<strong>BSK</strong>-R-M AND <strong>BSK</strong>-R-L CIRCULAR <strong>FIRE</strong> <strong>DAMPERS</strong> PAGE 2<br />

Airtight for <strong>90</strong> minutes<br />

Fire dampers represent safety equipment<br />

that must reliably prevent the spreading<br />

of fire and smoke in ventilation and airconditioning<br />

systems. They are installed<br />

inside air ducts where they enter fire<br />

zones and must have at least the same<br />

fire resistance period as the fire zone<br />

entered.<br />

PICHLER fire dampers with the European<br />

classification <strong>EI</strong> <strong>90</strong> (v , h , i < - > o) S are<br />

e o<br />

available in different lightweight and solid<br />

variants.<br />

Used for triggering is either a manual<br />

thermal trigger device at about 72°C via<br />

a soldered strut deployed outside with<br />

optional end position switches, or an<br />

electric motor-driven safety drive (spring<br />

return drive).<br />

e<br />

, h o<br />

, i < - > o) S<br />

<br />

<br />

<br />

<br />

variants<br />

<br />

<br />

<br />

pressure loss<br />

<br />

<br />

free operation<br />

<br />

lightweight walls (metal stud partitions)<br />

<br />

of the fire dampers flap<br />

<br />

<br />

<br />

<br />

<br />

MODEL<br />

<strong>BSK</strong>-R-L<br />

DESCRIPTION<br />

Model <strong>BSK</strong>-R-L fire dampers essentially comprise a zinc-plated sheet steel housing, a flap body made of calcium silicate, an<br />

integrated lip-seal for the cold smoke, an intumescent seal all around the flap housing and a trigger mechanism (either thermal/<br />

manual or motor-driven triggering of the sealing element). The fire dampers are available with diameters ø 100 mm to ø 315 mm.<br />

<strong>BSK</strong>-R-M<br />

Model <strong>BSK</strong>-R-M fire dampers essentially comprise a zinc-plated sheet steel housing, a flap body made of calcium silicate, an<br />

integrated lip-seal for the cold smoke, an intumescent seal all around the flap housing and a trigger mechanism (either thermal/<br />

manual or motor-driven triggering of the sealing element). The fire dampers are available with diameters ø 355 mm to ø 630 mm.<br />

<strong>BSK</strong>-E-L<br />

Rectangular <strong>BSK</strong>-E-L fire dampers essentially comprise a non-combustible housing, zinc-plated sheet steel connection flanges, a flap<br />

body made of calcium silicate, an integrated lip-seal for the cold smoke, an intumescent seal all around the flap housing and a trigger<br />

mechanism (either thermal/manual or motor-driven triggering of the sealing element). The fire dampers are available with dimensions<br />

200 x 100 mm (minimum) to 800 x 600 mm (maximum).<br />

<strong>BSK</strong>-E-M<br />

Rectangular <strong>BSK</strong>-E-M fire dampers essentially comprise a non-combustible housing made of calcium silicate plates, zinc-plated sheet<br />

steel connection flanges, a flap body made of calcium silicate, an integrated seal for the cold smoke, an intumescent seal all around the<br />

flap housing and a trigger mechanism (either thermal/manual or motor-driven triggering of the sealing element). The fire dampers are<br />

available with dimensions 200 x 200 mm (minimum) to 1500 x 800 mm (maximum).<br />

Also possible with this flap model is the ability to supply combinations of a maximum of 4 individual of model <strong>BSK</strong>-E-MK with maximum<br />

dimensions of 2450 x 1650 mm for wall installation. Fire dampers combined this way may only be used in solid walls, in the horizontal<br />

axis position.