RGO Refrigeration Dryers - Ingersoll Rand

ingersollrand.pl

RGO Refrigeration Dryers - Ingersoll Rand

RGO Refrigeration Dryers


When it comes to large capacity

Compressed Air systems, no-one

can out perform the experience of

INGERSOLL RAND.

For over 100 years, all over the

World, our products have been

setting the pace for performance,

reliability and innovative design.

Building from strength we have

confirmed that a successful air

compressor system frequently

demands not only durable

compressors like CENTAC but

also high quality, robust and

efficient Compressed Air Dryers.

Technical Specifications

A simple design concept.

The compressed air is pre-cooled

as it enters the dryer by thermally

mixing it with the cooler outgoing

air. It is then cooled further as

refrigerant is directly expanded

with the compressed air in the

evaporator until the desired dew

point is reached.

Condensed water vapour is then

separated from the air stream and

removed from the system

automatically.

Finally the cool, DRY air is

reheated by thermally mixing it

with the incoming warm, moist air,

raising its temperature so avoiding

external pipe sweating.

C

A Wealth of Design Features.

• Pre-cooler, Re-heater – reduces the load on

the refrigeration system. Reheats the air so

avoiding external pipe sweating.

• Flooded Evaporator Design – ensures highly

efficient heat transfer and the capability to

produce a near constant dew point under

varying load conditions.

• Integral Water Separator – removes the

condensed water efficiently and reliably.

• Water Cooled condensers – built into the

package and uses high efficiency extended

surfaces for compact design.

• Semi Hermetic Refrigeration Compressor –

with integral protective devices.

• Automatic Hot Gas Bypass Valve – providing

a near constant dew point at all load

conditions.

• Sophisticated Control – Microprocessor

controlled as standard with continuous dew

point display. A status report listing the 8

most recent occurrences, whilst a second

report memorises all sensor readings at alarm

intervention, for easy fault diagnosis.

A

B

Model

Nominal Air Flow

m 3 /min

cfm

Air

Connections

PN/DIN

Water

Connections

inch

Dimensions (mm)

A B C

Weight

kg

RGO 8 61 2.154 10/150 1 2906 1162 1750 1250

RGO 11 90 3.178 10/150 1 2916 1192 1770 1400

RGO 14 116 4.096 10/150 1 2939 1205 1770 1500

RGO 17 137 4.838 10/200 1 4252 1385 1850 2100

RGO 21 176 6.215 10/200 1 4316 1415 1865 2290

RGO 26 200 7.063 10/200 1 4316 1470 1910 2400

RGO 32 248 8.758 10/200 1 1/2 4343 1622 1920 2650

RGO 38 297 10.488 10/300 1 1/2 5426 1720 1920 3500

RGO 46 363 12.819 10/300 1 1/2 5476 1875 2000 4500

RGO 55 440 15.538 10/300 2 1/2 5566 2037 2000 5000

Performances refer to air suction of FAD 20ºC, 1 bar and the following operating conditions:

Air suction 25ºC / 60% RH, 7 barg working pressure, 3ºC pressure dew point, 25ºC condenser water temperature, 40ºC condensing temperature,

35ºC compressed air inlet temperature.

All indicated data refers to DIN ISO 7183. All models supplied with refrigerant R404a and for operation up to 10 barg. 50 Hz models supplied for

400/3/50 power supply. 60 HZ models also available. IP rating IP54

For other operating conditions please revert back to Ingersoll Rand.

99932527

Printed in UK

© 10/2003 by Ingersoll-Rand

Air Solutions

Heavy Industrial Systems

Strada Provinciale Cassanese, 108

I-20060 Vignate, Milano

Italy