Low Voltage Products<br />
<strong>COMPACT</strong> <strong>NS630b</strong> <strong>to</strong> <strong>1600</strong> A<br />
User manual
User manual for circuit breakers<br />
<strong>COMPACT</strong> <strong>NS630b</strong> <strong>to</strong> <strong>1600</strong> A<br />
Discovering Compact 2<br />
Manually operated Compact with a <strong>to</strong>ggle 4<br />
Components 4<br />
Opening, closing, reset 5<br />
Testing the device 6<br />
Locking the <strong>to</strong>ggle 7<br />
Manually operated Compact with a rotary handle 8<br />
Components 8<br />
Opening, closing, reset 9<br />
Testing the device 10<br />
Locking the rotary handle 11<br />
Remote operated Compact 14<br />
Components 14<br />
Opening, closing, reset 15<br />
Locking the controls 18<br />
Compact chassis 20<br />
Components 20<br />
Matching a device with its chassis 21<br />
Racking 22<br />
Racking 23<br />
Locking in the "disconnected" position 24<br />
Locking the switchboard door 26<br />
Locking the device when the door is open 27<br />
Locking the safety shutters 28<br />
<strong>Electric</strong>al auxiliaries 30<br />
<strong>Electric</strong>al diagrams 30<br />
Operation 32<br />
<strong>Electric</strong>al characteristics of contacts and control auxiliaries 33<br />
Start-up 36<br />
Start-up operations 36<br />
What <strong>to</strong> do when the circuit breaker trips? 37<br />
Compact operating conditions 38<br />
1<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
Discovering Compact<br />
Rating plate<br />
E60438A<br />
E89310A<br />
Compact<br />
<strong>NS630b</strong> N<br />
Ui 750 V<br />
Ics = 75% Icu<br />
Icw 25kA / 0.5s<br />
Uimp 8 kV<br />
Ue 220/240 Icu 50<br />
(V) 380/415 (kA) 50<br />
440 50<br />
500/525 40<br />
660/690 30<br />
cat B<br />
Rated current (x 100 A)<br />
Performance level<br />
Suitability for isolation<br />
Type of device:<br />
circuit breaker or switch-disconnec<strong>to</strong>r<br />
Ui - rated insulation level<br />
Uimp - impulse withstand voltage<br />
Icu - ultimate breaking capacity<br />
Ue - rated operational voltage<br />
Ics - rated service breaking capacity<br />
Icw - rated short-time withstand current<br />
Standards<br />
IEC 60947-2<br />
AS UNE CEI BS<br />
UTE VDE NEMA<br />
2<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
3<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Manually operated<br />
Compact with a <strong>to</strong>ggle<br />
Components<br />
E89311A<br />
Control auxiliary terminals<br />
OF1 ON/OFF indication contact<br />
OF2 ON/OFF indication contact<br />
OF3 ON/OFF indication contact<br />
SD trip-indication contact<br />
MX opening voltage release<br />
or MN undervoltage release<br />
Control unit<br />
SDE fault-trip indication contact<br />
Rating plate<br />
Spring-charging handle<br />
and ON/OFF <strong>to</strong>ggle<br />
Device for padlocking the <strong>to</strong>ggle<br />
in all positions<br />
push<br />
<strong>to</strong><br />
trip<br />
"Push <strong>to</strong> trip" but<strong>to</strong>n<br />
Device rating<br />
Padlocking device for the<br />
<strong>to</strong>ggle in the OFF position<br />
4<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
Opening, closing, reset<br />
E60436A<br />
Local opening and closing<br />
b OFF: breaker open, ON: breaker closed.<br />
E60435A<br />
ON<br />
ON<br />
OFF<br />
OFF<br />
E60433A<br />
Remote opening<br />
Use either:<br />
b an MX opening release<br />
b an MN undervoltage release<br />
b a delayed MN undervoltage release.<br />
When connected <strong>to</strong> the control panel, these releases may be used <strong>to</strong> remotely<br />
open the device.<br />
MX, MN<br />
Delay unit<br />
E71805A<br />
E71806A<br />
1 2 3<br />
4 5 6<br />
3 6<br />
MN<br />
UVR<br />
100/130 V<br />
AC/DC<br />
1012<br />
S<br />
0.5 1<br />
3 1.5<br />
Retardateur de MN<br />
Time delay for UVR<br />
1 2 3<br />
Resetting the device following a trip<br />
b the device trips.<br />
E60432A<br />
CLAC !<br />
b reset the device, then close it again.<br />
E60431A<br />
1<br />
ON<br />
reset<br />
1<br />
2<br />
5<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
Manually operated<br />
Compact with a <strong>to</strong>ggle<br />
Testing the device<br />
E60436A<br />
b close the device.<br />
E60429A<br />
ON<br />
1<br />
b press the "Press <strong>to</strong> trip" but<strong>to</strong>n.<br />
E60428A<br />
CLAC !<br />
2<br />
b push the <strong>to</strong>ggle down <strong>to</strong> reset the device, then back up close it again.<br />
E60427A<br />
3<br />
ON<br />
reset<br />
4<br />
6<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
Locking the <strong>to</strong>ggle<br />
E60425A<br />
Locking the <strong>to</strong>ggle in the OFF position using one <strong>to</strong> three<br />
padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />
E60424A<br />
OFF<br />
E60423A<br />
Locking the <strong>to</strong>ggle in the ON or OFF position using one <strong>to</strong><br />
three padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />
E60422A<br />
ON<br />
OFF<br />
7<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Manually operated<br />
Compact with a rotary<br />
handle<br />
Components<br />
E89312A<br />
CAF early-make contact<br />
CAO early-break contact<br />
OF1 ON/OFF indication contact<br />
OF2 ON/OFF indication contact<br />
OF3 ON/OFF indication contact<br />
SD trip-indication contact<br />
MX opening voltage release<br />
or MN undervoltage release<br />
Direct rotary handle<br />
Control unit<br />
SDE fault-trip indication<br />
contact<br />
Padlocking<br />
device<br />
Rating<br />
plate<br />
profalux<br />
Keylocks<br />
"Push <strong>to</strong> trip" but<strong>to</strong>n<br />
Extended rotary handle<br />
Padlocking device<br />
Door lock<br />
Extended rotary handle<br />
8<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Opening, closing, reset<br />
E71844A<br />
Local opening and closing<br />
b OFF: breaker open, ON: breaker closed.<br />
E71845A<br />
OFF<br />
ON<br />
E71847A<br />
Remote opening<br />
Use either:<br />
b an MX opening release<br />
b an MN undervoltage release<br />
b a delayed MN undervoltage release.<br />
When connected <strong>to</strong> the control panel, these releases may be used <strong>to</strong> remotely<br />
open the device.<br />
MX, MN<br />
Delay unit<br />
E71805A<br />
E71806A<br />
1 2 3<br />
4 5 6<br />
3 6<br />
MN<br />
UVR<br />
100/130 V<br />
AC/DC<br />
1012<br />
S<br />
0.5 1<br />
3 1.5<br />
Retardateur de MN<br />
Time delay for UVR<br />
1 2 3<br />
Resetting the device following a trip<br />
b the device trips.<br />
E71848A<br />
CLAC !<br />
1<br />
!<br />
b reset the device, then close it again.<br />
E71849A<br />
reset<br />
2<br />
3<br />
ON<br />
9<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Manually operated<br />
Compact with a rotary<br />
handle<br />
Testing the device<br />
E71844A<br />
b close the device.<br />
E71852A<br />
ON<br />
1<br />
b press the "Press <strong>to</strong> trip" but<strong>to</strong>n.<br />
E71850A<br />
CLAC !<br />
!<br />
2<br />
b turn the handle <strong>to</strong> reset the device, then back <strong>to</strong> close it again.<br />
E71851A<br />
reset<br />
ON<br />
3<br />
4<br />
10<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Locking the rotary handle<br />
E71854A<br />
Locking the direct or extended rotary handle in all positions<br />
using one <strong>to</strong> three padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />
E71859A<br />
b in the standard configuration, the device may be locked in the OFF<br />
position.<br />
OFF<br />
b remove the ring as indicated below <strong>to</strong> enable locking in both<br />
the ON and OFF positions.<br />
E71855A<br />
3<br />
1<br />
2<br />
b lock the handle.<br />
E71857A<br />
4 5<br />
b the controls are locked.<br />
E71883A<br />
ON<br />
OFF<br />
Note:<br />
the rotary handle can equipped for locking by both<br />
padlocks and keylocks.<br />
11<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
profalux<br />
Manually operated<br />
Compact with a rotary<br />
handle<br />
Locking the rotary handle<br />
E71862A<br />
Locking the direct rotary handle in all positions using a<br />
keylock<br />
b lock.<br />
E71867A<br />
E71863A<br />
E71865A<br />
1<br />
2<br />
b the controls are locked.<br />
E71758A<br />
ON<br />
OFF<br />
b unlock.<br />
2<br />
1<br />
Two types of keylocks are available<br />
RONIS<br />
PROFALUX<br />
E71810A<br />
E71811A<br />
12<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
eset<br />
reset<br />
tripped<br />
tripped<br />
reset<br />
reset<br />
tripped<br />
tripped<br />
Door locking when the device is in the ON position, using the<br />
extended rotary handle<br />
b in the standard configuration, the door cannot be opened when the rotary handle<br />
is set <strong>to</strong> the ON position.<br />
E71869A E71872A<br />
E71870A<br />
OFF<br />
2<br />
1<br />
3<br />
ON<br />
OK<br />
b it is possible, however, <strong>to</strong> defeat the door lock.<br />
4<br />
E71871A<br />
E71873A<br />
ON<br />
5 ON<br />
OK<br />
b the door-lock function may be permanently disabled by removing the lock.<br />
13<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Remote operated Compact<br />
Components<br />
E89313A<br />
MX opening voltage release<br />
or MN undervoltage release<br />
Fixed device<br />
SD trip-indication contact<br />
OF ON/OFF indication contacts<br />
SDE fault-trip indication contact<br />
Charging handle for<br />
the closing order<br />
Control auxiliary terminals<br />
Mo<strong>to</strong>r mechanism<br />
Locking in the OFF position<br />
using a padlock<br />
Locking in the OFF position<br />
using a keylock and a padlock<br />
Control unit<br />
ON but<strong>to</strong>n<br />
OFF but<strong>to</strong>n<br />
Operation counter<br />
Front<br />
E89314A<br />
Trip indication but<strong>to</strong>n used<br />
<strong>to</strong> reset before closing<br />
RESET<br />
Rating plate<br />
Locking by padlock, lead-seal cover<br />
or screws for pushbut<strong>to</strong>ns<br />
Indica<strong>to</strong>r for position<br />
of the main contacts<br />
Closing spring status indica<strong>to</strong>r<br />
14<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Opening, closing, reset<br />
E71885A<br />
MERLIN GERIN<br />
Local opening and closing<br />
Device open (OFF),<br />
discharged<br />
Device closed (ON),<br />
discharged<br />
E60405A<br />
O I<br />
Push OFF<br />
Push ON<br />
E60404A<br />
O I<br />
Push OFF<br />
Push ON<br />
Device open (OFF),<br />
charged<br />
Device closed (ON),<br />
charged<br />
E71759A<br />
E71877A<br />
O I<br />
Push OFF<br />
Push ON<br />
E71876A<br />
O I<br />
Push OFF<br />
Push ON<br />
15<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Remote operated Compact<br />
Opening, closing, reset<br />
E71760A<br />
Remote opening<br />
Use either:<br />
b an MX opening release<br />
b an MN undervoltage release<br />
b a delayed MN undervoltage release<br />
b a mo<strong>to</strong>r mechanism.<br />
When connected <strong>to</strong> the control panel, these releases may be used <strong>to</strong> remotely<br />
open the device.<br />
MX, MN<br />
Delay unit<br />
E71805A<br />
E71806A<br />
1 2 3<br />
4 5 6<br />
3 6<br />
MN<br />
UVR<br />
100/130 V<br />
AC/DC<br />
1012<br />
S<br />
0.5 1<br />
3 1.5<br />
Retardateur de MN<br />
Time delay for UVR<br />
1 2 3<br />
Mo<strong>to</strong>r mechanism<br />
E71880A<br />
E71805A<br />
E71760A<br />
Remotely close<br />
Mo<strong>to</strong>r mechanism<br />
E71880A<br />
E71805A<br />
E71805A<br />
E71805A<br />
16<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Manually recharge the device following a trip<br />
E71759A<br />
b the device trips.<br />
E71886A<br />
MERLIN GERIN<br />
CLAC !<br />
E71878A<br />
O I<br />
Push OFF<br />
Push ON<br />
E71887A<br />
b reset the device, then recharge it.<br />
E71879A<br />
MERLIN GERIN<br />
or<br />
17<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
Remote operated Compact<br />
Locking the controls<br />
Disabling local or remote closing<br />
E71888A<br />
Locking the device using one <strong>to</strong> three padlocks<br />
(shackle diameter 5 <strong>to</strong> 8 mm)<br />
b lock.<br />
Open the device.<br />
Pull out the tab.<br />
Install the padlock(s).<br />
E71807A<br />
I<br />
Push ON<br />
E71808A<br />
E60403A<br />
Push<br />
b the controls are locked.<br />
Push<br />
b unlock.<br />
E60402A<br />
E71889A<br />
b push in the tab.<br />
E71761A<br />
Note:<br />
Padlocks and keylocks may be used <strong>to</strong>gether.<br />
18<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
E71802A<br />
Locking the device using a keylock and/or one <strong>to</strong> three<br />
padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />
b keylocking.<br />
Open the device.<br />
Turn the key.<br />
Remove the key.<br />
E71807A<br />
I<br />
Push ON<br />
E60401A<br />
E60400A<br />
Push<br />
Padlocks and keylocks may be used<br />
<strong>to</strong>gether.<br />
Locking using padlocks is identical <strong>to</strong> the<br />
system on the previous page.<br />
b the controls are locked.<br />
E71889A<br />
Push<br />
b unlock.<br />
Insert the key.<br />
Turn the key.<br />
Push in the tab.<br />
Two types of keylocks are available<br />
RONIS<br />
PROFALUX<br />
E71810A<br />
E71811A<br />
E60399A<br />
E71800A<br />
E71801A<br />
19<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
Compact chassis<br />
Components<br />
E89315A<br />
Carriage switch terminals<br />
ON/OFF indication contact terminals<br />
Control auxiliary terminals<br />
Arc-chute cover<br />
Auxiliary terminal shield<br />
Terminals for control-unit<br />
and fault-trip indication<br />
contacts<br />
Carriage switch terminals<br />
Racking interlock<br />
Carrying grip<br />
Mismatch protection<br />
Door interlock<br />
Locking by keylocks<br />
Locking by padlocks<br />
"Connected", "test" or "disconnected" position indica<strong>to</strong>r<br />
Crank socket<br />
Position release but<strong>to</strong>n<br />
Crank s<strong>to</strong>rage<br />
Crank<br />
Disconnecting-contact cluster<br />
Withdraw grip<br />
Shutter locking blocks<br />
Safety shutters<br />
MERLIN GERIN<br />
Side plate for<br />
withdrawable<br />
device<br />
Manually operated device<br />
with a rotary handle<br />
Manually operated<br />
device with a <strong>to</strong>ggle<br />
<strong>Electric</strong>ally operated device<br />
20<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Matching a device with its chassis<br />
To set up a mismatch-prevention<br />
combination for the device and the chassis,<br />
see the mismatch-prevention installation<br />
manual.<br />
E60408A<br />
The mismatch protection ensures that a device is installed only in a chassis with<br />
compatible characteristics.<br />
The possible combinations are listed below.<br />
2<br />
4<br />
1<br />
3<br />
5<br />
A<br />
B<br />
C<br />
D<br />
E<br />
A B C<br />
A B D<br />
A B E<br />
A B<br />
A C D<br />
A C E<br />
A C<br />
A D E<br />
A D<br />
A E<br />
4 5<br />
3 5<br />
3 4<br />
3 4 5<br />
2 5<br />
2 4<br />
2 4 5<br />
2 3<br />
2 3 5<br />
2 3 4<br />
B C D<br />
B C E<br />
B C<br />
B D E<br />
B D<br />
B E<br />
C D E<br />
C D<br />
C E<br />
D E<br />
1 5<br />
1 4<br />
1 4 5<br />
1 3<br />
1 3 5<br />
1 3 4<br />
1 2<br />
1 2 5<br />
1 2 4<br />
1 2 3<br />
21<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push O F<br />
O OFF<br />
push ON<br />
discharged<br />
push O F<br />
O OFF<br />
push ON<br />
discharged<br />
push O F<br />
O OFF<br />
push ON<br />
discharged<br />
Compact chassis<br />
Racking<br />
For complete information on Compact<br />
handling and mounting, see the installation<br />
manual(s).<br />
Removing the rails<br />
Press the release tabs and<br />
pull the rails out.<br />
To put the rails back in, press the<br />
release tabs and push the rails in.<br />
Before mounting Compact NS, make sure<br />
it matches the chassis.<br />
E71813A<br />
1<br />
E71814A<br />
2<br />
3<br />
Inserting the device<br />
Open the circuit breaker<br />
(in any case, it opens<br />
au<strong>to</strong>matically during<br />
connection).<br />
Position the circuit breaker on the rails.<br />
Check that it rests on all four supports.<br />
E71807A<br />
E60412A<br />
If you cannot insert the device in the<br />
chassis, check that the mismatch protection<br />
on the chassis corresponds<br />
<strong>to</strong> that on the device.<br />
Push the device in<strong>to</strong> the chassis, taking care not <strong>to</strong> push on the control unit.<br />
E60411A<br />
E60410A<br />
I<br />
Push ON<br />
Push<br />
MERLIN GERIN<br />
O<br />
I<br />
O<br />
I<br />
E60409A<br />
O<br />
I<br />
22<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Racking<br />
Prerequisites<br />
To connect and disconnect the device,<br />
the crank must be used.<br />
The locking systems, padlocks and the<br />
racking interlock all inhibit use of the crank.<br />
Racking the circuit breaker from the "disconnected" <strong>to</strong> "test"<br />
position, then <strong>to</strong> "connected" position<br />
The device is in "disconnected" position.<br />
DB110366A<br />
The indica<strong>to</strong>r on the front signals the position of the circuit breaker in the chassis.<br />
E71815A<br />
The device is in "test" position.<br />
The device is in "test" position.<br />
Remove the crank or continue <strong>to</strong><br />
"connected" position.<br />
b"connected" position<br />
E60413A<br />
Test<br />
The device is in "connected" position.<br />
E60414A<br />
b"test" position<br />
DB110365<br />
Withdrawing the circuit breaker from the "connected"<br />
<strong>to</strong> "test" position, then <strong>to</strong> "disconnected" position<br />
The circuit breaker is in "connected" position.<br />
Test<br />
b "disconnected" position<br />
E60415A<br />
Test<br />
The circuit breaker is in "test" position.<br />
The circuit breaker is in "test" position.<br />
Remove the crank or continue <strong>to</strong><br />
"disconnected" position.<br />
Note:<br />
These operations require that all chassis-locking<br />
functions be disabled (see page 24).<br />
The circuit breaker is in "disconnected" position.<br />
23<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Compact chassis<br />
Locking in the "disconnected"<br />
position<br />
Using one <strong>to</strong> three padlocks<br />
Combination of locking systems.<br />
It is possible <strong>to</strong> lock the device on the<br />
chassis in the "disconnected" position<br />
using:<br />
b one <strong>to</strong> three padlocks<br />
b one or two keylocks<br />
b a combination of both.<br />
E71816A<br />
Locking<br />
Use padlocks with a maximum shackle diameter of 5 <strong>to</strong> 8 millimetres.<br />
Device in "disconnected"<br />
position.<br />
Pull out the tab.<br />
1 2<br />
E71817A<br />
Test<br />
Insert the shackle<br />
(max. diameter 5 <strong>to</strong> 8 mm)<br />
of the padlock(s).<br />
The crank cannot be inserted.<br />
E71818A<br />
3 4<br />
E71819A<br />
Unlocking<br />
Remove the padlock(s).<br />
Release the tab.<br />
E71820A<br />
1<br />
E71821A<br />
2<br />
The crank can be inserted.<br />
E71822A<br />
3<br />
Note:<br />
Padlocks and keylocks may be used <strong>to</strong>gether.<br />
If specified when ordering the chassis, this locking<br />
function may be adapted <strong>to</strong> operate in all positions<br />
("connected", "test" and "disconnected"), instead of in<br />
"disconnected" position alone.<br />
24<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Using one or two keylocks<br />
Locking<br />
Device in "disconnected"<br />
position.<br />
Turn the key(s).<br />
E71823A<br />
1<br />
E71824A<br />
2<br />
Test<br />
Remove the key(s).<br />
The crank cannot be<br />
inserted.<br />
E71825A<br />
3<br />
E71826A<br />
Unlocking<br />
Insert the key(s).<br />
Turn the key(s).<br />
The crank can be inserted.<br />
E71827A<br />
Three types of keylocks are available.<br />
RONIS<br />
PROFALUX<br />
CASTELL<br />
E71810A<br />
E71811A<br />
E71812A<br />
1 2<br />
E71828A<br />
E71829A<br />
3<br />
25<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
O<br />
push ON<br />
push O F<br />
O O F<br />
I<br />
push ON<br />
discharged<br />
Compact chassis<br />
Locking the switchboard door<br />
The locking device is installed on the left or right-hand side of the chassis.<br />
b when the device is in "connected" or "test" position, the latch is lowered and the<br />
door is locked.<br />
b when the device is in "disconnected" position, the latch is raised and the door is<br />
unlocked.<br />
Disabling door opening<br />
Enabling door opening<br />
Turn the crank until the<br />
device is in<br />
"disconnected" position.<br />
The door is unlocked.<br />
E71834A<br />
E71835A<br />
E71831A<br />
E71832A<br />
E71833A<br />
E71830A<br />
O<br />
push OFF<br />
O OFF<br />
O<br />
push OFF<br />
I<br />
discharged<br />
O OFF<br />
Close the door.<br />
Turn the crank until the<br />
device is in "test" or<br />
"connected" position.<br />
The door is locked.<br />
26<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
O<br />
push O F<br />
O O F<br />
I<br />
push ON<br />
discharged<br />
Locking the device when the door<br />
is open<br />
E71836A<br />
O<br />
push OFF<br />
I<br />
push ON<br />
discharged<br />
O OFF<br />
When the door is open,<br />
the crank cannot be inserted.<br />
When the door is closed,<br />
the crank can be inserted.<br />
E71837A<br />
E71838A<br />
27<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Compact chassis<br />
Locking the safety shutters<br />
Four locking possibilities inside the chassis using one or two<br />
padlocks (maximum shackle diameter 5 <strong>to</strong> 8 mm) for each shutter<br />
Top and bot<strong>to</strong>m shutters not<br />
locked.<br />
Top shutter not locked.<br />
Bot<strong>to</strong>m shutter locked.<br />
E71840A<br />
E71839A<br />
Top shutter locked.<br />
Bot<strong>to</strong>m shutter not locked.<br />
Top and bot<strong>to</strong>m shutters locked.<br />
28<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
29<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
<strong>Electric</strong>al auxiliaries<br />
<strong>Electric</strong>al diagrams<br />
Fixed and withdrawable devices<br />
The diagram is shown with circuits<br />
de-energised, all devices open, connected<br />
and charged and relays in normal position.<br />
Power<br />
Control unit<br />
Remote operation<br />
DB112769<br />
E71765A<br />
AT<br />
BPO<br />
BPF<br />
D2<br />
MN<br />
MX<br />
D1<br />
C11<br />
A1<br />
C2<br />
A4<br />
A2<br />
A3<br />
(4)<br />
(3)<br />
Control unit<br />
Com UC1 UC2 UC3 M6C<br />
Remote operation<br />
CAF2 / CAF1 SDE SD<br />
E5 E6 Z5 M1 M2 M3 F2+ Q3<br />
D2 / C12 A4 A2<br />
E3 E4 Z3 Z4 T3 T4 VN Q2<br />
B4<br />
E1 E2 Z1 Z2 T1 T2 F1 – Q1<br />
D1 / C11 A1<br />
A<br />
P<br />
Control unit<br />
Remote operation<br />
b<br />
b<br />
Com: E1-E6 communication<br />
SDE : Fault-trip indication contact (supplied as standard)<br />
b<br />
b<br />
b<br />
b<br />
UC1 :<br />
Z1-Z5 zone selective interlocking;<br />
Z1 = ZSI = ZSI OUT SOURCE<br />
Z2 = ZSI OUT; Z3 = ZSI IN SOURCE<br />
Z4 = ZSI IN ST (short time)<br />
Z5 = ZSI IN GF (ground fault)<br />
M1 = Vigi module input (Micrologic 7)<br />
SD : Trip-indication contact (supplied as standard)<br />
MN : Undervoltage release<br />
or<br />
MX : Shunt release (standard or communicating)<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
b<br />
UC2 : T1, T2, T3, T4 = external neutral;<br />
M2, M3 = Vigi module input<br />
(Micrologic 7)<br />
UC3 : F2+, F1- external 24 V DC power<br />
supply VN external voltage connec<strong>to</strong>r<br />
(must be connected <strong>to</strong> neutral with<br />
circuit breaker 3P)<br />
M6C : 6 programmable contacts (must be<br />
connected <strong>to</strong> external relay M6C)<br />
ext. 24 V DC power supply required<br />
A: Digital ammeter<br />
P: A + power meter + programmable protection<br />
30<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Indication contacts<br />
Chassis contacts<br />
E89316A<br />
Open<br />
Closed<br />
Default<br />
Default<br />
Closed<br />
Open<br />
E89317A<br />
Disconnected Connected Test<br />
541<br />
531<br />
542<br />
544<br />
532<br />
534<br />
522<br />
524<br />
512<br />
514<br />
SD<br />
CAF2<br />
CAF1<br />
CAO2<br />
CAO1<br />
21<br />
11<br />
81<br />
91<br />
521<br />
511<br />
32<br />
34<br />
22<br />
24<br />
12<br />
14<br />
82<br />
84<br />
92<br />
94<br />
OF3 OF2 OF1 SDE<br />
31<br />
821<br />
822<br />
824<br />
812<br />
814<br />
CD2<br />
CD1<br />
811<br />
331<br />
332<br />
334<br />
CE3<br />
321<br />
322<br />
324<br />
CE2<br />
311<br />
312<br />
314<br />
914<br />
912<br />
CT1<br />
CE1<br />
911<br />
Indication contacts<br />
CAF1CAF2 SDE SD CAO2 CAO1 OF3 OF2 OF1<br />
544 534 84 94 544 514 34 24 14<br />
542 532 82 92 522 512 32 22 12<br />
542 531 81 91 521 511 31 21 11<br />
Chassis contacts<br />
CD2 CD1 CE3 CE2 CE1 CT1<br />
824 814 334 324 314 914<br />
822 812 332 322 312 912<br />
821 811 331 321 311 911<br />
Indication contacts<br />
OF3 / OF2 / OF1: ON/OFF indication contacts<br />
Chassis contacts<br />
CD2: Disconnected-<br />
CD1 position<br />
contacts<br />
CE3: Connected-<br />
CE2 position<br />
CE1 contacts<br />
CT1: Test-position<br />
contacts<br />
Key:<br />
XXX<br />
Withdrawable device only<br />
SDE1, OF1, OF2, OF3, OF4 supplied as standard<br />
Interconnected connections<br />
(only one wire per connection point)<br />
31<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
<strong>Electric</strong>al auxiliaries<br />
Operation<br />
The ON/OFF indication contacts signal<br />
the status of the device main contacts.<br />
Device<br />
E89318A<br />
completely closed<br />
completely open<br />
closed<br />
open<br />
main contacts<br />
open<br />
closed<br />
closed<br />
open<br />
OF: ON/OFF (closed/open) indication<br />
changeover contacts<br />
The carriage switches indicate the<br />
"connected", "test" and "disconnected"<br />
positions.<br />
Chassis<br />
E89319A<br />
completely connected<br />
separation of the main circuits<br />
test position<br />
separation of the auxiliary circuits<br />
completely disconnected<br />
open<br />
closed<br />
CE: connected-position<br />
carriage switch contact<br />
open<br />
closed<br />
closed<br />
open<br />
open<br />
closed<br />
CT: test-position carriage<br />
switch contact<br />
open<br />
closed<br />
CD: disconnected-position<br />
carriage switch contact<br />
32<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
<strong>Electric</strong>al characteristics of<br />
contacts and control auxiliaries<br />
Device indication contacts<br />
designation type standard, minimum current 100 mA 24 V low level, minimum current 2 mA 15 V<br />
OF ON/OFF contact 3 changeover contacts V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />
breaking capacity 480 6 A (rms) 240 5 A (rms)<br />
(AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />
947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />
125 0.5 A 125 0.5 A<br />
250 0.3 A 250 0.3 A<br />
SD fault indication 1 changeover contact V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />
breaking capacity 480 6 A (rms) 240 5 A (rms)<br />
(AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />
947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />
125 0.5 A 125 0.5 A<br />
250 0.3 A 250 0.3 A<br />
SDE fault-trip indication 1 changeover contact V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />
for device with mo<strong>to</strong>r breaking capacity 480 6 A (rms) 240 5 A (rms)<br />
mechanism (AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />
947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />
125 0.5 A 125 0.5 A<br />
250 0.3 A 250 0.3 A<br />
CAO early-break switch 2 changeover contacts V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />
for device with rotary breaking capacity 480 6 A (rms) 240 5 A (rms)<br />
handle (AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />
947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />
125 0.5 A 125 0.5 A<br />
250 0.3 A 250 0.3 A<br />
CAF early-make switch 2 changeover contacts V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />
for device with rotary breaking capacity 480 6 A (rms) 240 5 A (rms)<br />
handle (AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />
947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />
125 0.5 A 125 0.5 A<br />
250 0.3 A 250 0.3 A<br />
Device control auxiliaries<br />
designation power supply threshold consumption response time<br />
MX opening release V AC: 50/60 Hz: 24/48 - 0.7 <strong>to</strong> 1.1 Un pick-up: 200 VA or W (80 ms) device at Un:<br />
100/130 - 200/250 - 277 - hold: 4.5 VA or W 50 ms ± 10<br />
380/480<br />
V DC: 12 - 24/30 - 48/60 -<br />
100/130 - 200/250<br />
MN undervoltage release V AC: 50/60 Hz: 24/48 - open: pick-up: 200 VA or W (80 ms) device at Un:<br />
100/130 - 200/250 - 0.35 <strong>to</strong> 0.7 Un hold: 4.5 VA or W 40 ms ± 10<br />
380/480 close: 0.85 Un<br />
V DC: 24/30 - 48/60 -<br />
100/130 - 200/250<br />
Delay unit for undervoltage V AC: 50/60 Hz open: 200 VA device at Un:<br />
release V DC not adjustable: 0.35 <strong>to</strong> 0.7 Un not adjustable:<br />
100/130 - 200/250 close: 0.85 Un 0.25 s<br />
V DC adjustable:<br />
adjustable:<br />
48/60 - 100/130 - 0.5 - 0.9 - 1.5 - 3 s<br />
200/250 - 380/480<br />
Mo<strong>to</strong>r mechanism<br />
designation power supply threshold consumption and recharge time and<br />
mo<strong>to</strong>r overcurrent operating rate<br />
Mo<strong>to</strong>r mechanism V AC: 50/60 Hz: 48/60 - 0.85 <strong>to</strong> 1.1 Un consumption: 180 VA or W 3 seconds max.<br />
100/130 - 200/240 - 277 - overcurrent: 2 <strong>to</strong> 3 In for 0.1 s 3 cycles per minute<br />
400/440 - 480<br />
V DC: 24/30 - 48/60 -<br />
100/125 - 200/250<br />
"Connected", "test" and "disconnected" position carriage switches<br />
designation type standard, minimum current 100 mA 24 V low level, minimum current 2 mA 15 V<br />
CE, CT, CD 3 changeover contacts V AC 240 8 A (rms) V AC 24/48 5 A (rms)<br />
breaking capacity 380 8 A (rms) 240 5 A (rms)<br />
(AC 12 / DC 12 as per 480 8 A (rms) 380 5 A (rms)<br />
947-5-1) 690 6 A (rms)<br />
V DC 24/48 2.5 A V DC 24/48 2.5 A<br />
125 0.8 A 125 0.8 A<br />
250 0.3 A 250 0.3 A<br />
33<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
<strong>Electric</strong>al auxiliaries<br />
<strong>Electric</strong>al characteristics of<br />
contacts and control auxiliaries<br />
Wiring of control auxiliaries<br />
Under pick-up conditions, the level of consumption is approximately 150 <strong>to</strong> 200 VA.<br />
Consequently, for low supply voltages (12, 24, 48 V), cables must not exceed a<br />
maximum length determined by the supply voltage and the cross-section<br />
of the cables.<br />
Indicative values for maximum cable lengths (in meters)<br />
12 V 24 V 48 V<br />
2.5 mm 2 1.5 mm 2 2.5 mm 2 1.5 mm 2 2.5 mm 2 1.5 mm 2<br />
MN 100% source<br />
voltage — — 58 36 280 165<br />
85% source<br />
voltage — — 16 10 75 45<br />
MX-XF 100% source<br />
voltage 21 12 115 70 550 330<br />
85% source<br />
voltage 10 6 75 44 350 210<br />
Note:<br />
The indicated length is that for each of the two supply wires.<br />
34<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
35<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
Start-up<br />
Start-up operations<br />
Procedure<br />
These operations must be carried out<br />
before using a device for the first time.<br />
A general check of the device takes only a few minutes and avoids any risk of<br />
mistakes due <strong>to</strong> errors or negligence.<br />
A general check must be carried out:<br />
b prior <strong>to</strong> initial use<br />
b following an extended period during which the device is not used.<br />
A check must be carried out with the entire switchboard de-energised.<br />
In switchboards with compartments, only those compartments that may be<br />
accessed by the opera<strong>to</strong>rs must be de-energised.<br />
<strong>Electric</strong>al tests<br />
Insulation and dielectric-withstand tests must be carried out immediately after<br />
delivery of the switchboard. These tests are precisely defined by international<br />
standards and must be directed and carried out by a qualified expert.<br />
Prior <strong>to</strong> running the tests, it is absolutely necessary <strong>to</strong>:<br />
b disconnect all the electrical auxiliaries of the device (MCH, MX, MN)<br />
b remove the long-time rating plug on the 7.0 A control units.<br />
Removal of the rating plug disconnects the voltage measurement input.<br />
Switchboard inspection<br />
Check that the devices are installed in a clean environment, free of any installation<br />
scrap or items (<strong>to</strong>ols, electrical wires, broken parts or shreds, metal objects, etc.).<br />
Conformity with the installation diagram<br />
Check that the devices conform with the installation diagram:<br />
b breaking capacities indicated on the rating plates<br />
b identification of the control unit (type, rating)<br />
b presence of any optional functions (mo<strong>to</strong>r mechanism)<br />
b protection settings (long time, short time, instantaneous, ground fault)<br />
b identification of the protected circuit marked on the front of each device.<br />
Condition of connections and auxiliaries<br />
Check device mounting in the switchboard and the tightness of power connections.<br />
Check that all auxiliaries and accessories are correctly installed:<br />
b electrical auxiliaries<br />
b terminal blocks<br />
b connections of auxiliary circuits.<br />
Operation<br />
Check the mechanical operation of the devices:<br />
b opening of contacts<br />
b closing of contacts.<br />
Check on the control unit<br />
Check the control unit of each circuit breaker using the respective user manuals.<br />
36<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
What <strong>to</strong> do when the circuit<br />
breaker trips?<br />
Note the fault<br />
Faults are signalled locally and remotely by the indica<strong>to</strong>rs and auxiliary contacts<br />
installed on devices (depending on each configuration). See page 32 in this manual<br />
and the user manual of the control unit for information on the fault indications<br />
available with your circuit breaker.<br />
Identify the cause of tripping<br />
A circuit must never be reclosed (locally or remotely) before the cause of the fault<br />
has been identified and cleared.<br />
Depending on the type of fault and the criticality of the loads, a number of<br />
precautionary measures must be taken, in particular the insulation and dielectric<br />
tests on a part of or the entire installation. These checks and test must be directed<br />
and carried out by qualified personnel.<br />
Inspect the circuit breaker following a short-circuit<br />
b check the tightness of connections (see the device installation manual)<br />
b check the disconnecting-contact clusters.<br />
Reset the circuit breaker<br />
The circuit breaker can be reset locally or remotely. See pages 5, 9 and 15<br />
in this manual for information on how the device can be reset.<br />
37<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
push<br />
<strong>to</strong><br />
trip<br />
Compact operating<br />
conditions<br />
E60418A E60417A<br />
E60416A<br />
Ambient temperature<br />
Compact devices can operate under the following temperature conditions:<br />
b the electrical and mechanical characteristics are stipulated for an ambient<br />
temperature of -5° C <strong>to</strong> +70° C<br />
b circuit-breaker closing is guaranteed down <strong>to</strong> -35° C<br />
b Compact (without the control unit) can be s<strong>to</strong>red in an ambient temperature<br />
of -40° C <strong>to</strong> +85° C<br />
b the control unit can be s<strong>to</strong>red in an ambient temperature of -25° C <strong>to</strong> +85° C.<br />
Extreme atmospheric conditions<br />
Compact devices have successfully passed the tests defined by the following<br />
standards for extreme atmospheric conditions:<br />
b IEC 68-2-1: dry cold at -55° C<br />
b IEC 68-2-2: dry heat at +85° C<br />
b IEC 68-2-30: damp heat (temperature +55° C, relative humidity 95%)<br />
b IEC 68-2-52 level 2: salt mist.<br />
Compact devices can operate in the industrial environments defined by standard<br />
IEC 947 (pollution degree up <strong>to</strong> 3).<br />
It is nonetheless advised <strong>to</strong> check that the devices are installed in suitably cooled<br />
switchboards without excessive dust.<br />
Vibrations<br />
Compact devices resist electromagnetic or mechanical vibrations.<br />
Tests are carried out in compliance with standard IEC 68-2-6 for the levels required<br />
by merchant-marine inspection organisations (Veritas, Lloyd's, etc.):<br />
b 2 <strong>to</strong> 13.2 Hz: amplitude ±1 mm<br />
b 13.2 <strong>to</strong> 100 Hz: constant acceleration 0.7 g.<br />
Excessive vibration may cause tripping, breaks in connections or damage <strong>to</strong><br />
mechanical parts.<br />
38<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
push<br />
<strong>to</strong><br />
trip<br />
E60420A<br />
Electromagnetic disturbances<br />
Compact devices are protected against:<br />
v overvoltages caused by devices that generate electromagnetic disturbances<br />
v overvoltages caused by an atmospheric disturbance or by a distribution-system<br />
outage (e.g. failure of a lighting system)<br />
v devices emitting radio waves (radios, walkie-talkies, radar, etc.)<br />
v electrostatic discharges produced by users.<br />
Compact devices have successfully passed the electromagnetic-compatibility tests<br />
(EMC) defined by the following international standards:<br />
b IEC 947-2, appendix F<br />
b IEC 947-2, appendix B (trip units with earth-leakage function).<br />
The above tests guarantee that:<br />
b no nuisance tripping occurs<br />
b tripping times are respected.<br />
Cleaning<br />
v non-metallic parts:<br />
never use solvent, soap or any other cleaning product. Clean with a dry cloth only<br />
v metal parts:<br />
clean with a dry cloth whenever possible. If solvent, soap or any other cleaning<br />
product must be used, make sure that it does not come in<strong>to</strong> contact with<br />
non-metallic parts.<br />
39<br />
Compact NS<br />
<strong>Schneider</strong> <strong>Electric</strong>
<strong>Schneider</strong> <strong>Electric</strong> Industries SAS<br />
5, rue Nadar<br />
92506 Rueil-Malmaison Cedex<br />
France<br />
Tel: +33 (0)1 41 29 82 00<br />
Fax:+33 (0)1 47 51 80 20<br />
http://www.schneider-electric.com<br />
http://www.merlin-gerin.com<br />
As standards, specifications and designs develop from time, always ask for confirmation of the<br />
information given in this publication.<br />
Printed on recycled paper<br />
Designed by: SEDOC<br />
Pho<strong>to</strong>s: <strong>Schneider</strong><br />
Printed by:<br />
51201640AA-C1 11-2006