KX4 heat pump systems 18, 20, 22, 24hp<br />

(50.4kW – 68.0kW)<br />

Model No.<br />

FDCA504HKXE4BR<br />

FDCA560HKXE4BR<br />

FDCA615HKXE4BR<br />

FDCA680HKXE4BR<br />

Nominal Cooling Capacity<br />

50.4kW<br />

56.0kW<br />

61.5kW<br />

68.0kW<br />

• The KX4 heat pump 2-pipe systems offer high performance VRF for<br />

applications that require either cooling only or heating only, ideal<br />

for open plan areas.<br />

• Connect up to 40 indoor units/up to 130% capacity.<br />

• High efficiency with COP (in cooling) of 3.4.<br />

• KX4 employs DC inverter compressors ONLY.<br />

• Industry leading total piping length up to 510m and a maximum pipe<br />

run of 160m.<br />

Uniform footprint of all models (from<br />

8hp – 24 hp) allows continuous sideby-side<br />

installation<br />

Total length: 510m<br />

To the<br />

first branch:<br />

max 130m<br />

Outdoor unit<br />

Indoor unit<br />

Height difference<br />

50m(outdoor unit above)<br />

40m(outdoor unit below)<br />

Range of operation<br />

Summer/Winter<br />

switch included<br />

40<br />

50<br />

+43ºC DB<br />

From the first<br />

branch to the<br />

furthest indoor<br />

unit: 40m<br />

Furthest<br />

indoor unit: 160m<br />

Indoor unit<br />

Indoor unit<br />

Max height<br />

difference<br />

between<br />

indoor units:<br />

15m<br />

30<br />

20<br />

10<br />

0<br />

-10<br />

-20<br />

Cooling<br />

-5ºC DB<br />

-20ºC WB<br />

+15.5ºC WB<br />

Heating<br />

Specifications<br />

Item FDCA504HKXE4BR FDCA560HKXE4BR FDCA615HKXE4BR FDCA680HKXE4BR<br />

Nominal horse power 18HP 20HP 22HP 24HP<br />

Power source<br />

3 Phase 380-415V, 50Hz<br />

Nominal capacity<br />

Cooling<br />

50.4 56.0 61.5 68.0<br />

kW<br />

Heating 56.5 63.0 69.0 73.0<br />

UK cooling capacity kW 43.4 48.3 53.0 58.6<br />

Starting current A 8<br />

Power Cooling<br />

14.73 17.21 20.37 24.98<br />

kW<br />

Electrical characteristics consumption Heating 15.15 17.07 18.48 19.08<br />

Operating Cooling<br />

24.1/22.0 28.2/25.8 33.1/30.3 40.3/36.9<br />

A<br />

current Heating 25.2/23.1 28.5/26.1 30.7/28.1 31.6/29.0<br />

Exterior dimensions HxWxD mm 2048x1350x720<br />

Net weight kg 340 360<br />

Refrigerant charge R410A kg 19.4 21.2<br />

Noise level (cooling/heating) dB(A) 60/60.5 60.5/62.5 63/63 63.5/63.5<br />

Refrigerant piping size<br />

Liquid line<br />

ø1/2”(12.70)<br />

in (mm)<br />

Gas line ø1 1/8”(28.58)<br />

Capacity control % 11-110 10-113 9-110 8-108<br />

Number of connectable indoor units 29 33 36 40<br />