Level 3 PSA - EDF Hinkley Point
Level 3 PSA - EDF Hinkley Point
Level 3 PSA - EDF Hinkley Point
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
HPC-NNBOSL-U0-000-RES-000028 Version 1.0<br />
<strong>Level</strong> 3 <strong>PSA</strong><br />
NOT PROTECTIVELY MARKED<br />
N° Initiating Events Ass t<br />
101 Loss of RCV [CVCS] pumping. LowF<br />
102 Double ended primary guillotine break (LOCA - 2A), LowF<br />
103 Multiple steam generator tube rupture (SGTR - 20A) LowF<br />
104 Fuel assembly drop (into reactor building) TBC<br />
105 Fuel assembly mishandling (in reactor building ) LowC<br />
106 Fuelling machine fault leading to dropping of heavy items into the core leading to<br />
clad failure<br />
LowF<br />
107 Fuel element stuck in the fuel transfer mechanism LowC<br />
108 Heavy object dropped into fuel pool LowF<br />
109 Faults associated with spent resin transfer LowC<br />
110 Inadvertent discharge of liquid waste LowC<br />
111 Inadvertent discharge of gaseous waste LowC<br />
112 Dropping of solid waste package LowC<br />
113 Dropping of activated filter LowC<br />
115 Inadvertent operation of the auxiliary feed water system LowC<br />
116 Inadvertent partial cooldown to below 80 bar LowC<br />
118 RCCA Bank misalignment LowC<br />
119 Decay of frequency of off-site power system LowC<br />
120 Faults in sensors common to the control and protection system LowF<br />
121 Loss of spent fuel pool cooling TBC<br />
122 Spent fuel pool drainage TBC<br />
123 Boiling of the spent fuel pool LowC<br />
Assessment:<br />
LowC: event screened out on Low Consequence<br />
LowF: event screened out on Low Frequency<br />
TBC: event to be considered in off-site consequence assessment<br />
UNCONTROLLED WHEN PRINTED<br />
NOT PROTECTIVELY MARKED<br />
Page 40 of 60