51732 DBR51732-WT60-2

2-wire, 600VAC 70 DBR51732-WT70-2

3-pole, or 90 DBR51732-WT90-2

Style 2 250VDC 100 DBR51732-WT100-2

100 amp., 3-pole 11 ⁄2 60 DBR51742 DBR51742-WT60-3

3-wire, 600VAC 70 DBR51742-WT70-3

4-pole, 90 DBR51742-WT90-3

Style 2 100 DBR51742-WT100-3

APJ/NPJ Arktite Plugs

600VAC/250VDC with Cable Grip and

Neoprene Bushing

APJ Plug NPJ Plug

1030 Copyright © 2002 Cooper Industries, Inc.

Cl. II, Div. 1 and 2, Groups F,G

Cl. III

NEMA/EEMAC 3,9FG,12

Dust-Ignitionproof

Raintight

* Circuit breaker trip rating may exceed

receptacled rating for welding equipment

applications only, as higher trip rating may not

protect wiring.

Pressure connectors are standard.

Crimp/solder type terminators are optionally

available for 3 and 4-pole 30, 60 and 100 ampere.

For details, see table on page 938.

To specify, add the suffix ‘‘T’’ to the catalog

number. For example: APJ3375-T (Plug)

† Style 1 – Grounded through shell.

Style 2 – Grounded through extra pole and shell.

For a detailed description of these grounding

methods, see page 937.

‡ For circuit breaker Cat. No. refer to Section 6C,

Table 9, List FDB. For detailed information on

circuit breaker selection, see Section 6C.

Style 1† Style 2†

3-wire, 2-wire, 3-wire,

Cable 3-pole 3-pole 4-pole

Amps O.D. Range Cat. # Cat. # Cat. #

0.60 to 1.20 APJ3375 APJ3385 APJ3485

30 0.55 to 0.70 NPJ3383 NPJ3483

0.70 to 0.85 NPJ3384 NPJ3484

0.75 to 1.45 APJ6375 APJ6385 APJ6485

60 0.75 to 1.07 NPJ6384 NPJ6484

1.07 to 1.35 NPJ6385 NPJ6485

1.00 to 1.70 APJ10377 APJ10387 APJ10487

100 0.93 to 1.21 NPJ10386 NPJ10486

1.21 to 1.50 NPJ10387 NPJ10487