C OPPER<br />

E V APORATORS<br />

Engineering Data<br />

3<br />

46-1/8<br />

40-1/8<br />

34-1/8<br />

3<br />

232-5/8<br />

3 6-1/8 42 125<br />

42 17-1/2<br />

47-7/8<br />

48-7/8<br />

<strong>SCT</strong>W WORKROOM UNITS — 5 FAN MODELS<br />

Electric<br />

R22 Capacity* (Btuh/TD) Coil Data Shipping Defrost (KW)<br />

Liq. Rec. DX Airflow Velocity Fan Data Rows Volume Wt. Room Temp.<br />

Model No. Wet Frosted Wet Frosted (CFM) (FPM) Motor Hp RPM Dia. dBA† Deep fpi (ft3) (lb.) > + 33°F<br />

<strong>SCT</strong>W5-01645-3 18092 16447 15016 13651 27213 583 1/2 870 30 78 6 3 3.4 2102 30.5<br />

<strong>SCT</strong>W5-01890-3 - 18899 - 15686 32964 706 1 870 30 80 6 3 3.4 2096 30.5<br />

<strong>SCT</strong>W5-01956-3 21222 19559 17614 16234 25774 552 1/2 870 30 78 8 3 4.5 2301 36.6<br />

<strong>SCT</strong>W5-01959-4 21552 19593 17888 16262 26575 570 1/2 870 30 78 6 4 3.4 2198 30.5<br />

<strong>SCT</strong>W5-02211-3 - 22108 - 18350 30671 657 1 870 30 80 8 3 4.5 2294 36.6<br />

<strong>SCT</strong>W5-02237-4 - 22373 - 18569 31957 685 1 870 30 80 6 4 3.4 2192 30.5<br />

<strong>SCT</strong>W5-02255-4 24463 22546 20304 18713 24774 531 1/2 870 30 78 8 4 4.5 2429 36.6<br />

<strong>SCT</strong>W5-02547-4 27636 25471 22938 21141 29018 622 3/4 870 30 79 8 4 4.5 2422 36.6<br />

<strong>SCT</strong>W5-02579-4 - 25790 - 21405 29561 633 1 870 30 80 8 4 4.5 2422 36.6<br />

* Capacity based on R22 refrigerant at +20°F coil temperature at 0” ESP.<br />

† Sound ratings are based on 6 feet from the unit and under free field conditions.<br />