ELECTRICAL POWER<br />

Current Injectors<br />

Multi-Amp MS-2 High Current Test Set<br />

MUL,MS-2 (8415) AU<br />

Designed to test overload relays, circuit<br />

breakers and earth fault trip devices.<br />

Input 240V 50/60Hz. Output continuously<br />

adjustable in 4 ranges 120V/5A, 24V/25A,<br />

6V/120A & 3V/240A. Short term over<br />

current of several times the rated current ranges is possible. Digital current<br />

meter has read and hold facilities for short duration currents. Digital timer<br />

measures elapsed time between energisation and the test device operating.<br />

Programma Magnus 2.2kV Step Up<br />

Transformer for Testing CT’s<br />

PRO,MAGNUS-2.2kV (8464) AU<br />

Use in high-voltage substations and industrial<br />

environments. Protected with thermal<br />

cut-outs, mains voltage 230Vac ±10%, 50 to<br />

60Hz, power consumption is 2.3kVA. Used<br />

for preparing excitation curves for instrument<br />

transformers and for demagnetizing current transformer cones. Safety key<br />

lock (block unauthorised use).<br />

SMC PTE-100-C<br />

Secondary Current Test Set<br />

SMC,PTE-100-C (8414) AU<br />

AC current and voltage outputs in 4 ranges<br />

200V/5A, 40V/25A, 20V/50A & 10V/100A.<br />

Additional outputs AC voltage 0 to 220V at 1A<br />

(4A 1min), DC voltage 0 to 350V at 0.7A (2.8A<br />

1min), DC voltage 0 to 250V at 0.25A, fixed 110V AC at 0.3A. Timer 1ms<br />

to 99,999s. Additional functions include measurement of the phase angle<br />

between the voltage and the current output tap selected, and the measurement<br />

of the impedance of the load connected in the current output taps.<br />

T&R 200A-3PH/ED Current injection tester<br />

T&R,200A3PHEDIT (8464) AU<br />

0 to 200A/phase output capacity. <strong>Power</strong> supply 4 wire<br />

5A/phase 3ph 240/415V. Typically 10A 5 pin 3 phase<br />

socket outlet HPM.<br />

T&R CIT/LU2000 Primary Current Injection<br />

Test Set<br />

T&R,CIT (8481) AU<br />

Comprises control unit and 2kA loading unit<br />

(LU). Control unit includes timer, current and<br />

voltage meters, and variable output transformer.<br />

External loading unit output 0 to 2kA, duty 5min<br />

on 15min off at 6VAC, continuous 0 to 1kA at<br />

3VAC. Two units weight 35 & 45kg plus 2 quad<br />

70mm2 cable sets each 3m long. Control unit<br />

connects to LU with supplied interface cable.<br />

T&R PCU1-SP with CT Ratio/<br />

Polarity and NLU5000A Loading Unit<br />

T&R,PCU1-SP NLU5000A (8482) AU<br />

Medium powered primary current injection system.<br />

Features 5kA maximum output current (higher overload<br />

current for 2s). Multi-function digital timing system.<br />

Digital true RMS memory ammeter. Solid state switching.<br />

2,000A and 5,000A load units. Three range outputs on<br />

loading units. Rugged, compact design. Secondary injection up to 100A.<br />

Direct reading CT ratio and polarity. May be configured to either give a<br />

maximum current of 5,000A on the 2.3V range, 2,500A on the 4.6V range or<br />

1,250A on the 9.2V range.<br />

42<br />

www.techrentals.com.au<br />

Protection Relay Testing Systems<br />

Megger Protective Relay Test System<br />

IEC 61850<br />

MEG,MPRT8430-BAS-3CH (4607) AU<br />

Performs routine testing of protective relays.<br />

The standard configuration delivers three<br />

voltages and three currents, or six currents.<br />

Specifications: AC current output: 0 to 90A, AC voltage output: 0 to 600V,<br />

DC voltage output: 0 to 600V, frequency range: 0.001 to 9999.999Hz. The<br />

TouchView Interface Controller features a full color, touch screen interface.<br />

Includes AVTS software.<br />

<br />

OMI,CMA156-6PCA (4604) AU<br />

Six-phase current amplifier for tests requiring higher currents and/or higher<br />

power in the current path than is delivered by the CMC 156/256 or more than<br />

3/6 current channels (e.g., for testing three-winding transformer differential<br />

protection). Contains six independent current channels. Arranged in two<br />

isolated groups (A, B) and can be used independently of those of the CMC<br />

156/256. Connected to the CMC by means of a control cable. With a CMLIB<br />

F the available output power can be increased by a factor of 3 (210 VA at 7,5 A<br />

instead of 70 VA) for all single-phase fault loops.<br />

Omicron CMC256-6 Advanced Protection Relay Test Set<br />

OMI,CMC256-6 (4612) AU<br />

Advanced 3ph dynamic automatic protection relay test system.<br />

Current, integral 3ph current source max 140VA, 6 output sources,<br />

resolution 500μA, suitable for most relay types, including some high<br />

burden units. Voltage, 3ph 0 to 300RMS. Auxiliary DC supply, 0 to 264V, 0.2A.<br />

Relay monitoring trip, monitoring 6 isolated inputs, can be configured to be voltage<br />

free or 0 to 250V. Contact outputs 6 isolated change-over relay contacts<br />

(software controlled). Max 250VAC, 10A or 125VDC 1A. Interface connector,<br />

16 TTL digital inputs and outputs. Scope analogue inputs, 2 isolated analogue<br />

inputs ±500V peak max 12 bit resolution. Input supply 90 to 260VDC, 400Hz.<br />

Intuitive on-line help. Laptop and Test-Universe software up to TU V 2.01 supplied<br />

with test set, interface parallel port.<br />

Omicron CMGPS Syncronisation Control Unit<br />

OMI,CMGPS (4616) AU<br />

Accessory for the Omicron CMC etc. A single GPS unit, if used to sych relay<br />

tests when performing end-to-end tests of line protection systems two are<br />

required. The unit provides a start signal pulse based on the GPS clock time<br />

base. Software is both integrated in the testing modules (State Sequencer)<br />

and can also be used as a stand-alone application.<br />

Omicron C-Probe-1 Clamp-on CT AC/DC<br />

OMI,C-PROBE1 (4614) AU<br />

An active AC & DC current probe with voltage output. Recommended<br />

accessory for measuring currents with the CMC 256. Two measuring ranges:<br />

10A & 80A. Frequency range DC 10kHz. Accuracy error < 2% for currents up<br />

to 40A and frequencies up to 1kHz. Phase error < 0.5O @ 50/60Hz. Length<br />

230mm. Output: 0-10A range 100mV/A, 0-80A range 10mV/A.<br />

Programma EGIL Circuit Breaker Analyser<br />

<br />

One main contact per phase. Three time channels are<br />

connected together on one side. Events at parallel<br />

contacts equipped with pre-insertion resistors<br />

are recorded and displayed simultaneously.<br />

Two separate time channels for measurement of auxiliary contacts. On-site<br />

hookup comes with ready-made multi-cable sets for both main and auxiliary<br />

contacts. Coil currents are measured automatically, presented together with<br />

other readings immediately after testing on the display window or via the builtin<br />

printer. A built-in sequencer (program unit) sets the instrument automatically<br />

for the next sequential breaker operation. Intended primarily for measuring<br />

travel (motion). Can be equipped with an optional serial interface (RS232C) for<br />

communication with a PC and the CABA Win Breaker Analysis Software.