Globe Valves
Globe Valves
Globe Valves
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
GCO 2431
Irrigation
• Click here to return to
Wildmon’s homepage
Remote Control Valves
The theory of valve operation is the same
regardless of the manufacturer
• Forward Flow
• Reverse Flow
Two Different Styles of Valves
Identifying A Forward Flow Valve
• When looking into the inlet side, you will see the center
of the diaphragm
Identifying A Reverse Flow Valve
• When looking into the inlet side, you will find a wall of
brass or plastic, the diaphragm is not visible
Major Components
Internal Components
Valve Operation
• Forward flow in the closed position
Why does the valve stay off?
• There is greater force above the diaphragm than below
the diaphragm
• Why is pressure not the correct answer?
Force = Pressure x Surface Area
• The pressure above the diaphragm is the same as
below the diaphragm
• The surface area above the diaphragm is
approximately 1½ times greater than the surface area
below the diaphragm, therefore, there is 1½ times
greater force above the diaphragm keeping the valve
closed
Purpose Of The Spring
• It pushes down on the diaphragm so that it wants to
close.
Opening the Valve
• Release the pressure in the upper chamber
– This reduces the force above the diaphragm
• This can be done automatically or manually
Opening the Valve Automatically
• The controller sends 24 VAC to the solenoid
• The solenoid coil develops a magnetic field which lifts
the plunger
• The upper chamber water exits through the exhaust
port
• The force below the diaphragm is now greater
Opening The Valve Automatically
• Water Escapes From The Upper Chamber
Forward Flow Valve Open
Closing The Valve
• The controller stops sending 24 VAC
• The plunger covers the exhaust port
• Water is trapped in the upper chamber
• The force increases above the diaphragm
Force Increases In The Upper Chamber
Forward Flow Valve Closed
Opening the Valve Manually
• Internal manual bleed
– Turn the solenoid counter-clockwise ¼ turn
– The upper chamber water exits through the exhaust port
– The force below the diaphragm is now greater
– The valve opens
Internal Manual Bleed Operation
Reverse Flow Valve
• How does the water enter the upper chamber?
– External tube
– Internal port
– Directly through the diaphragm
Reverse Flow Valve
• Directly through the diaphragm
– DV series
DV Series Valve
• Internal port
– GB series
Reverse Flow Valve
GB Series Valve
• External tube
– EFB-CP series
Reverse Flow Valve
EFB-CP Series Valve
Closing Speed
• The closing speed is controlled by using a fluid resistor
to regulate how fast water enters the upper chamber
• The solenoid port and exhaust port allow water to
escape faster than it can be replenished into the upper
chamber
Opening the Valve Automatically
• The controller sends 24 VAC to the solenoid
• The solenoid coil develops a magnetic field which lifts
the plunger
• The upper chamber water exits through the exhaust
port
• The force below the diaphragm is now greater
Opening the Valve Automatically
• Water Escapes From The Upper Chamber
Reverse Flow Valve Open
Closing The Valve
• The controller stops sending 24 VAC
• The plunger covers the exhaust port
• Water is trapped in the upper chamber
• The force increases above the diaphragm
Force Increases In The Upper Chamber
The Valve Closes
Opening the Valve Manually
• Internal manual bleed
– Turn the solenoid counter-clockwise ¼ turn
– The upper chamber water exits through the exhaust port
– The force below the diaphragm is now greater
– The valve opens
Internal Manual Bleed Operation
Opening the Valve Manually
• External manual bleed
– Turn the bleed screw counter-clockwise
– The upper chamber water “vents to atmosphere”
» Water escapes faster through the external bleed
– The force below the diaphragm is now greater
– The valve opens
External Manual Bleed Operation
• Check for the obvious
– Is the water turned on?
Troubleshooting
» Manually bleed several valves
– Is the valve receiving 24 VAC?
» Feel the solenoid for heat or vibration
• Defective controller or programming problem
• Valve not closing
– Seeping
• Valve not opening
Troubleshooting
Valve Is Not Closing
• Solenoid plunger stuck in the up position
– Dirt and debris
– Corrosion
Plunger Stuck In The Up Position
• Diaphragm filter plugged
Valve Is Not Closing
– No water can enter the upper chamber
Diaphragm Filter Plugged
Valve Is Not Closing
• Receiving voltage from the controller
– Defective controller
– Incorrect programming
Constant Voltage To The Solenoid
Valve Is Not Closing
• Debris under the diaphragm assembly
– Rocks and other debris
Debris Under The Diaphragm
Valve Is Not Closing
• Large hole in the diaphragm - Forward Flow
– Sufficient force cannot develop in the upper chamber
Large Hole In A Diaphragm - FF Valve
Valve Is Not Closing
• DV valve installed backwards
• The valve operates backwards
– When 24 VAC is applied, the valve closes
• Diaphragm seat damaged
Valve Is Seeping
Diaphragm Seat Damaged
• Solenoid seat damaged
Valve Is Seeping
Solenoid Seat Damaged
Valve Is Seeping
• Small hole in the diaphragm - Forward Flow
Small Hole In The Diaphragm - FF Valve
Valve Is Not Opening
• Valve is installed backwards
– All valve have arrows on them which indicates the
direction of water flow
Valve Is Not Opening
• Flow control tightened too far
– Water will pass through the exhaust port only
Flow Control Stem Too Tight
• Solenoid defective
Valve Is Not Opening
– Check the resistance of the field wires and the coil with a
multimeter
» The solenoid should be between 20 and 60 ohms
Valve Is Not Opening
• Solenoid plunger stuck in the down position
– Dirt and debris
– Corrosion
– Plunger spring installed incorrectly
Plunger Stuck In The Down Position
• Plugged solenoid port
– Small rocks or sand
Valve Is Not Opening
Plugged Solenoid Port
• Plugged exhaust port
– Small rocks or sand
Valve Is Not Opening
Plugged Exhaust Port
Valve Is Not Opening
• Large hole in the diaphragm - Reverse Flow
– Water will pass through the exhaust port only
Large Hole In The Diaphragm - RF Valve
Valve Is Not Opening Fully
• Small hole in the diaphragm - Reverse Flow
Vave Not Opening Fully - RF Valve