Model: PEFY-P96NMHSU-E - Mitsubishi Electric Sales Canada Inc.
Model: PEFY-P96NMHSU-E - Mitsubishi Electric Sales Canada Inc.
Model: PEFY-P96NMHSU-E - Mitsubishi Electric Sales Canada Inc.
Transform your PDFs into Flipbooks and boost your revenue!
Leverage SEO-optimized Flipbooks, powerful backlinks, and multimedia content to professionally showcase your products and significantly increase your reach.
<strong>Model</strong>: <strong>PEFY</strong>-<strong>P96NMHSU</strong>-E<br />
Job Name:<br />
Location:<br />
Drawing Reference:<br />
Schedule No.<br />
System No.:<br />
Date:<br />
Net Weight<br />
Unit………………..…...……………............ 221 lbs. / 100 kg<br />
Coil Type………………...........................................….Cross Fin<br />
(Aluminum Fin and Copper Tube)<br />
GENERAL FEATURES<br />
R410A refrigerant<br />
Ten sizes from 15,000 to 96,000 Btu/h<br />
Ducted fan coil supporting multiple configurations for<br />
flexible installation<br />
Optional condensate lift; lifts to 21-21/32" (550mm)<br />
Quiet operation from 25 to 46 dB(A)<br />
Fan<br />
Type x Quantity………………..…………......…..Sirocco Fan x 2<br />
Airow Rate (Low-Mid-High)..……… ................. 2.048 - 2.507 - 2.966 CFM<br />
External Static Press.<br />
(208V) *** - - 0.602 - - in.WG<br />
(230V) *** - - 0.602 - - in.WG<br />
Motor<br />
Type………..………..………................................. DC motor.<br />
Output………..………..………..………..………..….0.870 kW<br />
Air Filter..…………………………….............................Optional<br />
Refrigerant Piping Dimensions<br />
Liquid (High Pressure)……............... 3/8" / 9.52 mm (Brazed)<br />
Gas (Low Pressure)……………….... 7/8" / 22.22 mm (Brazed)<br />
Drainpipe Dimension……............……...…O.D. 1-1/4" / 32 mm<br />
SPECIFICATIONS<br />
Capacity*<br />
Cooling…………………………………………….…96,000 Btu/h<br />
Heating…………………………………………….. 108,000 Btu/h<br />
Power<br />
Power Source………………..........208 / 230V, 1-phase, 60Hz<br />
Power Consumption**<br />
Cooling………………………………………................... 0.82 kW<br />
Heating…………………………………………............... 0.82 kW<br />
Current<br />
Cooling……...................................................….... 4.89 / 4.43 A<br />
Heating……........................................................... 4.89 / 4.43 A<br />
Minimum Circuit Ampacity (MCA)……………….….............. 8.2 A<br />
Maximum Overcurrent Protection (MOCP) Fuse..….......…..15 A<br />
External Finish……………...….…….….Galvanized-steel Sheet<br />
Sound Pressure Levels<br />
Low-Mid-High…(208V).…………….…....... 39 - 42 - 46 dB(A)<br />
Low-Mid-High…(230V).…………….…........ 39 - 42 - 46 dB(A)<br />
OPTIONS<br />
External Heat Adaptor……………………….…PAC-YU25HT<br />
Drain Pump………………...................……….…PAC-KE05DM-F<br />
Filter Box……………………….......................…PAC-KE250TB-F<br />
Long-life Filter……………………...................…PAC-KE85LAF<br />
* Cooling / Heating capacity indicated at the maximum value at<br />
operation under the following conditions:<br />
Cooling: Indoor 80°F (27°C) DB / 67°F (19°C) WB, Outdoor 95°F<br />
(35°C) DB<br />
Heating: Indoor 70°F (21°C) DB, Outdoor 47°F (8°C) DB / 43°F (6°C)<br />
WB<br />
Note: Ventilation air: Providing suf cient ventilation air is an important<br />
part of every building design. ASHRAE Standard 62 provides<br />
the minimum ventilation air requirement. Also, check local codes.<br />
** The values are measured at the rated external static pressure.<br />
*** The rated external static pressure is shown without < >. The factory setting is the rated setting.<br />
External Dimensions<br />
I nches…………………………. ........ . 18-9/16<br />
x 49-1/4 x 44-1/8<br />
mm…………………………………… 470 H x 1250<br />
W x 1,120 D<br />
Notes:
<strong>Model</strong>: <strong>PEFY</strong>-<strong>P96NMHSU</strong>-E – DIMENSIONS<br />
2X11-ø3(1/8) holes<br />
2X11-ø3(1/8) holes Unit:mm(in.) Required space for service and maintenance.<br />
(5-15/16~7-7/8)<br />
(21-11/16)<br />
(17-3/4)<br />
(7-7/8~11-13/16) (17-3/4)<br />
420(16-9/16)<br />
(DUCT)<br />
Air inlet Air outlet<br />
10<br />
(7/16)<br />
24(1)<br />
10<br />
(7/16)<br />
1034(40-3/4)(Suspension bolt pitch)<br />
1124(44-5/16)<br />
1120(44-1/8)<br />
1067(42-1/16)<br />
Gas pipe 489(19-5/16)<br />
Liquid pipe 95(3-4/3) 249<br />
Drain hole<br />
(9-13/16)<br />
(Option)<br />
80 342(13-1/2)<br />
(3-3/16)<br />
Knockout hole ø22.2(7/8)<br />
Drain hole<br />
(Power souse wiring) (Normal type)<br />
Knockout hole ø22.2(7/8) Terminal block MODEL<br />
(Transmission wiring) (MA remocon) <strong>PEFY</strong>-P72NMHSU-E<br />
<strong>PEFY</strong>-<strong>P96NMHSU</strong>-E<br />
15<br />
(5/8)<br />
60<br />
(2-3/8)<br />
(DUCT)<br />
340(13-7/16)<br />
4-14X30(9/16x3/16) Slot<br />
Suspension bolt hole<br />
Drain Piping.<br />
60<br />
(2-3/8)<br />
(3-15/16x3=11-13/16)<br />
100x3=300<br />
100(3-15/16)<br />
(1-3/4)<br />
44<br />
(3-15/16x3=11-13/16)<br />
470(18-9/16)<br />
(3-15/16)<br />
100<br />
100<br />
(3-15/16)<br />
(15/16)<br />
23<br />
100<br />
(3-15/16)<br />
20(13/16)<br />
Control box<br />
2X4-ø3(1/8) holes<br />
Terminal block<br />
(Transmission)<br />
Terminal block<br />
(Power source)<br />
2X4-ø3(1/8) holes<br />
Unit:mm(in.)<br />
Gas pipe Liquid pipe Drain hose<br />
ø19.05(3/4)<br />
Drain hose 32mm<br />
ø9.52(3/8)<br />
(1-1/4inch)<br />
<br />
ø22.2(7/8)<br />
<br />
Access door<br />
Note3<br />
800(31-1/2)<br />
150~200<br />
550 50(2)<br />
Access door Ceiling surface<br />
170(6-3/4±1/4)<br />
(Actual length)<br />
Make the access door<br />
at the appointed position properly<br />
for service maintenance.<br />
Note2<br />
50(2)<br />
200~300<br />
450<br />
50(2)<br />
730(28-3/4)<br />
450<br />
1350(53-3/16)<br />
102(4-1/16)<br />
50(2)<br />
1100(43-5/16)(DUCT)<br />
1250(49-1/4)<br />
100x10=1000(3-15/16x10=39-3/8)<br />
100(3-15/16)<br />
1326(52-1/4)(Suspension bolt pitch)<br />
1372(54-1/16)<br />
1100(43-5/16)(DUCT)<br />
29(1-3/16)<br />
15(5/8)<br />
105(4-3/16)<br />
Note 1.Use M10 screw for the suspension bolt (field supply).<br />
2.Keep the service space for the maintenance from the bottom<br />
when the heat exchanger is cleaned.<br />
3.Keep the service space for the maintenance from the bottom<br />
when the fan motor is changed.<br />
4.Make sure to install the air filter (field supply) on the air intake side.<br />
In case field supplied air filter is used, attach it<br />
where the filter service is easily done.<br />
30(1-3/16)<br />
41(1-5/8)<br />
164(6-1/2)<br />
327(12-7/8)<br />
100(3-15/16)<br />
20(13/16)<br />
100X3(=300)<br />
50(2)<br />
More than 20(13/16) More than 20(13/16)<br />
100(3-15/16)<br />
100x10=1000(3-15/16x10=39-3/8)<br />
Drain hose<br />
<strong>Mitsubishi</strong> <strong>Electric</strong> Air Conditioning & Refrigeration Systems Wo rks acquired ISO<br />
based on a review of quality warranties for the production of refrigeration and air<br />
conditioning equipment.<br />
ISO Authorization System<br />
The ISO 9000 series is a plant authorization system relating to quality warranties as<br />
development, production, installation and auxiliary services" for products built at<br />
an authorized plant.<br />
<strong>Mitsubishi</strong> <strong>Electric</strong> <strong>Sales</strong> <strong>Canada</strong> <strong>Inc</strong>.<br />
www.<strong>Mitsubishi</strong><strong>Electric</strong>.ca<br />
<strong>Mitsubishi</strong> <strong>Electric</strong> Air Conditioning & Refrigeration Systems Works acquired environmental<br />
The ISO 14000 series is a set of standards applying to environmental protection set by the<br />
International Standard Organization (ISO).<br />
Specifications are subject to change without notice.<br />
SB_<strong>PEFY</strong>-<strong>P96NMHSU</strong>-E_201112