31.03.2014 Views

Model: PEFY-P96NMHSU-E - Mitsubishi Electric Sales Canada Inc.

Model: PEFY-P96NMHSU-E - Mitsubishi Electric Sales Canada Inc.

Model: PEFY-P96NMHSU-E - Mitsubishi Electric Sales Canada Inc.

SHOW MORE
SHOW LESS

Transform your PDFs into Flipbooks and boost your revenue!

Leverage SEO-optimized Flipbooks, powerful backlinks, and multimedia content to professionally showcase your products and significantly increase your reach.

<strong>Model</strong>: <strong>PEFY</strong>-<strong>P96NMHSU</strong>-E<br />

Job Name:<br />

Location:<br />

Drawing Reference:<br />

Schedule No.<br />

System No.:<br />

Date:<br />

Net Weight<br />

Unit………………..…...……………............ 221 lbs. / 100 kg<br />

Coil Type………………...........................................….Cross Fin<br />

(Aluminum Fin and Copper Tube)<br />

GENERAL FEATURES<br />

R410A refrigerant<br />

Ten sizes from 15,000 to 96,000 Btu/h<br />

Ducted fan coil supporting multiple configurations for<br />

flexible installation<br />

Optional condensate lift; lifts to 21-21/32" (550mm)<br />

Quiet operation from 25 to 46 dB(A)<br />

Fan<br />

Type x Quantity………………..…………......…..Sirocco Fan x 2<br />

Airow Rate (Low-Mid-High)..……… ................. 2.048 - 2.507 - 2.966 CFM<br />

External Static Press.<br />

(208V) *** - - 0.602 - - in.WG<br />

(230V) *** - - 0.602 - - in.WG<br />

Motor<br />

Type………..………..………................................. DC motor.<br />

Output………..………..………..………..………..….0.870 kW<br />

Air Filter..…………………………….............................Optional<br />

Refrigerant Piping Dimensions<br />

Liquid (High Pressure)……............... 3/8" / 9.52 mm (Brazed)<br />

Gas (Low Pressure)……………….... 7/8" / 22.22 mm (Brazed)<br />

Drainpipe Dimension……............……...…O.D. 1-1/4" / 32 mm<br />

SPECIFICATIONS<br />

Capacity*<br />

Cooling…………………………………………….…96,000 Btu/h<br />

Heating…………………………………………….. 108,000 Btu/h<br />

Power<br />

Power Source………………..........208 / 230V, 1-phase, 60Hz<br />

Power Consumption**<br />

Cooling………………………………………................... 0.82 kW<br />

Heating…………………………………………............... 0.82 kW<br />

Current<br />

Cooling……...................................................….... 4.89 / 4.43 A<br />

Heating……........................................................... 4.89 / 4.43 A<br />

Minimum Circuit Ampacity (MCA)……………….….............. 8.2 A<br />

Maximum Overcurrent Protection (MOCP) Fuse..….......…..15 A<br />

External Finish……………...….…….….Galvanized-steel Sheet<br />

Sound Pressure Levels<br />

Low-Mid-High…(208V).…………….…....... 39 - 42 - 46 dB(A)<br />

Low-Mid-High…(230V).…………….…........ 39 - 42 - 46 dB(A)<br />

OPTIONS<br />

External Heat Adaptor……………………….…PAC-YU25HT<br />

Drain Pump………………...................……….…PAC-KE05DM-F<br />

Filter Box……………………….......................…PAC-KE250TB-F<br />

Long-life Filter……………………...................…PAC-KE85LAF<br />

* Cooling / Heating capacity indicated at the maximum value at<br />

operation under the following conditions:<br />

Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F<br />

(35°C) DB<br />

Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C)<br />

WB<br />

Note: Ventilation air: Providing suf cient ventilation air is an important<br />

part of every building design. ASHRAE Standard 62 provides<br />

the minimum ventilation air requirement. Also, check local codes.<br />

** The values are measured at the rated external static pressure.<br />

*** The rated external static pressure is shown without < >. The factory setting is the rated setting.<br />

External Dimensions<br />

I nches…………………………. ........ . 18-9/16<br />

x 49-1/4 x 44-1/8<br />

mm…………………………………… 470 H x 1250<br />

W x 1,120 D<br />

Notes:


<strong>Model</strong>: <strong>PEFY</strong>-<strong>P96NMHSU</strong>-E – DIMENSIONS<br />

2X11-ø3(1/8) holes<br />

2X11-ø3(1/8) holes Unit:mm(in.) Required space for service and maintenance.<br />

(5-15/16~7-7/8)<br />

(21-11/16)<br />

(17-3/4)<br />

(7-7/8~11-13/16) (17-3/4)<br />

420(16-9/16)<br />

(DUCT)<br />

Air inlet Air outlet<br />

10<br />

(7/16)<br />

24(1)<br />

10<br />

(7/16)<br />

1034(40-3/4)(Suspension bolt pitch)<br />

1124(44-5/16)<br />

1120(44-1/8)<br />

1067(42-1/16)<br />

Gas pipe 489(19-5/16)<br />

Liquid pipe 95(3-4/3) 249<br />

Drain hole<br />

(9-13/16)<br />

(Option)<br />

80 342(13-1/2)<br />

(3-3/16)<br />

Knockout hole ø22.2(7/8)<br />

Drain hole<br />

(Power souse wiring) (Normal type)<br />

Knockout hole ø22.2(7/8) Terminal block MODEL<br />

(Transmission wiring) (MA remocon) <strong>PEFY</strong>-P72NMHSU-E<br />

<strong>PEFY</strong>-<strong>P96NMHSU</strong>-E<br />

15<br />

(5/8)<br />

60<br />

(2-3/8)<br />

(DUCT)<br />

340(13-7/16)<br />

4-14X30(9/16x3/16) Slot<br />

Suspension bolt hole<br />

Drain Piping.<br />

60<br />

(2-3/8)<br />

(3-15/16x3=11-13/16)<br />

100x3=300<br />

100(3-15/16)<br />

(1-3/4)<br />

44<br />

(3-15/16x3=11-13/16)<br />

470(18-9/16)<br />

(3-15/16)<br />

100<br />

100<br />

(3-15/16)<br />

(15/16)<br />

23<br />

100<br />

(3-15/16)<br />

20(13/16)<br />

Control box<br />

2X4-ø3(1/8) holes<br />

Terminal block<br />

(Transmission)<br />

Terminal block<br />

(Power source)<br />

2X4-ø3(1/8) holes<br />

Unit:mm(in.)<br />

Gas pipe Liquid pipe Drain hose<br />

ø19.05(3/4)<br />

Drain hose 32mm<br />

ø9.52(3/8)<br />

(1-1/4inch)<br />

<br />

ø22.2(7/8)<br />

<br />

Access door<br />

Note3<br />

800(31-1/2)<br />

150~200<br />

550 50(2)<br />

Access door Ceiling surface<br />

170(6-3/4±1/4)<br />

(Actual length)<br />

Make the access door<br />

at the appointed position properly<br />

for service maintenance.<br />

Note2<br />

50(2)<br />

200~300<br />

450<br />

50(2)<br />

730(28-3/4)<br />

450<br />

1350(53-3/16)<br />

102(4-1/16)<br />

50(2)<br />

1100(43-5/16)(DUCT)<br />

1250(49-1/4)<br />

100x10=1000(3-15/16x10=39-3/8)<br />

100(3-15/16)<br />

1326(52-1/4)(Suspension bolt pitch)<br />

1372(54-1/16)<br />

1100(43-5/16)(DUCT)<br />

29(1-3/16)<br />

15(5/8)<br />

105(4-3/16)<br />

Note 1.Use M10 screw for the suspension bolt (field supply).<br />

2.Keep the service space for the maintenance from the bottom<br />

when the heat exchanger is cleaned.<br />

3.Keep the service space for the maintenance from the bottom<br />

when the fan motor is changed.<br />

4.Make sure to install the air filter (field supply) on the air intake side.<br />

In case field supplied air filter is used, attach it<br />

where the filter service is easily done.<br />

30(1-3/16)<br />

41(1-5/8)<br />

164(6-1/2)<br />

327(12-7/8)<br />

100(3-15/16)<br />

20(13/16)<br />

100X3(=300)<br />

50(2)<br />

More than 20(13/16) More than 20(13/16)<br />

100(3-15/16)<br />

100x10=1000(3-15/16x10=39-3/8)<br />

Drain hose<br />

<strong>Mitsubishi</strong> <strong>Electric</strong> Air Conditioning & Refrigeration Systems Wo rks acquired ISO<br />

based on a review of quality warranties for the production of refrigeration and air<br />

conditioning equipment.<br />

ISO Authorization System<br />

The ISO 9000 series is a plant authorization system relating to quality warranties as<br />

development, production, installation and auxiliary services" for products built at<br />

an authorized plant.<br />

<strong>Mitsubishi</strong> <strong>Electric</strong> <strong>Sales</strong> <strong>Canada</strong> <strong>Inc</strong>.<br />

www.<strong>Mitsubishi</strong><strong>Electric</strong>.ca<br />

<strong>Mitsubishi</strong> <strong>Electric</strong> Air Conditioning & Refrigeration Systems Works acquired environmental<br />

The ISO 14000 series is a set of standards applying to environmental protection set by the<br />

International Standard Organization (ISO).<br />

Specifications are subject to change without notice.<br />

SB_<strong>PEFY</strong>-<strong>P96NMHSU</strong>-E_201112

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!