Installation and Set Up<br />

Mounting the <strong>SVI</strong> <strong>II</strong> AP on Rotary Valves<br />

Figure 7<br />

Model 33 Actuator<br />

Rotary - 90 Degree<br />

For actuators with 60 to 120 degrees rotation, follow the instructions in<br />

“Mounting the <strong>SVI</strong> <strong>II</strong> AP on Rotary Valves” on page 10 except mount the<br />

magnet at plus or minus 45 degrees while the actuator de-energized as<br />

shown in Figure 7 on page 13.<br />

Magnet Orientation on Rotary Valve Shafts<br />

The same mounting hardware is used for Models 35, 30 actuators. For each<br />

actuator type the magnetic coupling must be properly oriented to the active<br />

sensing angle of the positioners Hall Effect sensor. The active range of the<br />

Hall-Effect sensor is plus⁄minus 70 degrees from the null magnet axis. If the<br />

total valve travel is less than 60 degrees, allowing a margin for tolerances, the<br />

best accuracy is achieved by mounting the magnet with the axis vertical in the<br />

valve-closed position. Note the location of the magnets in the ring of the<br />

magnet holder. The axis of the magnets is the line through the centers of both<br />

magnets. Mount the magnet holder with the magnet axis vertical on the 35, 30<br />

when the valve is closed. If travel of the valve exceeds 60 degrees, the<br />

magnet must be assembled to the rotary valve shaft so that the magnet axis is<br />

vertical when the valve is at mid-scale.<br />

Dismantling the <strong>SVI</strong> <strong>II</strong> AP from Rotary Valves<br />

Before carrying out any work on the device, power off the instrument or make<br />

sure that the device’s location conditions for potentially explosive atmosphere<br />

permit the safe opening of the cover.<br />

To remove the <strong>SVI</strong> <strong>II</strong> AP positioner from a rotary valve perform Steps 1 - 8 on<br />

page 7 in reverse.<br />