Page 4 of 46 of <strong>ETA</strong> <strong>12</strong>/0581, issued on 17.01.2013<br />
The environmental use categories are specified in <strong>ETA</strong>G 018 Part 2, section 2.2.2:<br />
• Type X: external use<br />
• Type Y: internal use and semi-exposed conditions<br />
• Type Z 1 : internal use with high humidity conditions<br />
• Type Z 2 :internal use<br />
1.3 Assumed working life<br />
The provisions made in this <strong>European</strong> <strong>Technical</strong> <strong>Approval</strong> (<strong>ETA</strong>) are based on an assumed<br />
working life of the reactive coatings for fire protection HEMPACORE ONE 43600 and<br />
HEMPACORE ONE FD 43601 of at least 10 years, provided that the conditions laid down in<br />
sections 4.2, 5.1 and 5.2 for the packaging, transport, storage and installation as well as<br />
appropriate use, maintenance and repair are met.<br />
The indications given on the working life cannot be interpreted as a guarantee given by the<br />
manufacturer or the <strong>Approval</strong> Body, but should only be regarded as a means for choosing the<br />
appropriate products in relation to the expected economically reasonable working life of the<br />
works.<br />
2 Characteristics of products and methods of verification<br />
The assessment of the fitness of HEMPACORE ONE 43600 and HEMPACORE ONE FD 43601<br />
for the intended use considering the essential requirements was performed following the<br />
Guideline for <strong>European</strong> <strong>Technical</strong> <strong>Approval</strong> 018 for Fire Protective Products Part 1: General and<br />
Part 2: Reactive coatings for fire protection of steel elements.<br />
2.1 Mechanical resistance and stability (ER 1)<br />
Not relevant.<br />
2.2 Safety in case of fire (ER 2)<br />
2.2.1 Reaction to fire<br />
The reactive coating systems including all the primers and topcoats listed in Table 1 have a<br />
performance determined for a reaction to fire Class D-s2,d0 according to EN 13501-1 7 .<br />
2.2.2 Fire resistance<br />
The product has been tested according to EN 13381-8 8 . Fire resistance classes have been<br />
defined according to EN 13501-2 and are presented in Annex 1.<br />
2.2.3 Smouldering fire exposure<br />
The verification under exposure to the smouldering fire curve according to EN 13381-8, Annex<br />
A, has been carried out and the product meets the requirements established in EN 13381-8.<br />
2.3 Hygiene, health and the environment (ER 3)<br />
2.3.1 Release of dangerous substances<br />
According to the manufacturer’s declaration, the product specification has been compared with<br />
the regulated dangerous substances listed on the database established on the EC construction<br />
website, with Annex XVII and Annex XIV of REACH and with the ECHA Candidate List of<br />
Substances of Very High Concern to verify that they do not contain such substances above the<br />
acceptable limits.<br />
In addition to the specific clauses relating to dangerous substances contained in this <strong>European</strong><br />
<strong>Technical</strong> <strong>Approval</strong>, there may be other requirements applicable to the products falling within its<br />
7 EN 13501-1:2007 Fire classification of construction products and building elements. Part 1: Classification using data from<br />
reaction to fire tests implemented.<br />
8 EN 13381-8:2010 Test methods for determining the contribution to the fire resistance of structural members. Part 8: Applied<br />
reactive protection to steel members.