Low Voltage Products<br />

<strong>COMPACT</strong> <strong>NS630b</strong> <strong>to</strong> <strong>1600</strong> A<br />

User manual


User manual for circuit breakers<br />

<strong>COMPACT</strong> <strong>NS630b</strong> <strong>to</strong> <strong>1600</strong> A<br />

Discovering Compact 2<br />

Manually operated Compact with a <strong>to</strong>ggle 4<br />

Components 4<br />

Opening, closing, reset 5<br />

Testing the device 6<br />

Locking the <strong>to</strong>ggle 7<br />

Manually operated Compact with a rotary handle 8<br />

Components 8<br />

Opening, closing, reset 9<br />

Testing the device 10<br />

Locking the rotary handle 11<br />

Remote operated Compact 14<br />

Components 14<br />

Opening, closing, reset 15<br />

Locking the controls 18<br />

Compact chassis 20<br />

Components 20<br />

Matching a device with its chassis 21<br />

Racking 22<br />

Racking 23<br />

Locking in the "disconnected" position 24<br />

Locking the switchboard door 26<br />

Locking the device when the door is open 27<br />

Locking the safety shutters 28<br />

<strong>Electric</strong>al auxiliaries 30<br />

<strong>Electric</strong>al diagrams 30<br />

Operation 32<br />

<strong>Electric</strong>al characteristics of contacts and control auxiliaries 33<br />

Start-up 36<br />

Start-up operations 36<br />

What <strong>to</strong> do when the circuit breaker trips? 37<br />

Compact operating conditions 38<br />

1<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

Discovering Compact<br />

Rating plate<br />

E60438A<br />

E89310A<br />

Compact<br />

<strong>NS630b</strong> N<br />

Ui 750 V<br />

Ics = 75% Icu<br />

Icw 25kA / 0.5s<br />

Uimp 8 kV<br />

Ue 220/240 Icu 50<br />

(V) 380/415 (kA) 50<br />

440 50<br />

500/525 40<br />

660/690 30<br />

cat B<br />

Rated current (x 100 A)<br />

Performance level<br />

Suitability for isolation<br />

Type of device:<br />

circuit breaker or switch-disconnec<strong>to</strong>r<br />

Ui - rated insulation level<br />

Uimp - impulse withstand voltage<br />

Icu - ultimate breaking capacity<br />

Ue - rated operational voltage<br />

Ics - rated service breaking capacity<br />

Icw - rated short-time withstand current<br />

Standards<br />

IEC 60947-2<br />

AS UNE CEI BS<br />

UTE VDE NEMA<br />

2<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


3<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Manually operated<br />

Compact with a <strong>to</strong>ggle<br />

Components<br />

E89311A<br />

Control auxiliary terminals<br />

OF1 ON/OFF indication contact<br />

OF2 ON/OFF indication contact<br />

OF3 ON/OFF indication contact<br />

SD trip-indication contact<br />

MX opening voltage release<br />

or MN undervoltage release<br />

Control unit<br />

SDE fault-trip indication contact<br />

Rating plate<br />

Spring-charging handle<br />

and ON/OFF <strong>to</strong>ggle<br />

Device for padlocking the <strong>to</strong>ggle<br />

in all positions<br />

push<br />

<strong>to</strong><br />

trip<br />

"Push <strong>to</strong> trip" but<strong>to</strong>n<br />

Device rating<br />

Padlocking device for the<br />

<strong>to</strong>ggle in the OFF position<br />

4<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

Opening, closing, reset<br />

E60436A<br />

Local opening and closing<br />

b OFF: breaker open, ON: breaker closed.<br />

E60435A<br />

ON<br />

ON<br />

OFF<br />

OFF<br />

E60433A<br />

Remote opening<br />

Use either:<br />

b an MX opening release<br />

b an MN undervoltage release<br />

b a delayed MN undervoltage release.<br />

When connected <strong>to</strong> the control panel, these releases may be used <strong>to</strong> remotely<br />

open the device.<br />

MX, MN<br />

Delay unit<br />

E71805A<br />

E71806A<br />

1 2 3<br />

4 5 6<br />

3 6<br />

MN<br />

UVR<br />

100/130 V<br />

AC/DC<br />

1012<br />

S<br />

0.5 1<br />

3 1.5<br />

Retardateur de MN<br />

Time delay for UVR<br />

1 2 3<br />

Resetting the device following a trip<br />

b the device trips.<br />

E60432A<br />

CLAC !<br />

b reset the device, then close it again.<br />

E60431A<br />

1<br />

ON<br />

reset<br />

1<br />

2<br />

5<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

Manually operated<br />

Compact with a <strong>to</strong>ggle<br />

Testing the device<br />

E60436A<br />

b close the device.<br />

E60429A<br />

ON<br />

1<br />

b press the "Press <strong>to</strong> trip" but<strong>to</strong>n.<br />

E60428A<br />

CLAC !<br />

2<br />

b push the <strong>to</strong>ggle down <strong>to</strong> reset the device, then back up close it again.<br />

E60427A<br />

3<br />

ON<br />

reset<br />

4<br />

6<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

Locking the <strong>to</strong>ggle<br />

E60425A<br />

Locking the <strong>to</strong>ggle in the OFF position using one <strong>to</strong> three<br />

padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />

E60424A<br />

OFF<br />

E60423A<br />

Locking the <strong>to</strong>ggle in the ON or OFF position using one <strong>to</strong><br />

three padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />

E60422A<br />

ON<br />

OFF<br />

7<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Manually operated<br />

Compact with a rotary<br />

handle<br />

Components<br />

E89312A<br />

CAF early-make contact<br />

CAO early-break contact<br />

OF1 ON/OFF indication contact<br />

OF2 ON/OFF indication contact<br />

OF3 ON/OFF indication contact<br />

SD trip-indication contact<br />

MX opening voltage release<br />

or MN undervoltage release<br />

Direct rotary handle<br />

Control unit<br />

SDE fault-trip indication<br />

contact<br />

Padlocking<br />

device<br />

Rating<br />

plate<br />

profalux<br />

Keylocks<br />

"Push <strong>to</strong> trip" but<strong>to</strong>n<br />

Extended rotary handle<br />

Padlocking device<br />

Door lock<br />

Extended rotary handle<br />

8<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Opening, closing, reset<br />

E71844A<br />

Local opening and closing<br />

b OFF: breaker open, ON: breaker closed.<br />

E71845A<br />

OFF<br />

ON<br />

E71847A<br />

Remote opening<br />

Use either:<br />

b an MX opening release<br />

b an MN undervoltage release<br />

b a delayed MN undervoltage release.<br />

When connected <strong>to</strong> the control panel, these releases may be used <strong>to</strong> remotely<br />

open the device.<br />

MX, MN<br />

Delay unit<br />

E71805A<br />

E71806A<br />

1 2 3<br />

4 5 6<br />

3 6<br />

MN<br />

UVR<br />

100/130 V<br />

AC/DC<br />

1012<br />

S<br />

0.5 1<br />

3 1.5<br />

Retardateur de MN<br />

Time delay for UVR<br />

1 2 3<br />

Resetting the device following a trip<br />

b the device trips.<br />

E71848A<br />

CLAC !<br />

1<br />

!<br />

b reset the device, then close it again.<br />

E71849A<br />

reset<br />

2<br />

3<br />

ON<br />

9<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Manually operated<br />

Compact with a rotary<br />

handle<br />

Testing the device<br />

E71844A<br />

b close the device.<br />

E71852A<br />

ON<br />

1<br />

b press the "Press <strong>to</strong> trip" but<strong>to</strong>n.<br />

E71850A<br />

CLAC !<br />

!<br />

2<br />

b turn the handle <strong>to</strong> reset the device, then back <strong>to</strong> close it again.<br />

E71851A<br />

reset<br />

ON<br />

3<br />

4<br />

10<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Locking the rotary handle<br />

E71854A<br />

Locking the direct or extended rotary handle in all positions<br />

using one <strong>to</strong> three padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />

E71859A<br />

b in the standard configuration, the device may be locked in the OFF<br />

position.<br />

OFF<br />

b remove the ring as indicated below <strong>to</strong> enable locking in both<br />

the ON and OFF positions.<br />

E71855A<br />

3<br />

1<br />

2<br />

b lock the handle.<br />

E71857A<br />

4 5<br />

b the controls are locked.<br />

E71883A<br />

ON<br />

OFF<br />

Note:<br />

the rotary handle can equipped for locking by both<br />

padlocks and keylocks.<br />

11<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


profalux<br />

Manually operated<br />

Compact with a rotary<br />

handle<br />

Locking the rotary handle<br />

E71862A<br />

Locking the direct rotary handle in all positions using a<br />

keylock<br />

b lock.<br />

E71867A<br />

E71863A<br />

E71865A<br />

1<br />

2<br />

b the controls are locked.<br />

E71758A<br />

ON<br />

OFF<br />

b unlock.<br />

2<br />

1<br />

Two types of keylocks are available<br />

RONIS<br />

PROFALUX<br />

E71810A<br />

E71811A<br />

12<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


eset<br />

reset<br />

tripped<br />

tripped<br />

reset<br />

reset<br />

tripped<br />

tripped<br />

Door locking when the device is in the ON position, using the<br />

extended rotary handle<br />

b in the standard configuration, the door cannot be opened when the rotary handle<br />

is set <strong>to</strong> the ON position.<br />

E71869A E71872A<br />

E71870A<br />

OFF<br />

2<br />

1<br />

3<br />

ON<br />

OK<br />

b it is possible, however, <strong>to</strong> defeat the door lock.<br />

4<br />

E71871A<br />

E71873A<br />

ON<br />

5 ON<br />

OK<br />

b the door-lock function may be permanently disabled by removing the lock.<br />

13<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Remote operated Compact<br />

Components<br />

E89313A<br />

MX opening voltage release<br />

or MN undervoltage release<br />

Fixed device<br />

SD trip-indication contact<br />

OF ON/OFF indication contacts<br />

SDE fault-trip indication contact<br />

Charging handle for<br />

the closing order<br />

Control auxiliary terminals<br />

Mo<strong>to</strong>r mechanism<br />

Locking in the OFF position<br />

using a padlock<br />

Locking in the OFF position<br />

using a keylock and a padlock<br />

Control unit<br />

ON but<strong>to</strong>n<br />

OFF but<strong>to</strong>n<br />

Operation counter<br />

Front<br />

E89314A<br />

Trip indication but<strong>to</strong>n used<br />

<strong>to</strong> reset before closing<br />

RESET<br />

Rating plate<br />

Locking by padlock, lead-seal cover<br />

or screws for pushbut<strong>to</strong>ns<br />

Indica<strong>to</strong>r for position<br />

of the main contacts<br />

Closing spring status indica<strong>to</strong>r<br />

14<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Opening, closing, reset<br />

E71885A<br />

MERLIN GERIN<br />

Local opening and closing<br />

Device open (OFF),<br />

discharged<br />

Device closed (ON),<br />

discharged<br />

E60405A<br />

O I<br />

Push OFF<br />

Push ON<br />

E60404A<br />

O I<br />

Push OFF<br />

Push ON<br />

Device open (OFF),<br />

charged<br />

Device closed (ON),<br />

charged<br />

E71759A<br />

E71877A<br />

O I<br />

Push OFF<br />

Push ON<br />

E71876A<br />

O I<br />

Push OFF<br />

Push ON<br />

15<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Remote operated Compact<br />

Opening, closing, reset<br />

E71760A<br />

Remote opening<br />

Use either:<br />

b an MX opening release<br />

b an MN undervoltage release<br />

b a delayed MN undervoltage release<br />

b a mo<strong>to</strong>r mechanism.<br />

When connected <strong>to</strong> the control panel, these releases may be used <strong>to</strong> remotely<br />

open the device.<br />

MX, MN<br />

Delay unit<br />

E71805A<br />

E71806A<br />

1 2 3<br />

4 5 6<br />

3 6<br />

MN<br />

UVR<br />

100/130 V<br />

AC/DC<br />

1012<br />

S<br />

0.5 1<br />

3 1.5<br />

Retardateur de MN<br />

Time delay for UVR<br />

1 2 3<br />

Mo<strong>to</strong>r mechanism<br />

E71880A<br />

E71805A<br />

E71760A<br />

Remotely close<br />

Mo<strong>to</strong>r mechanism<br />

E71880A<br />

E71805A<br />

E71805A<br />

E71805A<br />

16<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Manually recharge the device following a trip<br />

E71759A<br />

b the device trips.<br />

E71886A<br />

MERLIN GERIN<br />

CLAC !<br />

E71878A<br />

O I<br />

Push OFF<br />

Push ON<br />

E71887A<br />

b reset the device, then recharge it.<br />

E71879A<br />

MERLIN GERIN<br />

or<br />

17<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

Remote operated Compact<br />

Locking the controls<br />

Disabling local or remote closing<br />

E71888A<br />

Locking the device using one <strong>to</strong> three padlocks<br />

(shackle diameter 5 <strong>to</strong> 8 mm)<br />

b lock.<br />

Open the device.<br />

Pull out the tab.<br />

Install the padlock(s).<br />

E71807A<br />

I<br />

Push ON<br />

E71808A<br />

E60403A<br />

Push<br />

b the controls are locked.<br />

Push<br />

b unlock.<br />

E60402A<br />

E71889A<br />

b push in the tab.<br />

E71761A<br />

Note:<br />

Padlocks and keylocks may be used <strong>to</strong>gether.<br />

18<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

E71802A<br />

Locking the device using a keylock and/or one <strong>to</strong> three<br />

padlocks (shackle diameter 5 <strong>to</strong> 8 mm)<br />

b keylocking.<br />

Open the device.<br />

Turn the key.<br />

Remove the key.<br />

E71807A<br />

I<br />

Push ON<br />

E60401A<br />

E60400A<br />

Push<br />

Padlocks and keylocks may be used<br />

<strong>to</strong>gether.<br />

Locking using padlocks is identical <strong>to</strong> the<br />

system on the previous page.<br />

b the controls are locked.<br />

E71889A<br />

Push<br />

b unlock.<br />

Insert the key.<br />

Turn the key.<br />

Push in the tab.<br />

Two types of keylocks are available<br />

RONIS<br />

PROFALUX<br />

E71810A<br />

E71811A<br />

E60399A<br />

E71800A<br />

E71801A<br />

19<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

Compact chassis<br />

Components<br />

E89315A<br />

Carriage switch terminals<br />

ON/OFF indication contact terminals<br />

Control auxiliary terminals<br />

Arc-chute cover<br />

Auxiliary terminal shield<br />

Terminals for control-unit<br />

and fault-trip indication<br />

contacts<br />

Carriage switch terminals<br />

Racking interlock<br />

Carrying grip<br />

Mismatch protection<br />

Door interlock<br />

Locking by keylocks<br />

Locking by padlocks<br />

"Connected", "test" or "disconnected" position indica<strong>to</strong>r<br />

Crank socket<br />

Position release but<strong>to</strong>n<br />

Crank s<strong>to</strong>rage<br />

Crank<br />

Disconnecting-contact cluster<br />

Withdraw grip<br />

Shutter locking blocks<br />

Safety shutters<br />

MERLIN GERIN<br />

Side plate for<br />

withdrawable<br />

device<br />

Manually operated device<br />

with a rotary handle<br />

Manually operated<br />

device with a <strong>to</strong>ggle<br />

<strong>Electric</strong>ally operated device<br />

20<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Matching a device with its chassis<br />

To set up a mismatch-prevention<br />

combination for the device and the chassis,<br />

see the mismatch-prevention installation<br />

manual.<br />

E60408A<br />

The mismatch protection ensures that a device is installed only in a chassis with<br />

compatible characteristics.<br />

The possible combinations are listed below.<br />

2<br />

4<br />

1<br />

3<br />

5<br />

A<br />

B<br />

C<br />

D<br />

E<br />

A B C<br />

A B D<br />

A B E<br />

A B<br />

A C D<br />

A C E<br />

A C<br />

A D E<br />

A D<br />

A E<br />

4 5<br />

3 5<br />

3 4<br />

3 4 5<br />

2 5<br />

2 4<br />

2 4 5<br />

2 3<br />

2 3 5<br />

2 3 4<br />

B C D<br />

B C E<br />

B C<br />

B D E<br />

B D<br />

B E<br />

C D E<br />

C D<br />

C E<br />

D E<br />

1 5<br />

1 4<br />

1 4 5<br />

1 3<br />

1 3 5<br />

1 3 4<br />

1 2<br />

1 2 5<br />

1 2 4<br />

1 2 3<br />

21<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push O F<br />

O OFF<br />

push ON<br />

discharged<br />

push O F<br />

O OFF<br />

push ON<br />

discharged<br />

push O F<br />

O OFF<br />

push ON<br />

discharged<br />

Compact chassis<br />

Racking<br />

For complete information on Compact<br />

handling and mounting, see the installation<br />

manual(s).<br />

Removing the rails<br />

Press the release tabs and<br />

pull the rails out.<br />

To put the rails back in, press the<br />

release tabs and push the rails in.<br />

Before mounting Compact NS, make sure<br />

it matches the chassis.<br />

E71813A<br />

1<br />

E71814A<br />

2<br />

3<br />

Inserting the device<br />

Open the circuit breaker<br />

(in any case, it opens<br />

au<strong>to</strong>matically during<br />

connection).<br />

Position the circuit breaker on the rails.<br />

Check that it rests on all four supports.<br />

E71807A<br />

E60412A<br />

If you cannot insert the device in the<br />

chassis, check that the mismatch protection<br />

on the chassis corresponds<br />

<strong>to</strong> that on the device.<br />

Push the device in<strong>to</strong> the chassis, taking care not <strong>to</strong> push on the control unit.<br />

E60411A<br />

E60410A<br />

I<br />

Push ON<br />

Push<br />

MERLIN GERIN<br />

O<br />

I<br />

O<br />

I<br />

E60409A<br />

O<br />

I<br />

22<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Racking<br />

Prerequisites<br />

To connect and disconnect the device,<br />

the crank must be used.<br />

The locking systems, padlocks and the<br />

racking interlock all inhibit use of the crank.<br />

Racking the circuit breaker from the "disconnected" <strong>to</strong> "test"<br />

position, then <strong>to</strong> "connected" position<br />

The device is in "disconnected" position.<br />

DB110366A<br />

The indica<strong>to</strong>r on the front signals the position of the circuit breaker in the chassis.<br />

E71815A<br />

The device is in "test" position.<br />

The device is in "test" position.<br />

Remove the crank or continue <strong>to</strong><br />

"connected" position.<br />

b"connected" position<br />

E60413A<br />

Test<br />

The device is in "connected" position.<br />

E60414A<br />

b"test" position<br />

DB110365<br />

Withdrawing the circuit breaker from the "connected"<br />

<strong>to</strong> "test" position, then <strong>to</strong> "disconnected" position<br />

The circuit breaker is in "connected" position.<br />

Test<br />

b "disconnected" position<br />

E60415A<br />

Test<br />

The circuit breaker is in "test" position.<br />

The circuit breaker is in "test" position.<br />

Remove the crank or continue <strong>to</strong><br />

"disconnected" position.<br />

Note:<br />

These operations require that all chassis-locking<br />

functions be disabled (see page 24).<br />

The circuit breaker is in "disconnected" position.<br />

23<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Compact chassis<br />

Locking in the "disconnected"<br />

position<br />

Using one <strong>to</strong> three padlocks<br />

Combination of locking systems.<br />

It is possible <strong>to</strong> lock the device on the<br />

chassis in the "disconnected" position<br />

using:<br />

b one <strong>to</strong> three padlocks<br />

b one or two keylocks<br />

b a combination of both.<br />

E71816A<br />

Locking<br />

Use padlocks with a maximum shackle diameter of 5 <strong>to</strong> 8 millimetres.<br />

Device in "disconnected"<br />

position.<br />

Pull out the tab.<br />

1 2<br />

E71817A<br />

Test<br />

Insert the shackle<br />

(max. diameter 5 <strong>to</strong> 8 mm)<br />

of the padlock(s).<br />

The crank cannot be inserted.<br />

E71818A<br />

3 4<br />

E71819A<br />

Unlocking<br />

Remove the padlock(s).<br />

Release the tab.<br />

E71820A<br />

1<br />

E71821A<br />

2<br />

The crank can be inserted.<br />

E71822A<br />

3<br />

Note:<br />

Padlocks and keylocks may be used <strong>to</strong>gether.<br />

If specified when ordering the chassis, this locking<br />

function may be adapted <strong>to</strong> operate in all positions<br />

("connected", "test" and "disconnected"), instead of in<br />

"disconnected" position alone.<br />

24<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Using one or two keylocks<br />

Locking<br />

Device in "disconnected"<br />

position.<br />

Turn the key(s).<br />

E71823A<br />

1<br />

E71824A<br />

2<br />

Test<br />

Remove the key(s).<br />

The crank cannot be<br />

inserted.<br />

E71825A<br />

3<br />

E71826A<br />

Unlocking<br />

Insert the key(s).<br />

Turn the key(s).<br />

The crank can be inserted.<br />

E71827A<br />

Three types of keylocks are available.<br />

RONIS<br />

PROFALUX<br />

CASTELL<br />

E71810A<br />

E71811A<br />

E71812A<br />

1 2<br />

E71828A<br />

E71829A<br />

3<br />

25<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


O<br />

push ON<br />

push O F<br />

O O F<br />

I<br />

push ON<br />

discharged<br />

Compact chassis<br />

Locking the switchboard door<br />

The locking device is installed on the left or right-hand side of the chassis.<br />

b when the device is in "connected" or "test" position, the latch is lowered and the<br />

door is locked.<br />

b when the device is in "disconnected" position, the latch is raised and the door is<br />

unlocked.<br />

Disabling door opening<br />

Enabling door opening<br />

Turn the crank until the<br />

device is in<br />

"disconnected" position.<br />

The door is unlocked.<br />

E71834A<br />

E71835A<br />

E71831A<br />

E71832A<br />

E71833A<br />

E71830A<br />

O<br />

push OFF<br />

O OFF<br />

O<br />

push OFF<br />

I<br />

discharged<br />

O OFF<br />

Close the door.<br />

Turn the crank until the<br />

device is in "test" or<br />

"connected" position.<br />

The door is locked.<br />

26<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


O<br />

push O F<br />

O O F<br />

I<br />

push ON<br />

discharged<br />

Locking the device when the door<br />

is open<br />

E71836A<br />

O<br />

push OFF<br />

I<br />

push ON<br />

discharged<br />

O OFF<br />

When the door is open,<br />

the crank cannot be inserted.<br />

When the door is closed,<br />

the crank can be inserted.<br />

E71837A<br />

E71838A<br />

27<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Compact chassis<br />

Locking the safety shutters<br />

Four locking possibilities inside the chassis using one or two<br />

padlocks (maximum shackle diameter 5 <strong>to</strong> 8 mm) for each shutter<br />

Top and bot<strong>to</strong>m shutters not<br />

locked.<br />

Top shutter not locked.<br />

Bot<strong>to</strong>m shutter locked.<br />

E71840A<br />

E71839A<br />

Top shutter locked.<br />

Bot<strong>to</strong>m shutter not locked.<br />

Top and bot<strong>to</strong>m shutters locked.<br />

28<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


29<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


<strong>Electric</strong>al auxiliaries<br />

<strong>Electric</strong>al diagrams<br />

Fixed and withdrawable devices<br />

The diagram is shown with circuits<br />

de-energised, all devices open, connected<br />

and charged and relays in normal position.<br />

Power<br />

Control unit<br />

Remote operation<br />

DB112769<br />

E71765A<br />

AT<br />

BPO<br />

BPF<br />

D2<br />

MN<br />

MX<br />

D1<br />

C11<br />

A1<br />

C2<br />

A4<br />

A2<br />

A3<br />

(4)<br />

(3)<br />

Control unit<br />

Com UC1 UC2 UC3 M6C<br />

Remote operation<br />

CAF2 / CAF1 SDE SD<br />

E5 E6 Z5 M1 M2 M3 F2+ Q3<br />

D2 / C12 A4 A2<br />

E3 E4 Z3 Z4 T3 T4 VN Q2<br />

B4<br />

E1 E2 Z1 Z2 T1 T2 F1 – Q1<br />

D1 / C11 A1<br />

A<br />

P<br />

Control unit<br />

Remote operation<br />

b<br />

b<br />

Com: E1-E6 communication<br />

SDE : Fault-trip indication contact (supplied as standard)<br />

b<br />

b<br />

b<br />

b<br />

UC1 :<br />

Z1-Z5 zone selective interlocking;<br />

Z1 = ZSI = ZSI OUT SOURCE<br />

Z2 = ZSI OUT; Z3 = ZSI IN SOURCE<br />

Z4 = ZSI IN ST (short time)<br />

Z5 = ZSI IN GF (ground fault)<br />

M1 = Vigi module input (Micrologic 7)<br />

SD : Trip-indication contact (supplied as standard)<br />

MN : Undervoltage release<br />

or<br />

MX : Shunt release (standard or communicating)<br />

b<br />

b<br />

b<br />

b<br />

b<br />

b<br />

b<br />

b<br />

UC2 : T1, T2, T3, T4 = external neutral;<br />

M2, M3 = Vigi module input<br />

(Micrologic 7)<br />

UC3 : F2+, F1- external 24 V DC power<br />

supply VN external voltage connec<strong>to</strong>r<br />

(must be connected <strong>to</strong> neutral with<br />

circuit breaker 3P)<br />

M6C : 6 programmable contacts (must be<br />

connected <strong>to</strong> external relay M6C)<br />

ext. 24 V DC power supply required<br />

A: Digital ammeter<br />

P: A + power meter + programmable protection<br />

30<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Indication contacts<br />

Chassis contacts<br />

E89316A<br />

Open<br />

Closed<br />

Default<br />

Default<br />

Closed<br />

Open<br />

E89317A<br />

Disconnected Connected Test<br />

541<br />

531<br />

542<br />

544<br />

532<br />

534<br />

522<br />

524<br />

512<br />

514<br />

SD<br />

CAF2<br />

CAF1<br />

CAO2<br />

CAO1<br />

21<br />

11<br />

81<br />

91<br />

521<br />

511<br />

32<br />

34<br />

22<br />

24<br />

12<br />

14<br />

82<br />

84<br />

92<br />

94<br />

OF3 OF2 OF1 SDE<br />

31<br />

821<br />

822<br />

824<br />

812<br />

814<br />

CD2<br />

CD1<br />

811<br />

331<br />

332<br />

334<br />

CE3<br />

321<br />

322<br />

324<br />

CE2<br />

311<br />

312<br />

314<br />

914<br />

912<br />

CT1<br />

CE1<br />

911<br />

Indication contacts<br />

CAF1CAF2 SDE SD CAO2 CAO1 OF3 OF2 OF1<br />

544 534 84 94 544 514 34 24 14<br />

542 532 82 92 522 512 32 22 12<br />

542 531 81 91 521 511 31 21 11<br />

Chassis contacts<br />

CD2 CD1 CE3 CE2 CE1 CT1<br />

824 814 334 324 314 914<br />

822 812 332 322 312 912<br />

821 811 331 321 311 911<br />

Indication contacts<br />

OF3 / OF2 / OF1: ON/OFF indication contacts<br />

Chassis contacts<br />

CD2: Disconnected-<br />

CD1 position<br />

contacts<br />

CE3: Connected-<br />

CE2 position<br />

CE1 contacts<br />

CT1: Test-position<br />

contacts<br />

Key:<br />

XXX<br />

Withdrawable device only<br />

SDE1, OF1, OF2, OF3, OF4 supplied as standard<br />

Interconnected connections<br />

(only one wire per connection point)<br />

31<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


<strong>Electric</strong>al auxiliaries<br />

Operation<br />

The ON/OFF indication contacts signal<br />

the status of the device main contacts.<br />

Device<br />

E89318A<br />

completely closed<br />

completely open<br />

closed<br />

open<br />

main contacts<br />

open<br />

closed<br />

closed<br />

open<br />

OF: ON/OFF (closed/open) indication<br />

changeover contacts<br />

The carriage switches indicate the<br />

"connected", "test" and "disconnected"<br />

positions.<br />

Chassis<br />

E89319A<br />

completely connected<br />

separation of the main circuits<br />

test position<br />

separation of the auxiliary circuits<br />

completely disconnected<br />

open<br />

closed<br />

CE: connected-position<br />

carriage switch contact<br />

open<br />

closed<br />

closed<br />

open<br />

open<br />

closed<br />

CT: test-position carriage<br />

switch contact<br />

open<br />

closed<br />

CD: disconnected-position<br />

carriage switch contact<br />

32<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


<strong>Electric</strong>al characteristics of<br />

contacts and control auxiliaries<br />

Device indication contacts<br />

designation type standard, minimum current 100 mA 24 V low level, minimum current 2 mA 15 V<br />

OF ON/OFF contact 3 changeover contacts V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />

breaking capacity 480 6 A (rms) 240 5 A (rms)<br />

(AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />

947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />

125 0.5 A 125 0.5 A<br />

250 0.3 A 250 0.3 A<br />

SD fault indication 1 changeover contact V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />

breaking capacity 480 6 A (rms) 240 5 A (rms)<br />

(AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />

947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />

125 0.5 A 125 0.5 A<br />

250 0.3 A 250 0.3 A<br />

SDE fault-trip indication 1 changeover contact V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />

for device with mo<strong>to</strong>r breaking capacity 480 6 A (rms) 240 5 A (rms)<br />

mechanism (AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />

947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />

125 0.5 A 125 0.5 A<br />

250 0.3 A 250 0.3 A<br />

CAO early-break switch 2 changeover contacts V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />

for device with rotary breaking capacity 480 6 A (rms) 240 5 A (rms)<br />

handle (AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />

947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />

125 0.5 A 125 0.5 A<br />

250 0.3 A 250 0.3 A<br />

CAF early-make switch 2 changeover contacts V AC 240/380 6 A (rms) V AC 24/48 5 A (rms)<br />

for device with rotary breaking capacity 480 6 A (rms) 240 5 A (rms)<br />

handle (AC 12 / DC 12 as per 690 6 A (rms) 380 5 A (rms)<br />

947-5-1) V DC 24/48 2.5 A V DC 24/48 5 / 2.5 A<br />

125 0.5 A 125 0.5 A<br />

250 0.3 A 250 0.3 A<br />

Device control auxiliaries<br />

designation power supply threshold consumption response time<br />

MX opening release V AC: 50/60 Hz: 24/48 - 0.7 <strong>to</strong> 1.1 Un pick-up: 200 VA or W (80 ms) device at Un:<br />

100/130 - 200/250 - 277 - hold: 4.5 VA or W 50 ms ± 10<br />

380/480<br />

V DC: 12 - 24/30 - 48/60 -<br />

100/130 - 200/250<br />

MN undervoltage release V AC: 50/60 Hz: 24/48 - open: pick-up: 200 VA or W (80 ms) device at Un:<br />

100/130 - 200/250 - 0.35 <strong>to</strong> 0.7 Un hold: 4.5 VA or W 40 ms ± 10<br />

380/480 close: 0.85 Un<br />

V DC: 24/30 - 48/60 -<br />

100/130 - 200/250<br />

Delay unit for undervoltage V AC: 50/60 Hz open: 200 VA device at Un:<br />

release V DC not adjustable: 0.35 <strong>to</strong> 0.7 Un not adjustable:<br />

100/130 - 200/250 close: 0.85 Un 0.25 s<br />

V DC adjustable:<br />

adjustable:<br />

48/60 - 100/130 - 0.5 - 0.9 - 1.5 - 3 s<br />

200/250 - 380/480<br />

Mo<strong>to</strong>r mechanism<br />

designation power supply threshold consumption and recharge time and<br />

mo<strong>to</strong>r overcurrent operating rate<br />

Mo<strong>to</strong>r mechanism V AC: 50/60 Hz: 48/60 - 0.85 <strong>to</strong> 1.1 Un consumption: 180 VA or W 3 seconds max.<br />

100/130 - 200/240 - 277 - overcurrent: 2 <strong>to</strong> 3 In for 0.1 s 3 cycles per minute<br />

400/440 - 480<br />

V DC: 24/30 - 48/60 -<br />

100/125 - 200/250<br />

"Connected", "test" and "disconnected" position carriage switches<br />

designation type standard, minimum current 100 mA 24 V low level, minimum current 2 mA 15 V<br />

CE, CT, CD 3 changeover contacts V AC 240 8 A (rms) V AC 24/48 5 A (rms)<br />

breaking capacity 380 8 A (rms) 240 5 A (rms)<br />

(AC 12 / DC 12 as per 480 8 A (rms) 380 5 A (rms)<br />

947-5-1) 690 6 A (rms)<br />

V DC 24/48 2.5 A V DC 24/48 2.5 A<br />

125 0.8 A 125 0.8 A<br />

250 0.3 A 250 0.3 A<br />

33<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


<strong>Electric</strong>al auxiliaries<br />

<strong>Electric</strong>al characteristics of<br />

contacts and control auxiliaries<br />

Wiring of control auxiliaries<br />

Under pick-up conditions, the level of consumption is approximately 150 <strong>to</strong> 200 VA.<br />

Consequently, for low supply voltages (12, 24, 48 V), cables must not exceed a<br />

maximum length determined by the supply voltage and the cross-section<br />

of the cables.<br />

Indicative values for maximum cable lengths (in meters)<br />

12 V 24 V 48 V<br />

2.5 mm 2 1.5 mm 2 2.5 mm 2 1.5 mm 2 2.5 mm 2 1.5 mm 2<br />

MN 100% source<br />

voltage — — 58 36 280 165<br />

85% source<br />

voltage — — 16 10 75 45<br />

MX-XF 100% source<br />

voltage 21 12 115 70 550 330<br />

85% source<br />

voltage 10 6 75 44 350 210<br />

Note:<br />

The indicated length is that for each of the two supply wires.<br />

34<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


35<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


Start-up<br />

Start-up operations<br />

Procedure<br />

These operations must be carried out<br />

before using a device for the first time.<br />

A general check of the device takes only a few minutes and avoids any risk of<br />

mistakes due <strong>to</strong> errors or negligence.<br />

A general check must be carried out:<br />

b prior <strong>to</strong> initial use<br />

b following an extended period during which the device is not used.<br />

A check must be carried out with the entire switchboard de-energised.<br />

In switchboards with compartments, only those compartments that may be<br />

accessed by the opera<strong>to</strong>rs must be de-energised.<br />

<strong>Electric</strong>al tests<br />

Insulation and dielectric-withstand tests must be carried out immediately after<br />

delivery of the switchboard. These tests are precisely defined by international<br />

standards and must be directed and carried out by a qualified expert.<br />

Prior <strong>to</strong> running the tests, it is absolutely necessary <strong>to</strong>:<br />

b disconnect all the electrical auxiliaries of the device (MCH, MX, MN)<br />

b remove the long-time rating plug on the 7.0 A control units.<br />

Removal of the rating plug disconnects the voltage measurement input.<br />

Switchboard inspection<br />

Check that the devices are installed in a clean environment, free of any installation<br />

scrap or items (<strong>to</strong>ols, electrical wires, broken parts or shreds, metal objects, etc.).<br />

Conformity with the installation diagram<br />

Check that the devices conform with the installation diagram:<br />

b breaking capacities indicated on the rating plates<br />

b identification of the control unit (type, rating)<br />

b presence of any optional functions (mo<strong>to</strong>r mechanism)<br />

b protection settings (long time, short time, instantaneous, ground fault)<br />

b identification of the protected circuit marked on the front of each device.<br />

Condition of connections and auxiliaries<br />

Check device mounting in the switchboard and the tightness of power connections.<br />

Check that all auxiliaries and accessories are correctly installed:<br />

b electrical auxiliaries<br />

b terminal blocks<br />

b connections of auxiliary circuits.<br />

Operation<br />

Check the mechanical operation of the devices:<br />

b opening of contacts<br />

b closing of contacts.<br />

Check on the control unit<br />

Check the control unit of each circuit breaker using the respective user manuals.<br />

36<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


What <strong>to</strong> do when the circuit<br />

breaker trips?<br />

Note the fault<br />

Faults are signalled locally and remotely by the indica<strong>to</strong>rs and auxiliary contacts<br />

installed on devices (depending on each configuration). See page 32 in this manual<br />

and the user manual of the control unit for information on the fault indications<br />

available with your circuit breaker.<br />

Identify the cause of tripping<br />

A circuit must never be reclosed (locally or remotely) before the cause of the fault<br />

has been identified and cleared.<br />

Depending on the type of fault and the criticality of the loads, a number of<br />

precautionary measures must be taken, in particular the insulation and dielectric<br />

tests on a part of or the entire installation. These checks and test must be directed<br />

and carried out by qualified personnel.<br />

Inspect the circuit breaker following a short-circuit<br />

b check the tightness of connections (see the device installation manual)<br />

b check the disconnecting-contact clusters.<br />

Reset the circuit breaker<br />

The circuit breaker can be reset locally or remotely. See pages 5, 9 and 15<br />

in this manual for information on how the device can be reset.<br />

37<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

push<br />

<strong>to</strong><br />

trip<br />

Compact operating<br />

conditions<br />

E60418A E60417A<br />

E60416A<br />

Ambient temperature<br />

Compact devices can operate under the following temperature conditions:<br />

b the electrical and mechanical characteristics are stipulated for an ambient<br />

temperature of -5° C <strong>to</strong> +70° C<br />

b circuit-breaker closing is guaranteed down <strong>to</strong> -35° C<br />

b Compact (without the control unit) can be s<strong>to</strong>red in an ambient temperature<br />

of -40° C <strong>to</strong> +85° C<br />

b the control unit can be s<strong>to</strong>red in an ambient temperature of -25° C <strong>to</strong> +85° C.<br />

Extreme atmospheric conditions<br />

Compact devices have successfully passed the tests defined by the following<br />

standards for extreme atmospheric conditions:<br />

b IEC 68-2-1: dry cold at -55° C<br />

b IEC 68-2-2: dry heat at +85° C<br />

b IEC 68-2-30: damp heat (temperature +55° C, relative humidity 95%)<br />

b IEC 68-2-52 level 2: salt mist.<br />

Compact devices can operate in the industrial environments defined by standard<br />

IEC 947 (pollution degree up <strong>to</strong> 3).<br />

It is nonetheless advised <strong>to</strong> check that the devices are installed in suitably cooled<br />

switchboards without excessive dust.<br />

Vibrations<br />

Compact devices resist electromagnetic or mechanical vibrations.<br />

Tests are carried out in compliance with standard IEC 68-2-6 for the levels required<br />

by merchant-marine inspection organisations (Veritas, Lloyd's, etc.):<br />

b 2 <strong>to</strong> 13.2 Hz: amplitude ±1 mm<br />

b 13.2 <strong>to</strong> 100 Hz: constant acceleration 0.7 g.<br />

Excessive vibration may cause tripping, breaks in connections or damage <strong>to</strong><br />

mechanical parts.<br />

38<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


push<br />

<strong>to</strong><br />

trip<br />

E60420A<br />

Electromagnetic disturbances<br />

Compact devices are protected against:<br />

v overvoltages caused by devices that generate electromagnetic disturbances<br />

v overvoltages caused by an atmospheric disturbance or by a distribution-system<br />

outage (e.g. failure of a lighting system)<br />

v devices emitting radio waves (radios, walkie-talkies, radar, etc.)<br />

v electrostatic discharges produced by users.<br />

Compact devices have successfully passed the electromagnetic-compatibility tests<br />

(EMC) defined by the following international standards:<br />

b IEC 947-2, appendix F<br />

b IEC 947-2, appendix B (trip units with earth-leakage function).<br />

The above tests guarantee that:<br />

b no nuisance tripping occurs<br />

b tripping times are respected.<br />

Cleaning<br />

v non-metallic parts:<br />

never use solvent, soap or any other cleaning product. Clean with a dry cloth only<br />

v metal parts:<br />

clean with a dry cloth whenever possible. If solvent, soap or any other cleaning<br />

product must be used, make sure that it does not come in<strong>to</strong> contact with<br />

non-metallic parts.<br />

39<br />

Compact NS<br />

<strong>Schneider</strong> <strong>Electric</strong>


<strong>Schneider</strong> <strong>Electric</strong> Industries SAS<br />

5, rue Nadar<br />

92506 Rueil-Malmaison Cedex<br />

France<br />

Tel: +33 (0)1 41 29 82 00<br />

Fax:+33 (0)1 47 51 80 20<br />

http://www.schneider-electric.com<br />

http://www.merlin-gerin.com<br />

As standards, specifications and designs develop from time, always ask for confirmation of the<br />

information given in this publication.<br />

Printed on recycled paper<br />

Designed by: SEDOC<br />

Pho<strong>to</strong>s: <strong>Schneider</strong><br />

Printed by:<br />

51201640AA-C1 11-2006