biologic sci

cpp.ucr.edu

biologic sci

Transition Plan


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

1-Stairways: Biological

Sciences. [All stairs

should be reviewed.]

2-Stairway Handrails:

North Biological

Sciences.

3-Pedestrian Ramps:

Biological Sciences. [All

ramps should be

reviewed.]

4-Ramp Handrails:

Biological Sciences.

All steps have uniform riser height and tread

width. Stairs do not accumulate water. Ext. - Top

landing and all steps have color striping

minimum 2" wide and a maximum 4" wide

parallel to, and not more than 1" maximum from

tread nose or landing.

1-1/2" clearance provided between rail and wall.

Rails are 34" - 38" above stair nosing. Ends of

rails are rounded or returned smoothly to wall or

floor.

60" x 60" min. top landing. NOTE: When a ramp

leads directly to a door that swings out into the

top landing area the top landing must measure a

minimum 42"+ the door width. 2% maximum

slope in any direction at bottom landing.

Handrails are provided on both sides.

Handrails are on both sides and continuous the

full length of the ramp.

Install slip-resistant color

contrast striping to steps.

Requires

engineering/architectural

evaluation.

All stairs should be reviewed.

Round rails back to wall / floor.

Handrails are non-compliant

and further review is

suggested. See Sequence #1

for actions.

Requires

engineering/architectural

evaluation.

All ramp handrails should be

reviewed. See Sequence #3

(above) for action.

2 $7,380.23

2 $0.00

1 $7,115.62

1 $0.00

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

5-Doors: Main Entry

Door to Biological

Sciences. [All doors

should be reviewed.]

6-Clear Space at Doors:

Main Entry Door to

Biological Sciences. [All

door clear spaces on

exterior should be

reviewed.]

5 lb. maximum pressure to operate exterior

doors. The international symbol of accessibility

is posted at all primary entrances.

Floor or landing is level and clear (2% max.

slope).

Post a sign/decal displaying

the "International Symbol of

Accessibility" at the primary

entrance.

Install automatic door opening

device.

1 $24.51

2 $6,489.45

UCR P5186

Biological

Sciences

7-Floors and Levels:

Main Entry Door to

Biological Sciences. [All

doormats must be

secured down and all

should be reviewed or

secured.]

Carpets or carpet tiles are securely attached

and do not exceed 1/2" in height. Carpet's

exposed edges are fastened to floor surfaces

and have trim along entire length.

Secure loose doormat. 1 $245.01

5/31/2012 Page 1 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

9-Stairways: Stairway 2

at Biological Sciences.

[All stairways should be

reviewed.]

10-Stairway Handrails:

Stairway 2 at Biological

Sciences.

11-Doors: Equipment

Room CR1200C at

Biological Sciences.

[Excessive pressure. All

interior doors should be

reviewed.]

13-Protruding Objects:

Equipment Room

CR1200C at Biological

Sciences. [All areas

should be reviewed for

protruding objects.]

14-Protruding Objects:

Shelving Unit Next to

Activity Room 1224 at

Biological Sciences. [All

areas should be

reviewed for hazardous

objects.]

15-Visual/Audible

Alarms: Biologic Science

Equipment Room

Outside of Activity Room

1224. [All fire alarms

should be reviewed.]

Nosing projection is less than 1-1/4". All steps

have uniform riser height and tread width. Stairs

do not accumulate water. Int. - Top landing and

lower tread have color striping minimum 2" wide

and a maximum 4" wide parallel to, and not

more than 1" maximum from tread nose or

landing.

1-1/2" clearance provided between rail and wall.

12" minimum level extension beyond top nosing

(parallel with the ground or floor surface) before

being returned. 12" plus one tread width level

extension beyond bottom nosing (parallel with

the ground or floor surface) before being

returned.

5 lb. maximum pressure to operate interior

doors.

Objects projecting from walls (i.e. telephones,

etc.) have 4" maximum projection into walks,

halls, corridors, passageways or aisles if lower

edge of object is above 27" and below 80".

Objects projecting from walls (i.e. telephones,

etc.) have 4" maximum projection into walks,

halls, corridors, passageways or aisles if lower

edge of object is above 27" and below 80".

The appliance is placed 80" above the highest

floor level within the space or 6" below the

ceiling, whichever is lower.

Requires

engineering/architectural

evaluation.

All stairway handrails should

be reviewed. Guardrail is noncompliant

due to a gap at the

bottom. See Sequence #9 for

action.

2 $7,115.62

2 $0.00

Adjust door opening pressure /

closing time unless accepted

by DSA Fire / Life Safety.

Consider issues connected

with building pressure / climate

control.

2 $306.26

Relocate restricting object. 1 $490.00

Install cane detectable barrier

below object.

Requires

engineering/architectural

evaluation.

1 $490.00

1 $7,115.62

5/31/2012 Page 2 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

16-Sinks: Biologic

Science Room 1227 Lab

and 1226. [Provide

insulation for piping.]

17-Controls, Operating

Mechanisms & Vending

Machines.: Fume Hood

at Biologic Sciences

Room 1227 Lab and

1226. [No knee

clearance and controls

are not accessible. All

fume hoods should be

reviewed.]

34" maximum height of rim or counter above

floor surfaces. Sink is a maximum of 6-1/2"

deep. Knee clearance under sink is a minimum

of 27" high and 30" wide, and provides an

absolute depth of 19" underneath the sink

[ADAAG 606.2 Exception 6 The dip of the

overflow shall not be considered in determining

knee and toe clearance]. Drain and hot water

piping is insulated or configured to prevent

contact. 5 lb. maximum force required to

activate controls.

Side Reach to Objects: Highest operable part of

the object is a maximum of 54" above the floor

surface.

Insulate pipes under sink. Cut

the paneling under the sink

counter to comply with knee

clearance. Replace with

accessible sink.

Replace the fume hood with an

accessible fume hood work

station.

3 $3,920.09

3 $18,216.00 Until such time

as accessible

furniture /

stations are

available in this

room staff shall

be informed of

the immediate

availability of

accessible

furniture /

stations that

may be placed

in the room to

meet the needs

of people with

disabilities.

5/31/2012 Page 3 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

18-Seating, Tables and

Work Surfaces: Biologic

Sciences Room 1227

Lab and 1226. [All

accessible stations in

labs should be

reviewed.]

19-Sinks: Biologic

Sciences Room 1224

Activity Room. [Provide

insulation for piping. All

accessible sinks should

be reviewed.]

20-Seating, Tables and

Work Surfaces: Biologic

Sciences Room 1224

Activity Room. [All

seating should be

reviewed for accessible

stations.]

27" high, 30" wide and 19" deep knee clearance

provided.

Sink is a maximum of 6-1/2" deep. Knee

clearance under sink is a minimum of 27" high

and 30" wide, and provides an absolute depth of

19" underneath the sink [ADAAG 606.2

Exception 6 The dip of the overflow shall not be

considered in determining knee and toe

clearance]. Drain and hot water piping is

insulated or configured to prevent contact.

27" high, 30" wide and 19" deep knee clearance

provided.

Provide accessible table. 1M $245.01 Until such time

as accessible

furniture /

stations are

available in this

room staff shall

be informed of

the immediate

availability of

accessible

furniture /

stations that

may be placed

in the room to

meet the needs

of people with

disabilities.

Insulate pipes under sink. 3 $3,430.07

Replace with accessible sink.

Provide accessible table. 1M $245.01 Until such time

as accessible

furniture /

stations are

available in this

room staff shall

be informed of

the immediate

availability of

accessible

furniture /

stations that

may be placed

in the room to

meet the needs

of people with

disabilities.

5/31/2012 Page 4 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

21-Seating, Tables and

Work Surfaces:

Biological Safety

Cabinet at Biologic

Sciences Room 1221

Support Room. [Noncompliant

fume hood

and further review is

suggested.]

22-Protruding Objects:

Biologic Sciences Room

1219 Freezer Room. [All

areas should be

reviewed for protruding

objects.]

24-Doors: Biologic

Sciences Room 1207

Dark Room. [Door in is

non-compliant and

further review is

suggested.]

27-Water Fountains

(Drinking): Biologic

Sciences 3rd Floor Hall.

[All drinking fountains

should be reviewed.]

27" high, 30" wide and 19" deep knee clearance

provided.

Objects projecting from walls (i.e. telephones,

etc.) have 4" maximum projection into walks,

halls, corridors, passageways or aisles if lower

edge of object is above 27" and below 80".

5 lb. maximum pressure to operate interior

doors.

27" high x 8" deep clear knee space under

fountain. Stream of bubbler is parallel to front

edge. 4" minimum height of stream.

Replace the fume hood with an

accessible fume hood work

station.

Install cane detectable barrier

below object.

Adjust door opening pressure /

closing time unless accepted

by DSA Fire / Life Safety.

Consider issues connected

with building pressure / climate

control.

Raise existing drinking

fountain. Adjust water pressure

of existing fountain. Adjust

angle of stream.

3 $18,216.00 Until such time

as accessible

furniture /

stations are

available in this

room staff shall

be informed of

the immediate

availability of

accessible

furniture /

stations that

may be placed

in the room to

meet the needs

of people with

disabilities.

1 $122.51

2 $306.26

2 $1,531.28 Defer.

UCR P5186

Biological

Sciences

29-Clear Space at

Doors: Biologic

Sciences Women's

Restroom on the 3rd

Floor.

60" min. clear space in direction of door swing.

Minimum strike side clearance on PULL side of

door: 18" wide x 60" depth at interior doors, front

approach.

Install automatic door opening

device.

2 $6,489.45

5/31/2012 Page 5 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

31-Multiple

Accommodation Toilets:

Biologic Science

Women's Restroom on

the 3rd Floor. [Relocate

the paper towel

dispenser to provide

clearance of 44"

throughout restroom.]

44" min. clear path provided throughout facility.

18" betwen centerline of water closet and side

wall or partition [ADAAG 604.2 16" - 18" to

centerline of water closet].. The toilet paper

dispenser is located on the side wall below the

grab bar and within 7" - 9" of the front of the

toilet seat as measured to the centerline of the

dispenser.

Relocate water closet.

Relocate the toilet paper

dispenser away from the top of

the grab bar. Relocate the

paper towel dispenser.

3 $2,327.54

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

32-Toilet Grab Bars:

Biologic Science

Women's Restroom on

the 3rd Floor.

33-Lavatories: Biologic

Science Women's

Restroom on the 3rd

Floor.

Area directly above grab bars or proposed grab

bars is free of protruding obstructions to a height

of 18" (recessed items are allowed).

27" high x 8" deep knee clearance under front

lip. 5 lb. max. force required to operate controls.

See Sequence #31 (above) for

actions.

Raise existing multiple lavatory

counter. Reduce force needed

to operate faucet controls (5 lb.

maximum).

3 $0.00

3 $3,981.33

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

34-Accessories: Biologic

Sciences Women's

Restroom on the 3rd

Floor.

35-Doors: Biologic

Sciences Men's

Restroom on the 3rd

Floor.

37-Identification

Symbols, Restrooms:

Biologic Sciences Men's

Restroom on the 3rd

Floor.

40" max. height to all other fixtures (i.e., soap

dispensers, towels, toilet seat covers, auto

dryers, sanitary napkins, waste recepatacles,

etc.).

5 lb. maximum pressure to operate interior

doors.

Wall mounted signage: Symbol of accessibility is

mounted on wall sign adjacent to latch side of

door [ADAAG 703.6.1 & CBC 1117B.5.5 Item 4

Pictograms shall have a field height of 6"

ADAAG 703.6.1 Characters and Braille shall not

be located in the pictogram field].

See Sequence #31 for actions. 3 $0.00

Adjust door opening pressure /

closing time unless accepted

by DSA Fire / Life Safety.

Consider issues connected

with building pressure / climate

control.

Install wall-mounted sign at

single entrance.

2 $306.26

3 $183.75

5/31/2012 Page 6 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

38-Multiple

Accommodation Toilets:

Biologic Sciences Men's

Restroom on the 3rd

Floor. [Relocate the

paper towel dispenser to

provide 44" minimum

clearance throughout

restroom.]

44" min. clear path provided throughout facility.

18" betwen centerline of water closet and side

wall or partition [ADAAG 604.2 16" - 18" to

centerline of water closet].. The toilet paper

dispenser is located on the side wall below the

grab bar and within 7" - 9" of the front of the

toilet seat as measured to the centerline of the

dispenser.

Relocate water closet.

Relocate toilet paper

dispenser.

3 $2,205.04

UCR P5186

Biological

Sciences

39-Toilet Grab Bars:

Biologic Sciences Men's

Restroom on the 3rd

Floor.

The front of the side grab bar extends 52" from

back wall in multiple accommodation restroom.

Area directly above grab bars or proposed grab

bars is free of protruding obstructions to a height

of 18" (recessed items are allowed).

Relocate side grab bar. See

Sequence #38 for additional

actions.

3 $245.01

UCR P5186

Biological

Sciences

40-Lavatories: Biologic

Sciences Men's

Restroom on the 3rd

Floor.

27" high x 8" deep knee clearance under front

lip. 5 lb. max. force required to operate controls.

Raise existing multiple lavatory

counter. Reduce force needed

to operate faucet controls (5 lb.

maximum).

3 $3,981.33

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

42-Accessories: Biologic

Sciences Men's

Restroom on the 3rd

Floor.

43-Water Fountains

(Drinking): 2nd Floor

Administration Hall.

44-Doors: Women's

Restroom on the 2nd

Floor.

40" max. height to all other fixtures (i.e., soap

dispensers, towels, toilet seat covers, auto

dryers, sanitary napkins, waste recepatacles,

etc.).

27" high x 8" deep clear knee space under

fountain. Stream of bubbler is parallel to front

edge. 4" minimum height of stream.

5 lb. maximum pressure to operate interior

doors.

Paper towel dispenser is

protruding. Lower the paper

towel dispenser.

Raise existing drinking

fountain. Adjust water pressure

of existing fountain. Adjust

angle of stream.

Adjust door opening pressure /

closing time unless accepted

by DSA Fire / Life Safety.

Consider issues connected

with building pressure / climate

control.

3 $122.51

2 $1,531.28 Defer.

2 $306.26

5/31/2012 Page 7 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

47-Multiple

Accommodation Toilets:

Women's Restroom on

the 2nd Floor. [Relocate

the paper towel

dispenser to provide 44"

minimum clearance

throughout restroom.]

44" min. clear path provided throughout facility.

The clear floor area on the pull side of the door

within the stall is the width of the door and a

minimum 60" deep. If the compartment has an

inward swinging, side opening door and contains

a wall mounted water closet, the clearance

around the water closet is a minimum of 60"

wide and and a minimum 56" deep that is clear

of the stall door swing. If the compartment has a

side opening door, a minimum 60" wide x 60"

deep clear floor space is provided in front of the

water closet. 60" minimum width of stall [ADAAG

604.8.1.4 toe clearances - The front partition

and at least one side partition shall provide a toe

clearance of 9 inches minimum above the finish

floor and 6 inches deep minimum beyond the

compartment side face of the partition exclusive

of partition support members]. 18" betwen

centerline of water closet and side wall or

partition [ADAAG 604.2 16" - 18" to centerline of

water closet].. The toilet paper dispenser is

located on the side wall below the grab bar and

within 7" - 9" of the front of the toilet seat as

measured to the centerline of the dispenser.

Relocate toilet partition.

Relocate water closet.

Relocate the toilet paper

dispenser away from the top of

the grab bar. Relocate the

paper towel dispenser.

3 $3,068.03

UCR P5186

Biological

Sciences

48-Toilet Grab Bars:

Women's Restroom on

the 2nd Floor.

Area directly above grab bars or proposed grab

bars is free of protruding obstructions to a height

of 18" (recessed items are allowed).

See Sequence #47 (above) for

actions.

3 $0.00

UCR P5186

Biological

Sciences

49-Lavatories: Women's

Restroom on the 2nd

Floor.

18" minimum from center of fixture to side wall

or partition. 29" min. clearance from bottom of

apron to floor surface. 27" high x 8" deep knee

clearance under front lip. 5 lb. max. force

required to operate controls.

Relocate existing lavatory.

Raise existing multiple lavatory

counter. Reduce force needed

to operate faucet controls (5 lb.

maximum).

3 $6,827.58

UCR P5186

Biological

Sciences

50-Accessories:

Women's Restroom on

the 2nd Floor.

40" max. height to all other fixtures (i.e., soap

dispensers, towels, toilet seat covers, auto

dryers, sanitary napkins, waste recepatacles,

etc.).

See Sequence #47 for actions. 3 $0.00

5/31/2012 Page 8 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

51-Doors: Men's

Restroom on the 2nd

Floor.

54-Multiple

Accommodation Toilets:

Men's Restroom on the

2nd Floor.

55-Toilet Grab Bars:

Men's Restroom on the

2nd Floor. [See

Sequence #54 for

additional actions.]

5 lb. maximum pressure to operate interior

doors.

44" min. clear path provided throughout facility.

18" betwen centerline of water closet and side

wall or partition [ADAAG 604.2 16" - 18" to

centerline of water closet].. The toilet paper

dispenser is located on the side wall below the

grab bar and within 7" - 9" of the front of the

toilet seat as measured to the centerline of the

dispenser.

The front of the side grab bar extends 52" from

back wall in multiple accommodation restroom.

Area directly above grab bars or proposed grab

bars is free of protruding obstructions to a height

of 18" (recessed items are allowed).

Adjust door opening pressure /

closing time unless accepted

by DSA Fire / Life Safety.

Consider issues connected

with building pressure / climate

control.

Relocate water closet.

Relocate toilet paper

dispenser. Relocate the paper

towel dispenser.

2 $306.26

3 $2,327.54

Relocate side grab bar. 3 $245.01

UCR P5186

Biological

Sciences

56-Lavatories: Men's

Restroom on the 2nd

Floor.

5 lb. max. force required to operate controls. Reduce force needed to

operate faucet controls (5 lb.

maximum).

3 $306.26

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

58-Accessories: Men's

Restroom on the 2nd

Floor.

59-Sales and Service

Counters: 2nd Floor

Lobby. [Protruding

objects at counter - 7".

All counters should be

reviewed.]

60-Water Fountains

(Drinking): Biological

Science 1st Floor.

40" max. height to all other fixtures (i.e., soap

dispensers, towels, toilet seat covers, auto

dryers, sanitary napkins, waste recepatacles,

etc.).

A portion of the counter is a minimum of 36" in

length, at a height between 28" - 34" above the

floor and;

Stream of bubbler is parallel to front edge. 4"

minimum height of stream.

See Sequence #54 for actions. 3 $0.00

Install cane detectable barrier

below object.

Adjust water pressure of

existing fountain. Adjust angle

of stream.

2 $245.01

2 $673.76

UCR P5186

Biological

Sciences

61-Doors: Men's

Restroom at Biological

Science 1st Floor.

5 lb. maximum pressure to operate interior

doors.

Adjust door opening pressure /

closing time unless accepted

by DSA Fire / Life Safety.

Consider issues connected

with building pressure / climate

control.

1 $306.26

5/31/2012 Page 9 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

64-Multiple

Accommodation Toilets:

Men's Restroom at

Biological Science 1st

Floor.

65-Toilet Grab Bars:

Men's Restroom at

Biological Science 1st

Floor. [See Sequence

#64 for additional

action.]

66-Lavatories: Men's

Restroom at Biological

Science 1st Floor.

The toilet paper dispenser is located on the side

wall below the grab bar and within 7" - 9" of the

front of the toilet seat as measured to the

centerline of the dispenser.

The front of the side grab bar extends 52" from

back wall in multiple accommodation restroom.

Area directly above grab bars or proposed grab

bars is free of protruding obstructions to a height

of 18" (recessed items are allowed).

27" high x 8" deep knee clearance under front

lip.

Relocate the toilet paper

dispenser away from the top of

the grab bar.

1 $122.51

Relocate side grab bar. 1 $245.01

Raise existing multiple lavatory

counter.

1 $3,675.08

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

68-Accessories: Men's

Restroom at Biological

Science 1st Floor.

69-Doors: Women's

Restroom at Biological

Science 1st Floor.

72-Multiple

Accommodation Toilets:

Women's Restroom at

Biological Science 1st

Floor. [Relocate the

paper towel dispenser to

provide 44" clearance

throughout restroom.]

40" max. height to all other fixtures (i.e., soap

dispensers, towels, toilet seat covers, auto

dryers, sanitary napkins, waste recepatacles,

etc.).

5 lb. maximum pressure to operate interior

doors.

44" min. clear path provided throughout facility.

The toilet paper dispenser is located on the side

wall below the grab bar and within 7" - 9" of the

front of the toilet seat as measured to the

centerline of the dispenser.

Lower the paper towel

dispenser.

Adjust door opening pressure /

closing time unless accepted

by DSA Fire / Life Safety.

Consider issues connected

with building pressure / climate

control.

Relocate the toilet paper

dispenser away from the top of

the grab bar. Relocate the

paper towel dispenser.

1 $122.51

1 $306.26

1 $245.01

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

73-Toilet Grab Bars:

Women's Restroom at

Biological Science 1st

Floor. [See Sequence

#72 for additional

action.]

74-Lavatories: Women's

Restroom at Biological

Science 1st Floor.

The front of the side grab bar extends 52" from

back wall in multiple accommodation restroom.

Area directly above grab bars or proposed grab

bars is free of protruding obstructions to a height

of 18" (recessed items are allowed).

27" high x 8" deep knee clearance under front

lip.

Relocate side grab bar. 1 $245.01

Raise existing multiple lavatory

counter.

1 $3,675.08

5/31/2012 Page 10 of 11


Report #UCR P5186 Biological Sciences

Report

Name

Item/Location

Barrier

(noted feature, item or area does not meet the

new construction criteria detailed below)

Action Priority Target

Date

Estimated

Cost

Interim

Solution

Action

Completion

Date

UCR P5186

Biological

Sciences

UCR P5186

Biological

Sciences

75-Accessories:

Women's Restroom at

Biological Science 1st

Floor.

76-Seating, Tables and

Work Surfaces: Room

105 Office Support on

the 1st Floor. [Table is

non-compliant and

further review is

suggested.]

40" max. height to all other fixtures (i.e., soap

dispensers, towels, toilet seat covers, auto

dryers, sanitary napkins, waste recepatacles,

etc.).

27" high, 30" wide and 19" deep knee clearance

provided.

Lower the soap dispenser. 1 $122.51

Provide accessible table. 1M $245.01 Until such time

as accessible

furniture /

stations are

available in this

room staff shall

be informed of

the immediate

availability of

accessible

furniture /

stations that

may be placed

in the room to

meet the needs

of people with

disabilities.

Grand Total $127,994.01

5/31/2012 Page 11 of 11


Cost Report


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

1. Stairways - Biological Sciences.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Install slip-resistant color contrast striping to steps. 9 ea. $20.66 $185.94 $204.53 $230.10 $264.61 $264.61

Requires engineering/architectural evaluation. 1 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00

TOTAL EST: $264.61

5. Doors - Main Entry Door to Biological Sciences.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Post a sign/decal displaying the ”International Symbol of Accessibility”

at the primary entrance.

1 ea. $17.22 $17.22 $18.94 $21.31 $24.51 $24.51

TOTAL EST: $24.51

6. Clear Space at Doors - Main Entry Door to Biological Sciences.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Install automatic door opening device. 1 ea. $4,560.00 $4,560.00 $5,016.00 $5,643.00 $6,489.45 $6,489.45

TOTAL EST: $6,489.45

7. Floors and Levels - Main Entry Door to Biological Sciences.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Secure loose doormat. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

9. Stairways - Stairway 2 at Biological Sciences.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Requires engineering/architectural evaluation. 1 ea. $0.00 $0.00 $0.00 $0.00 $0.00 $0.00

TOTAL EST: $0.00

Page 1 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

13. Protruding Objects - Equipment Room CR1200C at Biological Sciences.

Priority: 1

RECOMMENDATIONS AND RETROFIT COSTS:

Modify, relocate, replace or remove restricting objects. 2 ea. $172.16 $344.32 $378.75 $426.09 $490.00 $490.00

TOTAL EST: $490.00

14. Protruding Objects - Shelving Unit Next to Activity Room 1224 at Biological Sciences.

Priority: 1

RECOMMENDATIONS AND RETROFIT COSTS:

Install cane detectable barrier below object. 4 l.f. $86.08 $344.32 $378.75 $426.09 $490.00 $490.00

TOTAL EST: $490.00

15. Visual/Audible Alarms - Biologic Science Equipment Room Outside of Activity Room 1224.

Priority: 0

RECOMMENDATIONS AND RETROFIT COSTS:

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62

TOTAL EST: $7,115.62

16. Sinks - Biologic Science Room 1227 Lab and 1226.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

Cut the paneling under the lavatory/sink counter to comply with 1 ea. $344.32 $344.32 $378.75 $426.09 $490.00 $490.00

knee clearance.

Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07

TOTAL EST: $3,920.08

17. Controls, Operating Mechanisms & Vending Machines. - Fume Hood at Biologic Sciences Room 1227 Lab and 1226.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Requires engineering/architectural evaluation. 1 ea. $5,000.00 $5,000.00 $5,500.00 $6,187.50 $7,115.62 $7,115.62

TOTAL EST: $7,115.62

Page 2 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

18. Seating, Tables and Work Surfaces - Biologic Sciences Room 1227 Lab and 1226.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

19. Sinks - Biologic Sciences Room 1224 Activity Room.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Insulate pipes under lavatory (or sink when applicable). 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

Replace/Install accessible sink. 1 ea. $2,238.08 $2,238.08 $2,461.89 $2,769.63 $3,185.07 $3,185.07

TOTAL EST: $3,430.08

20. Seating, Tables and Work Surfaces - Biologic Sciences Room 1224 Activity Room.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

22. Protruding Objects - Biologic Sciences Room 1219 Freezer Room.

Priority: 1

RECOMMENDATIONS AND RETROFIT COSTS:

Install cane detectable barrier below object. 1 l.f. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $122.51

24. Doors - Biologic Sciences Room 1207 Dark Room.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Adjust door for opening pressure/closing times unless accepted

by DSA / Fire Life Safety.

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $306.26

Page 3 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

27. Water Fountains (Drinking) - Biologic Sciences 3rd Floor Hall.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Raise/Lower existing drinking fountain. 1 ea. $602.56 $602.56 $662.82 $745.67 $857.52 $857.52

Adjust water pressure of existing fountain. 1 ea. $301.28 $301.28 $331.41 $372.84 $428.77 $428.77

Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $1,531.30

29. Clear Space at Doors - Biologic Sciences Women’s Restroom on the 3rd Floor.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Install automatic door opening device. 1 ea. $4,560.00 $4,560.00 $5,016.00 $5,643.00 $6,489.45 $6,489.45

TOTAL EST: $6,489.45

31. Multiple Accommodation Toilets - Biologic Science Women’s Restroom on the 3rd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate water closet. 1 ea. $1,463.36 $1,463.36 $1,609.70 $1,810.91 $2,082.55 $2,082.55

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

bars or proposed grab bars.

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $2,327.57

33. Lavatories - Biologic Science Women’s Restroom on the 3rd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Raise/Lower existing multiple lavatory counter. 1 ea. $2,582.40 $2,582.40 $2,840.64 $3,195.72 $3,675.08 $3,675.08

Reduce force needed to operate faucet controls (5 lb. maximum). 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $3,981.34

35. Doors - Biologic Sciences Men’s Restroom on the 3rd Floor.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Adjust door for opening pressure/closing times unless accepted

by DSA / Fire Life Safety.

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $306.26

Page 4 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

37. Identification Symbols, Restrooms - Biologic Sciences Men’s Restroom on the 3rd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Install wall-mounted sign at single entrance. 1 ea. $129.12 $129.12 $142.03 $159.78 $183.75 $183.75

TOTAL EST: $183.75

38. Multiple Accommodation Toilets - Biologic Sciences Men’s Restroom on the 3rd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate water closet. 1 ea. $1,463.36 $1,463.36 $1,609.70 $1,810.91 $2,082.55 $2,082.55

Relocate toilet paper dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $2,205.06

39. Toilet Grab Bars - Biologic Sciences Men’s Restroom on the 3rd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

40. Lavatories - Biologic Sciences Men’s Restroom on the 3rd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Raise/Lower existing multiple lavatory counter. 1 ea. $2,582.40 $2,582.40 $2,840.64 $3,195.72 $3,675.08 $3,675.08

Reduce force needed to operate faucet controls (5 lb. maximum). 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $3,981.34

43. Water Fountains (Drinking) - 2nd Floor Administration Hall.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Raise/Lower existing drinking fountain. 1 ea. $602.56 $602.56 $662.82 $745.67 $857.52 $857.52

Adjust water pressure of existing fountain. 1 ea. $301.28 $301.28 $331.41 $372.84 $428.77 $428.77

Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $1,531.30

Page 5 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

44. Doors - Women’s Restroom on the 2nd Floor.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Adjust door for opening pressure/closing times unless accepted

by DSA / Fire Life Safety.

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $306.26

47. Multiple Accommodation Toilets - Women’s Restroom on the 2nd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate toilet partition. 1 ea. $520.32 $520.32 $572.35 $643.89 $740.47 $740.47

Relocate water closet. 1 ea. $1,463.36 $1,463.36 $1,609.70 $1,810.91 $2,082.55 $2,082.55

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

bars or proposed grab bars.

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $3,068.04

49. Lavatories - Women’s Restroom on the 2nd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate existing lavatory. 1 ea. $2,000.00 $2,000.00 $2,200.00 $2,475.00 $2,846.25 $2,846.25

Raise/Lower existing multiple lavatory counter. 1 ea. $2,582.40 $2,582.40 $2,840.64 $3,195.72 $3,675.08 $3,675.08

Reduce force needed to operate faucet controls (5 lb. maximum). 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $6,827.59

51. Doors - Men’s Restroom on the 2nd Floor.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Adjust door for opening pressure/closing times unless accepted

by DSA / Fire Life Safety.

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $306.26

Page 6 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

54. Multiple Accommodation Toilets - Men’s Restroom on the 2nd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate water closet. 1 ea. $1,463.36 $1,463.36 $1,609.70 $1,810.91 $2,082.55 $2,082.55

Relocate toilet paper dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $2,327.57

55. Toilet Grab Bars - Men’s Restroom on the 2nd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

56. Lavatories - Men’s Restroom on the 2nd Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Reduce force needed to operate faucet controls (5 lb. maximum). 1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $306.26

59. Sales and Service Counters - 2nd Floor Lobby.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Install cane detectable barrier below object. 2 l.f. $86.08 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

60. Water Fountains (Drinking) - Biological Science 1st Floor.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Adjust water pressure of existing fountain. 1 ea. $301.28 $301.28 $331.41 $372.84 $428.77 $428.77

Adjust angle of stream. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $673.78

Page 7 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

61. Doors - Men’s Restroom at Biological Science 1st Floor.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Adjust door for opening pressure/closing times unless accepted

by DSA / Fire Life Safety.

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $306.26

64. Multiple Accommodation Toilets - Men’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

bars or proposed grab bars.

TOTAL EST: $122.51

65. Toilet Grab Bars - Men’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

66. Lavatories - Men’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Raise/Lower existing multiple lavatory counter. 1 ea. $2,582.40 $2,582.40 $2,840.64 $3,195.72 $3,675.08 $3,675.08

TOTAL EST: $3,675.08

68. Accessories - Men’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $122.51

Page 8 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

69. Doors - Women’s Restroom at Biological Science 1st Floor.

Priority: 2

RECOMMENDATIONS AND RETROFIT COSTS:

Adjust door for opening pressure/closing times unless accepted

by DSA / Fire Life Safety.

1 ea. $215.20 $215.20 $236.72 $266.31 $306.26 $306.26

TOTAL EST: $306.26

72. Multiple Accommodation Toilets - Women’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate the toilet paper dispenser away from the top of the grab 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

bars or proposed grab bars.

Relocate the paper towel dispenser / hand dryer. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $245.02

73. Toilet Grab Bars - Women’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate grab bar. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

74. Lavatories - Women’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Raise/Lower existing multiple lavatory counter. 1 ea. $2,582.40 $2,582.40 $2,840.64 $3,195.72 $3,675.08 $3,675.08

TOTAL EST: $3,675.08

75. Accessories - Women’s Restroom at Biological Science 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Relocate the soap dispenser. 1 ea. $86.08 $86.08 $94.69 $106.53 $122.51 $122.51

TOTAL EST: $122.51

Page 9 of 10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue Qty Unit

Sub

Contractor

Sub

Total

(10%)

Concealed

Conditions

(12.5%)

Security

Conditions

(15%)

General

Conditions

Total

76. Seating, Tables and Work Surfaces - Room 105 Office Support on the 1st Floor.

Priority: 3

RECOMMENDATIONS AND RETROFIT COSTS:

Provide accessible table. 1 ea. $172.16 $172.16 $189.38 $213.05 $245.01 $245.01

TOTAL EST: $245.01

REPORT TOTALS: $54,037.40 $59,441.14 $66,871.28 $76,901.97 $76,901.97

Page 10 of 10


Survey


Americans with Disabilities Act of 1990

Site Assessment Report

Report: UCR P5186

Biological Sciences

900 University Avenue

Riverside, CA 92521

Inspection Date: 08/03/2009

Prepared for:

University of California at Riverside

Prepared by:

National Access Consultants, LLC

2321 Abbot Kinney Blvd. Suite 200

Venice, California 90291

(805)497-6116


Contents

1. Stairways - Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2. Stairway Handrails - North Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

3. Pedestrian Ramps - Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

4. Ramp Handrails - Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

5. Doors - Main Entry Door to Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

6. Clear Space at Doors - Main Entry Door to Biological Sciences. . . . . . . . . . . . . . . . . . . . . 8

7. Floors and Levels - Main Entry Door to Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . 9

8. Stairway Signage - Stairway 2 at Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . 10

9. Stairways - Stairway 2 at Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

10. Stairway Handrails - Stairway 2 at Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . . . . 12

11. Doors - Equipment Room CR1200C at Biological Sciences. . . . . . . . . . . . . . . . . . . . . . . . 14

12. Clear Space at Doors - Equipment Room CR1200C at Biological Sciences. . . . . . . . . . . . . . . 15

13. Protruding Objects - Equipment Room CR1200C at Biological Sciences. . . . . . . . . . . . . . . . 16

14. Protruding Objects - Shelving Unit Next to Activity Room 1224 at Biological Sciences. . . . . . . . 18

15. Visual/Audible Alarms - Biologic Science Equipment Room Outside of Activity Room 1224. . . . . 19

16. Sinks - Biologic Science Room 1227 Lab and 1226. . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

17. Controls, Operating Mechanisms & Vending Machines. - Fume Hood at Biologic Sciences Room 1227

Lab and 1226. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

18. Seating, Tables and Work Surfaces - Biologic Sciences Room 1227 Lab and 1226. . . . . . . . . . . 24

19. Sinks - Biologic Sciences Room 1224 Activity Room. . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

20. Seating, Tables and Work Surfaces - Biologic Sciences Room 1224 Activity Room. . . . . . . . . . . 27

21. Seating, Tables and Work Surfaces - Biological Safety Cabinet at Biologic Sciences Room 1221 Support

Room. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

22. Protruding Objects - Biologic Sciences Room 1219 Freezer Room. . . . . . . . . . . . . . . . . . . . 29

23. Controls, Operating Mechanisms & Vending Machines. - Microscope on Vibrating Table at Biologic

Sciences Room 1210 Bio Lab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

24. Doors - Biologic Sciences Room 1207 Dark Room. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

25. Clear Space at Doors - Biologic Sciences Room 1207 Dark Room. . . . . . . . . . . . . . . . . . . . 32

26. Controls, Operating Mechanisms & Vending Machines. - Freezer Next to Room 2216 at Biologic

Sciences 2nd Floor Lab Hall. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33


27. Water Fountains (Drinking) - Biologic Sciences 3rd Floor Hall. . . . . . . . . . . . . . . . . . . . . . 34

28. Doors - Biologic Sciences Women’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . 36

29. Clear Space at Doors - Biologic Sciences Women’s Restroom on the 3rd Floor. . . . . . . . . . . . . 37

30. Identification Symbols, Restrooms - Biologic Sciences Women’s Restroom on the 3rd Floor. . . . . 38

31. Multiple Accommodation Toilets - Biologic Science Women’s Restroom on the 3rd Floor. . . . . . . 40

32. Toilet Grab Bars - Biologic Science Women’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . 43

33. Lavatories - Biologic Science Women’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . . . 45

34. Accessories - Biologic Sciences Women’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . . 47

35. Doors - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . . . 49

36. Clear Space at Doors - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . . . . . . . . 50

37. Identification Symbols, Restrooms - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . 51

38. Multiple Accommodation Toilets - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . . 52

39. Toilet Grab Bars - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . 55

40. Lavatories - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . 57

41. Urinals - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . . . . . . . 59

42. Accessories - Biologic Sciences Men’s Restroom on the 3rd Floor. . . . . . . . . . . . . . . . . . . . 60

43. Water Fountains (Drinking) - 2nd Floor Administration Hall. . . . . . . . . . . . . . . . . . . . . . . 62

44. Doors - Women’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

45. Clear Space at Doors - Women’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . 65

46. Identification Symbols, Restrooms - Women’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . 66

47. Multiple Accommodation Toilets - Women’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . 68

48. Toilet Grab Bars - Women’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . 71

49. Lavatories - Women’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

50. Accessories - Women’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

51. Doors - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

52. Clear Space at Doors - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . 78

53. Identification Symbols, Restrooms - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . 79

54. Multiple Accommodation Toilets - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . 81

55. Toilet Grab Bars - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . 84

56. Lavatories - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86


57. Urinals - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

58. Accessories - Men’s Restroom on the 2nd Floor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

59. Sales and Service Counters - 2nd Floor Lobby. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

60. Water Fountains (Drinking) - Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . 93

61. Doors - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . 95

62. Clear Space at Doors - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . 96

63. Identification Symbols, Restrooms - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . 97

64. Multiple Accommodation Toilets - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . . 99

65. Toilet Grab Bars - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . 101

66. Lavatories - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . . . . 103

67. Urinals - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . . 104

68. Accessories - Men’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . . . 105

69. Doors - Women’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . . . . . 107

70. Clear Space at Doors - Women’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . 108

71. Identification Symbols, Restrooms - Women’s Restroom at Biological Science 1st Floor. . . . . . . 109

72. Multiple Accommodation Toilets - Women’s Restroom at Biological Science 1st Floor. . . . . . . . 111

73. Toilet Grab Bars - Women’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . 114

74. Lavatories - Women’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . . 116

75. Accessories - Women’s Restroom at Biological Science 1st Floor. . . . . . . . . . . . . . . . . . . . 117

76. Seating, Tables and Work Surfaces - Room 105 Office Support on the 1st Floor. . . . . . . . . . . . 119


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

1. Stairways - Biological Sciences.

Memo:

All stairs should be reviewed.

Areas noted in compliance:

44” min. width if occupant load is more than 50.

All treads are slip resistant.

Nosing projection is less than 1-1/2”.

All risers are closed.

11” min. tread width. (12-1/2” - 13”.)

Areas not meeting new construction standards:

All steps have uniform riser height and tread width.

Stairs do not accumulate water. (Stairs accumulate water.)

Ext. - Top landing and all steps have color striping minimum 2” wide and a maximum 4” wide parallel to, and not

more than 1” maximum from tread nose or landing. (No color and 1-1/2”.)

Recommendation:

Install slip-resistant color contrast striping to steps.

Requires engineering/architectural evaluation.

Photo #UCR P5186 Biological Sciences-1-1 (originally 49-400)

1


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

2. Stairway Handrails - North Biological Sciences.

Memo:

All stairs should be reviewed. Round rails back to wall / floor. Handrails are non-compliant and further review is suggested.

Areas noted in compliance:

Handrails are provided on both sides and are continuous for the full length of the stairway.

1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.

12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned.

12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being

returned.

Handrails do not rotate in their fittings.

Wall or adjacent surface is free of sharp or abrasive elements.

Handrail is smooth with no sharp edges.

Handrails do not protrude into pathways.

Areas not meeting new construction standards:

1-1/2” clearance provided between rail and wall. (2”.)

Rails are 34” - 38” above stair nosing. (33”.)

Ends of rails are rounded or returned smoothly to wall or floor. (None.)

Recommendation:

None.

2


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-2-1 (originally 50-400)

3


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

3. Pedestrian Ramps - Biological Sciences.

Memo:

All ramps should be reviewed.

Areas noted in compliance:

Ramps do not exceed allowable lengths. (40’ up to 6.25%, 37.5’ up to 6.67%, 30’ up to 8.33%).

8.33% maximum surface slope at ramp.

2% maximum cross slope at ramp.

48” minimum width required at ramp.

2% maximum slope in any direction at top landing.

72” minimum bottom landing in the ramp direction.

Bottom landing is as wide as ramp.

Finished surface is slip resistant.

Outdoor ramps are designed so water does not accumulate on walking surfaces.

Areas not meeting new construction standards:

60” x 60” min. top landing. NOTE: When a ramp leads directly to a door that swings out into the top landing area the

top landing must measure a minimum 42”+ the door width. (57” x 88”.)

2% maximum slope in any direction at bottom landing. (2.6%.)

Handrails are provided on both sides. (None.)

Recommendation:

None.

4


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-3-1 (originally 51-400)

Photo #UCR P5186 Biological Sciences-3-2 (originally 52-400)

5


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

4. Ramp Handrails - Biological Sciences.

Memo:

All ramp handrails should be reviewed.

Areas noted in compliance:

None observed.

Areas not meeting new construction standards:

Handrails are on both sides and continuous the full length of the ramp. (Only on top part of ramp.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-4-1 (originally 53-400)

6


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

5. Doors - Main Entry Door to Biological Sciences.

Memo:

All doors should be reviewed.

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate exterior doors. (10 lbs.)

The international symbol of accessibility is posted at all primary entrances. (No International Symbol of Accessibility.)

Recommendation:

Post a sign/decal displaying the ”International Symbol of Accessibility” at the primary entrance.

Photo #UCR P5186 Biological Sciences-5-1 (originally 54-400)

7


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

6. Clear Space at Doors - Main Entry Door to Biological Sciences.

Memo:

All door clear spaces on exterior should be reviewed.

Areas noted in compliance:

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 24” exterior doors.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

Floor or landing is level and clear (2% max. slope). (2.7%.)

Recommendation:

Install automatic door opening device.

Photo #UCR P5186 Biological Sciences-6-1 (originally 55-400)

8


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

7. Floors and Levels - Main Entry Door to Biological Sciences.

Memo:

All doormats must be secured down and all should be reviewed or secured.

Areas noted in compliance:

None observed.

Areas not meeting new construction standards:

Carpets or carpet tiles are securely attached and do not exceed 1/2” in height.

Carpet’s exposed edges are fastened to floor surfaces and have trim along entire length.

Recommendation:

Secure loose doormat.

Photo #UCR P5186 Biological Sciences-7-1 (originally 56-400)

9


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

8. Stairway Signage - Stairway 2 at Biological Sciences.

Memo:

Areas noted in compliance:

Identification signage is located at each floor level in all enclosed stairways in buildings two or more stories in height.

Signs are a min. of 12” x 12” in size.

Sign identifies the stairway location, floor level number, and upper and lower terminus of stairway.

Information is presented with raised Arabic numerals and corresponding Grade II Braille.

Sign is centered 60” above the floor landing immediately adjacent to the door on the strike side.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-8-1 (originally 57-400)

10


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

9. Stairways - Stairway 2 at Biological Sciences.

Memo:

All stairways should be reviewed.

Areas noted in compliance:

44” min. width if occupant load is more than 50.

All treads are slip resistant.

All risers are closed.

11” min. tread width. (11-3/4” - 12” wide)

Areas not meeting new construction standards:

Nosing projection is less than 1-1/2”. (Not flush.)

All steps have uniform riser height and tread width.

Stairs do not accumulate water. (Accumulate water.)

Int. - Top landing and lower tread have color striping minimum 2” wide and a maximum 4” wide parallel to, and

not more than 1” maximum from tread nose or landing. (1-1/4”.)

Recommendation:

Requires engineering/architectural evaluation.

Photo #UCR P5186 Biological Sciences-9-1 (originally 58-400)

11


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

10. Stairway Handrails - Stairway 2 at Biological Sciences.

Memo:

All stairway handrails should be reviewed. Guardrail is non-compliant due to a gap at the bottom.

Areas noted in compliance:

Handrails are provided on both sides and are continuous for the full length of the stairway.

1-1/4” to 1-1/2” handgrip portion or cross section equivalent or the shape provides an equivalent gripping surface.

Rails are 34” - 38” above stair nosing.

Handrails do not rotate in their fittings.

Wall or adjacent surface is free of sharp or abrasive elements.

Ends of rails are rounded or returned smoothly to wall or floor.

Handrail is smooth with no sharp edges.

Handrails do not protrude into pathways.

Inner rails that double back or turn are continuous.

Areas not meeting new construction standards:

1-1/2” clearance provided between rail and wall. (1-3/4”.)

12” minimum level extension beyond top nosing (parallel with the ground or floor surface) before being returned. (9”.)

12” plus one tread width level extension beyond bottom nosing (parallel with the ground or floor surface) before being

returned. (10”.)

Recommendation:

None.

12


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-10-1 (originally 59-400)

13


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

11. Doors - Equipment Room CR1200C at Biological Sciences.

Memo:

Excessive pressure. All interior doors should be reviewed.

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (7 lbs.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-11-1 (originally 60-400)

14


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

12. Clear Space at Doors - Equipment Room CR1200C at Biological

Sciences.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-12-1 (originally 61-400)

15


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

13. Protruding Objects - Equipment Room CR1200C at Biological

Sciences.

Memo:

All areas should be reviewed for protruding objects.

Areas noted in compliance:

None observed.

Areas not meeting new construction standards:

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways

or aisles if lower edge of object is above 27” and below 80”. (4-1/2”.)

Recommendation:

Modify, relocate, replace or remove restricting objects.

Photo #UCR P5186 Biological Sciences-13-1 (originally 62-400)

16


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-13-2 (originally 63-400)

17


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

14. Protruding Objects - Shelving Unit Next to Activity Room 1224 at

Biological Sciences.

Memo:

All areas should be reviewed for hazardous objects.

Areas noted in compliance:

None observed.

Areas not meeting new construction standards:

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways

or aisles if lower edge of object is above 27” and below 80”. (24-1/2”.)

Recommendation:

Install cane detectable barrier below object.

Photo #UCR P5186 Biological Sciences-14-1 (originally 64-400)

18


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

15. Visual/Audible Alarms - Biologic Science Equipment Room Outside of

Activity Room 1224.

Memo:

All fire alarms should be reviewed.

Areas noted in compliance:

The alarm is integrated into the building or facility alarm system.

Lamp is a xenon strobe type or equivalent.

The color is clear and nominal white (unfiltered) or clear filtered white light.

The maximum pulse duration is two-tenths of one second (0.2 sec) with a maximum duty cycle of 40 percent.

The intensity is a maximum of 75 candela.

The flash rate is a minimum of 1Hz and a maximum of 3Hz.

There are no places in common corridors or hallways that are more than 50’ from required signaling appliances.

When provided/required, audible emergency alarms meet applicable requirements.

Areas not meeting new construction standards:

The appliance is placed 80” above the highest floor level within the space or 6” below the ceiling, whichever is lower.

(85-1/2”.)

Recommendation:

Requires engineering/architectural evaluation.

Photo #UCR P5186 Biological Sciences-15-1 (originally 65-400)

19


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-15-2 (originally 66-400)

20


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

16. Sinks - Biologic Science Room 1227 Lab and 1226.

Memo:

Provide insulation for piping.

Areas noted in compliance:

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.

Required clear space adjoins or overlaps an accessible route.

There are no sharp or abrasive elements under sink.

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.

Areas not meeting new construction standards:

34” maximum height of rim or counter above floor surfaces. (36”.)

Sink is a maximum of 6-1/2” deep. (10-1/2”.)

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the

sink. (No depth.)

Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)

5 lb. maximum force required to activate controls. (7 lbs.)

Recommendation:

Insulate pipes under lavatory (or sink when applicable).

Cut the paneling under the lavatory/sink counter to comply with knee clearance.

Replace/Install accessible sink.

21


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-16-1 (originally 67-400)

22


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

17. Controls, Operating Mechanisms & Vending Machines. - Fume Hood

at Biologic Sciences Room 1227 Lab and 1226.

Memo:

No knee clearance and controls are not accessible. All fume hoods should be reviewed.

Areas noted in compliance:

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not

require tight grasping, pinching or twisting of the wrist to operate.

Side Reach to Objects: Minimum 30” x 48” clear floor space for side approach is provided at the object.

Side Reach to Objects: Clear floor space begins a maximum of 10” from the wall/surface the object is mounted on.

Side Reach to Objects: Lowest operable part of the object is a minimum of 9” above the floor surface.

Areas not meeting new construction standards:

Side Reach to Objects: Highest operable part of the object is a maximum of 54” above the floor surface. (65”.)

Recommendation:

Requires engineering/architectural evaluation.

Photo #UCR P5186 Biological Sciences-17-1 (originally 68-400)

23


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

18. Seating, Tables and Work Surfaces - Biologic Sciences Room 1227

Lab and 1226.

Memo:

All accessible stations in labs should be reviewed.

Areas noted in compliance:

30” x 48” min. clear floor space is provided.

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.

28” - 34” height of table or work surface that is 36” wide.

Areas not meeting new construction standards:

27” high, 30” wide and 19” deep knee clearance provided. (17-3/4” deep.)

Recommendation:

Provide accessible table.

Photo #UCR P5186 Biological Sciences-18-1 (originally 69-400)

24


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

19. Sinks - Biologic Sciences Room 1224 Activity Room.

Memo:

Provide insulation for piping. All accessible sinks should be reviewed.

Areas noted in compliance:

Minimum 30” x 48” clear space is provided in front of sink that allows forward approach.

Required clear space adjoins or overlaps an accessible route.

34” maximum height of rim or counter above floor surfaces.

There are no sharp or abrasive elements under sink.

Faucets are lever type, electronically activated or approved self-closing valves (minimum 10 second open flow).

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of the wrist.

5 lb. maximum force required to activate controls.

Areas not meeting new construction standards:

Sink is a maximum of 6-1/2” deep. (7-1/2”.)

Knee clearance under sink is a minimum of 27” high and 30” wide, and provides an absolute depth of 19” underneath the

sink. (28-3/4” high.)

Drain and hot water piping is insulated or configured to prevent contact. (No insulation.)

Recommendation:

Insulate pipes under lavatory (or sink when applicable).

Replace/Install accessible sink.

25


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-19-1 (originally 70-400)

26


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

20. Seating, Tables and Work Surfaces - Biologic Sciences Room 1224

Activity Room.

Memo:

All seating should be reviewed for accessible stations.

Areas noted in compliance:

30” x 48” min. clear floor space is provided.

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.

28” - 34” height of table or work surface that is 36” wide.

Areas not meeting new construction standards:

27” high, 30” wide and 19” deep knee clearance provided. (0” to the table legs.)

Recommendation:

Provide accessible table.

Photo #UCR P5186 Biological Sciences-20-1 (originally 71-400)

27


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

21. Seating, Tables and Work Surfaces - Biological Safety Cabinet at

Biologic Sciences Room 1221 Support Room.

Memo:

Non-compliant fume hood and further review is suggested.

Areas noted in compliance:

30” x 48” min. clear floor space is provided.

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor

space.

Areas not meeting new construction standards:

27” high, 30” wide and 19” deep knee clearance provided. (26” high.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-21-1 (originally 72-400)

28


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

22. Protruding Objects - Biologic Sciences Room 1219 Freezer Room.

Memo:

All areas should be reviewed for protruding objects.

Areas noted in compliance:

None observed.

Areas not meeting new construction standards:

Objects projecting from walls (i.e. telephones, etc.) have 4” maximum projection into walks, halls, corridors, passageways

or aisles if lower edge of object is above 27” and below 80”. (7”.)

Recommendation:

Install cane detectable barrier below object.

Photo #UCR P5186 Biological Sciences-22-1 (originally 73-400)

29


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

23. Controls, Operating Mechanisms & Vending Machines. - Microscope

on Vibrating Table at Biologic Sciences Room 1210 Bio Lab.

Memo:

Table has non-compliant reach ranges and all machinery should be reviewed.

Areas noted in compliance:

Forward Reach to Objects: Minimum 30” x 48” clear floor space for forward approach is provided at object.

Forward Reach to Objects: Lowest operable part of object is a minimum of 15” above the floor surface.

Forward reach over obstruction: Depth of obstruction is not more than 25”.

Areas not meeting new construction standards:

Forward Reach to Objects: Highest operable part of object is a miximum of 48” above the floor surface. (56”.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-23-1 (originally 74-400)

30


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

24. Doors - Biologic Sciences Room 1207 Dark Room.

Memo:

Door in is non-compliant and further review is suggested.

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (8 lbs.)

Recommendation:

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.

Photo #UCR P5186 Biological Sciences-24-1 (originally 75-400)

31


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

25. Clear Space at Doors - Biologic Sciences Room 1207 Dark Room.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-25-1 (originally 76-400)

32


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

26. Controls, Operating Mechanisms & Vending Machines. - Freezer Next

to Room 2216 at Biologic Sciences 2nd Floor Lab Hall.

Memo:

Reach range is non-compliant and all controls should be reviewed for compliance.

Areas noted in compliance:

Controls and operating mechanisms (handles, coin slots, openings, buttons, etc.) are operable with one hand and do not

require tight grasping, pinching or twisting of the wrist to operate.

Side Reach to Objects: Minimum 30” x 48” clear floor space for side approach is provided at the object.

Side Reach to Objects: Clear floor space begins a maximum of 10” from the wall/surface the object is mounted on.

Side Reach to Objects: Lowest operable part of the object is a minimum of 9” above the floor surface.

Areas not meeting new construction standards:

Side Reach to Objects: Highest operable part of the object is a maximum of 54” above the floor surface. (64”.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-26-1 (originally 77-400)

33


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

27. Water Fountains (Drinking) - Biologic Sciences 3rd Floor Hall.

Memo:

All drinking fountains should be reviewed.

Areas noted in compliance:

32” minimum wide and 18” minimum deep alcove provided.

18” minimum depth of fountain.

9” high x 17” deep toe clearance.

Lever or push bar control is located 6” max. from front edge.

Bubbler outlet is 6” maximum from front.

Bubbler outlet is 36” maximum from floor.

The force required to activate controls does not exceed 5lbf.

Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty

bending or stooping.

Areas not meeting new construction standards:

27” high x 8” deep clear knee space under fountain. (26-3/4” high.)

Stream of bubbler is parallel to front edge. (On angle.)

4” minimum height of stream. (3”.)

Recommendation:

Raise/Lower existing drinking fountain.

Adjust water pressure of existing fountain.

Adjust angle of stream.

34


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-27-1 (originally 78-400)

35


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

28. Doors - Biologic Sciences Women’s Restroom on the 3rd Floor.

Memo:

See Sequence #29 for recommendation.

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (9 lbs.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-28-1 (originally 79-400)

36


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

29. Clear Space at Doors - Biologic Sciences Women’s Restroom on the

3rd Floor.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

60” min. clear space in direction of door swing. (59-1/4” to the wall.)

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach. (17-1/4” to the wall.)

Recommendation:

Install automatic door opening device.

Photo #UCR P5186 Biological Sciences-29-1 (originally 80-400)

37


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

30. Identification Symbols, Restrooms - Biologic Sciences Women’s

Restroom on the 3rd Floor.

Memo:

Areas noted in compliance:

Women’s - 12” diameter circle 1/4” thick. The circle symbol contrasts with the door, light on dark background or dark

on light background.

Signs are centered on door 60” from floor.

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door.

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal

identification and the border dimensions of this pictogram is a minimum of 6” in height.

Characters are min. of 5/8” high and max. of 2” high.

Letters and numerals are raised 1/32” sans-serif upper case and accompanied by Grade 2 Braille.

Signs are centered on the wall 60” from floor.

Mounting location allows a person to approach within 3” of signage without encountering protruding objects or standing

within the swing of the door.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

38


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-30-1 (originally 81-400)

39


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

31. Multiple Accommodation Toilets - Biologic Science Women’s

Restroom on the 3rd Floor.

Memo:

Relocate the paper towel dispenser to provide clearance of 44” throughout restroom.

Areas noted in compliance:

60” min. diameter turning circle clear of objects from floor height to 27” in room.

3 second min. automatic closing door.

Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.

Door has loop or U-shaped handle immediately below latch on both inside and outside of door.

34” minimum opening at side.

The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.

The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.

The clear floor area on the push side of the door is the width of the door and a minimum 48” deep., measured perpendicular

to the door in its closed position.

If the compartment has an inward swinging, side opening door and contains a wall mounted water closet, the clearance

around the water closet is a minimum of 60” wide and and a minimum 56” deep that is clear of the stall door swing.

If the compartment has a side opening door, a minimum 60” wide x 60” deep clear floor space is provided in front

of the water closet.

60” minimum width of stall.

32” minimum from side of water closet to opposite wall or partition.

42” minimum from centerline of water closet to opposite wall or partition.

The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toilet

seat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).

Flush valve is on wide side of the water closet.

44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.

Front of toilet paper dispenser is within 36” of back wall.

19” minimum height to toilet paper dispenser.

Toilet paper dispenser provides continuous flow.

Areas not meeting new construction standards:

44” min. clear path provided throughout facility. (40”.)

18” betwen centerline of water closet and side wall or partition. (19-1/2”.)

40


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet

seat. (Above the grab bar - 43”.)

Recommendation:

Relocate water closet.

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.

Relocate the paper towel dispenser / hand dryer.

Photo #UCR P5186 Biological Sciences-31-1 (originally 82-400)

41


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-31-2 (originally 83-400)

42


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

32. Toilet Grab Bars - Biologic Science Women’s Restroom on the 3rd

Floor.

Memo:

See Sequence #31 for recommendations.

Areas noted in compliance:

1-1/4” to 1-1/2” diameter of bars.

1-1/2” clearance between bars and each wall or partition.

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for

tank type toilets, 36” may be allowed if tank obstructs placement of bar).

Side bar has 42” min. length.

The front of the side grab bar extends 52” from back wall in multiple accommodation restroom.

Side bar begins a max. of 12” from back wall.

Back bar has 36” min. length.

Back bar begins a max. of 6” from side wall.

Bars are smooth with a min. edge radius of 1/8”.

Grab bars do not rotate within their fittings.

Min. structural strength to support 250 lb. point load.

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.

Areas not meeting new construction standards:

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed items

are allowed). (Toilet paper dispenser.)

Recommendation:

None.

43


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-32-1 (originally 84-400)

44


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

33. Lavatories - Biologic Science Women’s Restroom on the 3rd Floor.

Memo:

Areas noted in compliance:

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this

space).

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.

18” minimum from center of fixture to side wall or partition.

34” max. height to rim or counter above floor surface.

29” min. clearance from bottom of apron to floor surface.

30” wide x 9” high x 17” deep clearance from front of lavatory.

Drain and piping is insulated or configured to prevent contact.

There are no sharp or abrasive elements under lavatory.

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.

Areas not meeting new construction standards:

27” high x 8” deep knee clearance under front lip. (26” high.)

5 lb. max. force required to operate controls. (8 lbs.)

Recommendation:

Raise/Lower existing multiple lavatory counter.

Reduce force needed to operate faucet controls (5 lb. maximum).

45


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-33-1 (originally 85-400)

46


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

34. Accessories - Biologic Sciences Women’s Restroom on the 3rd Floor.

Memo:

See Sequence #31 for recommendations.

Areas noted in compliance:

40” maximum height to bottom of reflective surface of mirror.

height above floor surface is recom-

Coat hooks and shelving are located within appropriate reach ranges (48” max.

mended).

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.

A maximum of 5 lbs. force is required to operate mechanisms.

Areas not meeting new construction standards:

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste

recepatacles, etc.). (Paper towel dispensers - 43-1/2” high.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-34-1 (originally 86-400)

47


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-34-2 (originally 87-400)

48


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

35. Doors - Biologic Sciences Men’s Restroom on the 3rd Floor.

Memo:

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (11 lbs.)

Recommendation:

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.

Photo #UCR P5186 Biological Sciences-35-1 (originally 88-400)

49


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

36. Clear Space at Doors - Biologic Sciences Men’s Restroom on the 3rd

Floor.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-36-1 (originally 89-400)

50


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

37. Identification Symbols, Restrooms - Biologic Sciences Men’s

Restroom on the 3rd Floor.

Memo:

Areas noted in compliance:

Door mounted signage: Men’s - Equilateral triangle with 12” sides, 1/4” thick with the vertex pointing up. The triangle

symbol contrasts with the door, light on dark background or dark on light background.

Signs are centered on door 60” from floor.

Areas not meeting new construction standards:

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door. (None.)

Recommendation:

Install wall-mounted sign at single entrance.

Photo #UCR P5186 Biological Sciences-37-1 (originally 90-400)

51


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

38. Multiple Accommodation Toilets - Biologic Sciences Men’s Restroom

on the 3rd Floor.

Memo:

Relocate the paper towel dispenser to provide 44” minimum clearance throughout restroom.

Areas noted in compliance:

60” min. diameter turning circle clear of objects from floor height to 27” in room.

3 second min. automatic closing door.

Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.

Door has loop or U-shaped handle immediately below latch on both inside and outside of door.

34” minimum opening at side.

The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.

The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.

The clear floor area on the push side of the door is the width of the door and a minimum 48” deep., measured perpendicular

to the door in its closed position.

If the compartment has an inward swinging, side opening door and contains a wall mounted water closet, the clearance

around the water closet is a minimum of 60” wide and and a minimum 56” deep that is clear of the stall door swing.

If the compartment has a side opening door, a minimum 60” wide x 60” deep clear floor space is provided in front

of the water closet.

60” minimum width of stall.

32” minimum from side of water closet to opposite wall or partition.

42” minimum from centerline of water closet to opposite wall or partition.

The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toilet

seat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).

Flush valve is on wide side of the water closet.

44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.

Front of toilet paper dispenser is within 36” of back wall.

19” minimum height to toilet paper dispenser.

Toilet paper dispenser provides continuous flow.

Areas not meeting new construction standards:

44” min. clear path provided throughout facility. (38” between the paper towel dispenser and stall.)

18” betwen centerline of water closet and side wall or partition. (19-1/4”.)

52


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet

seat. (Above.)

Recommendation:

Relocate water closet.

Relocate toilet paper dispenser.

Photo #UCR P5186 Biological Sciences-38-1 (originally 91-400)

53


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-38-2 (originally 92-400)

54


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

39. Toilet Grab Bars - Biologic Sciences Men’s Restroom on the 3rd

Floor.

Memo:

See Sequence #38 for additional recommendations.

Areas noted in compliance:

1-1/4” to 1-1/2” diameter of bars.

1-1/2” clearance between bars and each wall or partition.

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for

tank type toilets, 36” may be allowed if tank obstructs placement of bar).

Side bar has 42” min. length.

Side bar begins a max. of 12” from back wall.

Back bar has 36” min. length.

Back bar begins a max. of 6” from side wall.

Bars are smooth with a min. edge radius of 1/8”.

Grab bars do not rotate within their fittings.

Min. structural strength to support 250 lb. point load.

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.

Areas not meeting new construction standards:

The front of the side grab bar extends 52” from back wall in multiple accommodation restroom. (49-1/2”.)

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed

items are allowed). (Toilet paper dispenser.)

Recommendation:

Relocate grab bar.

55


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-39-1 (originally 93-400)

Photo #UCR P5186 Biological Sciences-39-2 (originally 94-400)

56


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

40. Lavatories - Biologic Sciences Men’s Restroom on the 3rd Floor.

Memo:

Areas noted in compliance:

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this

space).

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.

18” minimum from center of fixture to side wall or partition.

34” max. height to rim or counter above floor surface.

29” min. clearance from bottom of apron to floor surface.

30” wide x 9” high x 17” deep clearance from front of lavatory.

Drain and piping is insulated or configured to prevent contact.

There are no sharp or abrasive elements under lavatory.

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.

Areas not meeting new construction standards:

27” high x 8” deep knee clearance under front lip. (26-1/2” high.)

5 lb. max. force required to operate controls. (11 lbs.)

Recommendation:

Raise/Lower existing multiple lavatory counter.

Reduce force needed to operate faucet controls (5 lb. maximum).

57


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-40-1 (originally 95-400)

58


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

41. Urinals - Biologic Sciences Men’s Restroom on the 3rd Floor.

Memo:

Areas noted in compliance:

A clear floor space that is a minimum 30” wide by 48” deep is provided in front of the urinal to allow forward approach.

17” maximum urinal rim height above the finished floor.

14” minimum projection and 17” maximum projection from the wall.

44” maximum height to flush valve above finished floor.

5 lb max. pressure to operate valve.

Walls within 24” of front and sides of urinals are smooth, hard and non-absorbent to 48” height, and are not adversely

affected by moisture.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-41-1 (originally 96-400)

59


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

42. Accessories - Biologic Sciences Men’s Restroom on the 3rd Floor.

Memo:

Paper towel dispenser is protruding. See Sequence #38 for recommendations.

Areas noted in compliance:

40” maximum height to bottom of reflective surface of mirror.

height above floor surface is recom-

Coat hooks and shelving are located within appropriate reach ranges (48” max.

mended).

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.

A maximum of 5 lbs. force is required to operate mechanisms.

Areas not meeting new construction standards:

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste

recepatacles, etc.). (Paper towel dispensers - 42-1/2”.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-42-1 (originally 97-400)

60


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-42-2 (originally 98-400)

61


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

43. Water Fountains (Drinking) - 2nd Floor Administration Hall.

Memo:

Areas noted in compliance:

32” minimum wide and 18” minimum deep alcove provided.

18” minimum depth of fountain.

9” high x 17” deep toe clearance.

Lever or push bar control is located 6” max. from front edge.

Bubbler outlet is 6” maximum from front.

Bubbler outlet is 36” maximum from floor.

The force required to activate controls does not exceed 5lbf.

Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty

bending or stooping.

Areas not meeting new construction standards:

27” high x 8” deep clear knee space under fountain. (26-3/4” high.)

Stream of bubbler is parallel to front edge. (On angle.)

4” minimum height of stream. (3”.)

Recommendation:

Raise/Lower existing drinking fountain.

Adjust water pressure of existing fountain.

Adjust angle of stream.

62


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-43-1 (originally 99-400)

63


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

44. Doors - Women’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (10 lbs.)

Recommendation:

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.

Photo #UCR P5186 Biological Sciences-44-1 (originally 100-400)

64


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

45. Clear Space at Doors - Women’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-45-1 (originally 101-400)

65


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

46. Identification Symbols, Restrooms - Women’s Restroom on the 2nd

Floor.

Memo:

Areas noted in compliance:

Women’s - 12” diameter circle 1/4” thick. The circle symbol contrasts with the door, light on dark background or dark

on light background.

Signs are centered on door 60” from floor.

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door.

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal

identification and the border dimensions of this pictogram is a minimum of 6” in height.

Characters are min. of 5/8” high and max. of 2” high.

Letters and numerals are raised 1/32” sans-serif upper case and accompanied by Grade 2 Braille.

Signs are centered on the wall 60” from floor.

Mounting location allows a person to approach within 3” of signage without encountering protruding objects or standing

within the swing of the door.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

66


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-46-1 (originally 102-400)

67


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

47. Multiple Accommodation Toilets - Women’s Restroom on the 2nd

Floor.

Memo:

Relocate the paper towel dispenser to provide 44” minimum clearance throughout restroom.

Areas noted in compliance:

60” min. diameter turning circle clear of objects from floor height to 27” in room.

3 second min. automatic closing door.

Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.

Door has loop or U-shaped handle immediately below latch on both inside and outside of door.

34” minimum opening at side.

The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.

The clear floor area on the push side of the door is the width of the door and a minimum 48” deep., measured perpendicular

to the door in its closed position.

32” minimum from side of water closet to opposite wall or partition.

42” minimum from centerline of water closet to opposite wall or partition.

The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toilet

seat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).

Flush valve is on wide side of the water closet.

44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.

Front of toilet paper dispenser is within 36” of back wall.

19” minimum height to toilet paper dispenser.

Toilet paper dispenser provides continuous flow.

Areas not meeting new construction standards:

44” min. clear path provided throughout facility. (38” to the paper towel dispenser.)

The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.

(59”.)

If the compartment has an inward swinging, side opening door and contains a wall mounted water closet, the clearance

around the water closet is a minimum of 60” wide and and a minimum 56” deep that is clear of the stall door swing.

(59” wide.)

If the compartment has a side opening door, a minimum 60” wide x 60” deep clear floor space is provided in front

of the water closet. (59” wide.)

60” minimum width of stall. (59”.)

68


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

18” betwen centerline of water closet and side wall or partition. (19-1/2”.)

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet

seat. (Above.)

Recommendation:

Relocate toilet partition.

Relocate water closet.

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.

Relocate the paper towel dispenser / hand dryer.

Photo #UCR P5186 Biological Sciences-47-1 (originally 103-400)

69


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-47-2 (originally 104-400)

70


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

48. Toilet Grab Bars - Women’s Restroom on the 2nd Floor.

Memo:

See Sequence #47 for recommendations.

Areas noted in compliance:

1-1/4” to 1-1/2” diameter of bars.

1-1/2” clearance between bars and each wall or partition.

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for

tank type toilets, 36” may be allowed if tank obstructs placement of bar).

Side bar has 42” min. length.

The front of the side grab bar extends 52” from back wall in multiple accommodation restroom.

Side bar begins a max. of 12” from back wall.

Back bar has 36” min. length.

Back bar begins a max. of 6” from side wall.

Bars are smooth with a min. edge radius of 1/8”.

Grab bars do not rotate within their fittings.

Min. structural strength to support 250 lb. point load.

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.

Areas not meeting new construction standards:

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed items

are allowed). (Toilet paper dispenser.)

Recommendation:

None.

71


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-48-1 (originally 105-400)

72


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

49. Lavatories - Women’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this

space).

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.

34” max. height to rim or counter above floor surface.

30” wide x 9” high x 17” deep clearance from front of lavatory.

Drain and piping is insulated or configured to prevent contact.

There are no sharp or abrasive elements under lavatory.

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.

Areas not meeting new construction standards:

18” minimum from center of fixture to side wall or partition. (17-1/2”.)

29” min. clearance from bottom of apron to floor surface. (28-3/4”.)

27” high x 8” deep knee clearance under front lip. (26-1/4”.)

5 lb. max. force required to operate controls. (10 lbs.)

Recommendation:

Relocate existing lavatory.

Raise/Lower existing multiple lavatory counter.

Reduce force needed to operate faucet controls (5 lb. maximum).

73


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-49-1 (originally 106-400)

74


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

50. Accessories - Women’s Restroom on the 2nd Floor.

Memo:

See Sequence #47 for recommendations.

Areas noted in compliance:

40” maximum height to bottom of reflective surface of mirror.

height above floor surface is recom-

Coat hooks and shelving are located within appropriate reach ranges (48” max.

mended).

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.

A maximum of 5 lbs. force is required to operate mechanisms.

Areas not meeting new construction standards:

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste

recepatacles, etc.). (43” high.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-50-1 (originally 107-400)

75


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-50-2 (originally 108-400)

76


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

51. Doors - Men’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (9 lbs.)

Recommendation:

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.

Photo #UCR P5186 Biological Sciences-51-1 (originally 109-400)

77


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

52. Clear Space at Doors - Men’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-52-1 (originally 110-400)

78


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

53. Identification Symbols, Restrooms - Men’s Restroom on the 2nd

Floor.

Memo:

Areas noted in compliance:

Door mounted signage: Men’s - Equilateral triangle with 12” sides, 1/4” thick with the vertex pointing up. The triangle

symbol contrasts with the door, light on dark background or dark on light background.

Signs are centered on door 60” from floor.

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door.

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal

identification and the border dimensions of this pictogram is a minimum of 6” in height.

Characters are min. of 5/8” high and max. of 2” high.

Letters and numerals are raised 1/32” sans-serif upper case and accompanied by Grade 2 Braille.

Signs are centered on the wall 60” from floor.

Mounting location allows a person to approach within 3” of signage without encountering protruding objects or standing

within the swing of the door.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

79


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-53-1 (originally 111-400)

80


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

54. Multiple Accommodation Toilets - Men’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

60” min. diameter turning circle clear of objects from floor height to 27” in room.

3 second min. automatic closing door.

Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.

Door has loop or U-shaped handle immediately below latch on both inside and outside of door.

34” minimum opening at side.

The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.

The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.

The clear floor area on the push side of the door is the width of the door and a minimum 48” deep., measured perpendicular

to the door in its closed position.

If the compartment has an inward swinging, side opening door and contains a wall mounted water closet, the clearance

around the water closet is a minimum of 60” wide and and a minimum 56” deep that is clear of the stall door swing.

If the compartment has a side opening door, a minimum 60” wide x 60” deep clear floor space is provided in front

of the water closet.

60” minimum width of stall.

32” minimum from side of water closet to opposite wall or partition.

42” minimum from centerline of water closet to opposite wall or partition.

The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toilet

seat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).

Flush valve is on wide side of the water closet.

44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.

Front of toilet paper dispenser is within 36” of back wall.

19” minimum height to toilet paper dispenser.

Toilet paper dispenser provides continuous flow.

Areas not meeting new construction standards:

44” min. clear path provided throughout facility. (38” to the paper towel dispenser.)

18” betwen centerline of water closet and side wall or partition. (19-1/2”.)

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet

81


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

seat. (Above.)

Recommendation:

Relocate water closet.

Relocate toilet paper dispenser.

Relocate the paper towel dispenser / hand dryer.

Photo #UCR P5186 Biological Sciences-54-1 (originally 112-400)

82


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-54-2 (originally 113-400)

83


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

55. Toilet Grab Bars - Men’s Restroom on the 2nd Floor.

Memo:

See Sequence #54 for additional recommendations.

Areas noted in compliance:

1-1/4” to 1-1/2” diameter of bars.

1-1/2” clearance between bars and each wall or partition.

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for

tank type toilets, 36” may be allowed if tank obstructs placement of bar).

Side bar has 42” min. length.

Side bar begins a max. of 12” from back wall.

Back bar has 36” min. length.

Back bar begins a max. of 6” from side wall.

Bars are smooth with a min. edge radius of 1/8”.

Grab bars do not rotate within their fittings.

Min. structural strength to support 250 lb. point load.

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.

Areas not meeting new construction standards:

The front of the side grab bar extends 52” from back wall in multiple accommodation restroom. (51-1/4”.)

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed

items are allowed). (11-1/4” to toilet paper.)

Recommendation:

Relocate grab bar.

84


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-55-1 (originally 114-400)

85


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

56. Lavatories - Men’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this

space).

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.

18” minimum from center of fixture to side wall or partition.

34” max. height to rim or counter above floor surface.

29” min. clearance from bottom of apron to floor surface.

27” high x 8” deep knee clearance under front lip.

30” wide x 9” high x 17” deep clearance from front of lavatory.

Drain and piping is insulated or configured to prevent contact.

There are no sharp or abrasive elements under lavatory.

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).

Faucets are operable with one hand and do not require tight grasping, pinching or twisting of wrist.

Areas not meeting new construction standards:

5 lb. max. force required to operate controls. (6 - 7 lbs.)

Recommendation:

Reduce force needed to operate faucet controls (5 lb. maximum).

86


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-56-1 (originally 115-400)

87


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

57. Urinals - Men’s Restroom on the 2nd Floor.

Memo:

Areas noted in compliance:

A clear floor space that is a minimum 30” wide by 48” deep is provided in front of the urinal to allow forward approach.

17” maximum urinal rim height above the finished floor.

14” minimum projection and 17” maximum projection from the wall.

44” maximum height to flush valve above finished floor.

5 lb max. pressure to operate valve.

Walls within 24” of front and sides of urinals are smooth, hard and non-absorbent to 48” height, and are not adversely

affected by moisture.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-57-1 (originally 116-400)

88


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

58. Accessories - Men’s Restroom on the 2nd Floor.

Memo:

See Sequence #54 for recommendations.

Areas noted in compliance:

40” maximum height to bottom of reflective surface of mirror.

height above floor surface is recom-

Coat hooks and shelving are located within appropriate reach ranges (48” max.

mended).

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.

A maximum of 5 lbs. force is required to operate mechanisms.

Areas not meeting new construction standards:

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste

recepatacles, etc.). (Paper towel dispenser - 42”.)

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-58-1 (originally 117-400)

89


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-58-2 (originally 118-400)

90


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

59. Sales and Service Counters - 2nd Floor Lobby.

Memo:

Protruding objects at counter - 7”. All counters should be reviewed.

Areas noted in compliance:

A minimum 30” x 48” clear floor space is provided at the counter and;

One full unobstructed side of the clear floor space adjoins or overlaps an accessible route.

Areas not meeting new construction standards:

A portion of the counter is a minimum of 36” in length, at a height between 28” - 34” above the floor and; (43-1/2”.)

Recommendation:

Install cane detectable barrier below object.

Photo #UCR P5186 Biological Sciences-59-1 (originally 119-400)

91


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-59-2 (originally 120-400)

92


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

60. Water Fountains (Drinking) - Biological Science 1st Floor.

Memo:

Areas noted in compliance:

32” minimum wide and 18” minimum deep alcove provided.

18” minimum depth of fountain.

27” high x 8” deep clear knee space under fountain.

9” high x 17” deep toe clearance.

Lever or push bar control is located 6” max. from front edge.

Bubbler outlet is 6” maximum from front.

Bubbler outlet is 36” maximum from floor.

The force required to activate controls does not exceed 5lbf.

Two fountains are provided, one that is wheelchair accessible and one at normal height for those persons having difficulty

bending or stooping.

Areas not meeting new construction standards:

Stream of bubbler is parallel to front edge. (On angle.)

4” minimum height of stream. (3”.)

Recommendation:

Adjust water pressure of existing fountain.

Adjust angle of stream.

93


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-60-1 (originally 121-400)

94


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

61. Doors - Men’s Restroom at Biological Science 1st Floor.

Memo:

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (11 lbs.)

Recommendation:

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.

Photo #UCR P5186 Biological Sciences-61-1 (originally 122-400)

95


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

62. Clear Space at Doors - Men’s Restroom at Biological Science 1st

Floor.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-62-1 (originally 123-400)

96


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

63. Identification Symbols, Restrooms - Men’s Restroom at Biological

Science 1st Floor.

Memo:

Areas noted in compliance:

Door mounted signage: Men’s - Equilateral triangle with 12” sides, 1/4” thick with the vertex pointing up. The triangle

symbol contrasts with the door, light on dark background or dark on light background.

Signs are centered on door 60” from floor.

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door.

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal

identification and the border dimensions of this pictogram is a minimum of 6” in height.

Characters are min. of 5/8” high and max. of 2” high.

Letters and numerals are raised 1/32” sans-serif upper case and accompanied by Grade 2 Braille.

Signs are centered on the wall 60” from floor.

Mounting location allows a person to approach within 3” of signage without encountering protruding objects or standing

within the swing of the door.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

97


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-63-1 (originally 124-400)

98


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

64. Multiple Accommodation Toilets - Men’s Restroom at Biological

Science 1st Floor.

Memo:

Areas noted in compliance:

60” min. diameter turning circle clear of objects from floor height to 27” in room.

44” min. clear path provided throughout facility.

3 second min. automatic closing door.

Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.

Door has loop or U-shaped handle immediately below latch on both inside and outside of door.

34” minimum opening at side.

The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.

The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.

The clear floor area on the push side of the door is the width of the door and a minimum 48” deep., measured perpendicular

to the door in its closed position.

If the compartment has an inward swinging, side opening door and contains a wall mounted water closet, the clearance

around the water closet is a minimum of 60” wide and and a minimum 56” deep that is clear of the stall door swing.

If the compartment has a side opening door, a minimum 60” wide x 60” deep clear floor space is provided in front

of the water closet.

60” minimum width of stall.

18” betwen centerline of water closet and side wall or partition. (18-1/4” (within dimensional tolerance).)

32” minimum from side of water closet to opposite wall or partition.

42” minimum from centerline of water closet to opposite wall or partition.

The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toilet

seat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).

Flush valve is on wide side of the water closet.

44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.

Front of toilet paper dispenser is within 36” of back wall.

19” minimum height to toilet paper dispenser.

Toilet paper dispenser provides continuous flow.

99


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Areas not meeting new construction standards:

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet seat.

(Above grab bar.)

Recommendation:

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.

Photo #UCR P5186 Biological Sciences-64-1 (originally 125-400)

Photo #UCR P5186 Biological Sciences-64-2 (originally 126-400)

100


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

65. Toilet Grab Bars - Men’s Restroom at Biological Science 1st Floor.

Memo:

See Sequence #64 for additional recommendation.

Areas noted in compliance:

1-1/4” to 1-1/2” diameter of bars.

1-1/2” clearance between bars and each wall or partition.

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for

tank type toilets, 36” may be allowed if tank obstructs placement of bar).

Side bar has 42” min. length.

Side bar begins a max. of 12” from back wall.

Back bar has 36” min. length.

Back bar begins a max. of 6” from side wall.

Bars are smooth with a min. edge radius of 1/8”.

Grab bars do not rotate within their fittings.

Min. structural strength to support 250 lb. point load.

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.

Areas not meeting new construction standards:

The front of the side grab bar extends 52” from back wall in multiple accommodation restroom. (51”.)

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed

items are allowed). (Toilet paper dispenser.)

Recommendation:

Relocate grab bar.

101


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-65-1 (originally 127-400)

102


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

66. Lavatories - Men’s Restroom at Biological Science 1st Floor.

Memo:

Areas noted in compliance:

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this

space).

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.

18” minimum from center of fixture to side wall or partition.

34” max. height to rim or counter above floor surface.

29” min. clearance from bottom of apron to floor surface.

30” wide x 9” high x 17” deep clearance from front of lavatory.

Drain and piping is insulated or configured to prevent contact.

There are no sharp or abrasive elements under lavatory.

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).

Areas not meeting new construction standards:

27” high x 8” deep knee clearance under front lip. (26-1/2”.)

Recommendation:

Raise/Lower existing multiple lavatory counter.

Photo #UCR P5186 Biological Sciences-66-1 (originally 128-400)

103


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

67. Urinals - Men’s Restroom at Biological Science 1st Floor.

Memo:

Areas noted in compliance:

A clear floor space that is a minimum 30” wide by 48” deep is provided in front of the urinal to allow forward approach.

17” maximum urinal rim height above the finished floor.

14” minimum projection and 17” maximum projection from the wall.

44” maximum height to flush valve above finished floor.

5 lb max. pressure to operate valve.

Walls within 24” of front and sides of urinals are smooth, hard and non-absorbent to 48” height, and are not adversely

affected by moisture.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-67-1 (originally 129-400)

104


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

68. Accessories - Men’s Restroom at Biological Science 1st Floor.

Memo:

Areas noted in compliance:

40” maximum height to bottom of reflective surface of mirror. (38”.)

height above floor surface is recom-

Coat hooks and shelving are located within appropriate reach ranges (48” max.

mended).

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.

A maximum of 5 lbs. force is required to operate mechanisms.

Areas not meeting new construction standards:

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste

recepatacles, etc.). (Paper towel dispenser - 41”.)

Recommendation:

Relocate the paper towel dispenser / hand dryer.

Photo #UCR P5186 Biological Sciences-68-1 (originally 130-400)

105


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-68-2 (originally 131-400)

106


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

69. Doors - Women’s Restroom at Biological Science 1st Floor.

Memo:

Areas noted in compliance:

Opens a min. of 90 degrees.

1/4” maximum vertical threshold or 1/2” beveled at 1:2.

32” minimum clear width of doorway.

Door hardware is operable with a single effort (lever type, panic bar or push pull type).

Hardware is 30” to 44” above floor.

3 seconds minimum for door closer to close from 70 degree position to within 3” of the latch.

Bottom 10” of door (except automatic or sliding doors) has a smooth uninterrupted surface that allows door to be

opened by a wheelchair footrest without creating a trap or hazardous condition (kick plate).

Areas not meeting new construction standards:

5 lb. maximum pressure to operate interior doors. (12 lbs.)

Recommendation:

Adjust door for opening pressure/closing times unless accepted by DSA / Fire Life Safety.

Photo #UCR P5186 Biological Sciences-69-1 (originally 132-400)

107


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

70. Clear Space at Doors - Women’s Restroom at Biological Science 1st

Floor.

Memo:

Areas noted in compliance:

Floor or landing is level and clear (2% max. slope).

60” min. clear space in direction of door swing.

44” min. clear space opposite direction of door swing (48” with latch and closer).

Minimum strike side clearance on PULL side of door: 18” interior doors, front approach.

Minimum strike side clearance on PUSH side of door: 12” front approach with latch and closer.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

Photo #UCR P5186 Biological Sciences-70-1 (originally 133-400)

108


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

71. Identification Symbols, Restrooms - Women’s Restroom at Biological

Science 1st Floor.

Memo:

Areas noted in compliance:

Women’s - 12” diameter circle 1/4” thick. The circle symbol contrasts with the door, light on dark background or dark

on light background.

Signs are centered on door 60” from floor.

Wall mounted signage: Symbol of accessibility is mounted on wall sign adjacent to latch side of door.

Verbal description as to restroom usage is placed directly below the pictogram, if utilized in conjunction with verbal

identification and the border dimensions of this pictogram is a minimum of 6” in height.

Characters are min. of 5/8” high and max. of 2” high.

Letters and numerals are raised 1/32” sans-serif upper case and accompanied by Grade 2 Braille.

Signs are centered on the wall 60” from floor.

Mounting location allows a person to approach within 3” of signage without encountering protruding objects or standing

within the swing of the door.

Areas not meeting new construction standards:

None observed.

Recommendation:

None.

109


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-71-1 (originally 134-400)

110


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

72. Multiple Accommodation Toilets - Women’s Restroom at Biological

Science 1st Floor.

Memo:

Relocate the paper towel dispenser to provide 44” clearance throughout restroom.

Areas noted in compliance:

60” min. diameter turning circle clear of objects from floor height to 27” in room.

3 second min. automatic closing door.

Door latch is a flip-over style, sliding or other hardware not requiring tight grasping or twisting.

Door has loop or U-shaped handle immediately below latch on both inside and outside of door.

34” minimum opening at side.

The clear floor area on the pull side of the door within the stall is the width of the door and a minimum 60” deep.

The clear floor area on the strike side of the door within the stall is a minimum 18” wide and a minimum 60” deep.

The clear floor area on the push side of the door is the width of the door and a minimum 48” deep., measured perpendicular

to the door in its closed position.

If the compartment has an inward swinging, side opening door and contains a wall mounted water closet, the clearance

around the water closet is a minimum of 60” wide and and a minimum 56” deep that is clear of the stall door swing.

If the compartment has a side opening door, a minimum 60” wide x 60” deep clear floor space is provided in front

of the water closet.

60” minimum width of stall.

18” betwen centerline of water closet and side wall or partition.

32” minimum from side of water closet to opposite wall or partition.

42” minimum from centerline of water closet to opposite wall or partition.

The top of the toilet seat is 17” - 19” from the floor surface as measured to the top of a maximum 2” high toilet

seat (a 3” high seat shall be permitted only in alterations where the existing fixture is less than 15” high).

Flush valve is on wide side of the water closet.

44” maximum height to flush valve and 5 lb maximum force to operate the flush valve.

Front of toilet paper dispenser is within 36” of back wall.

19” minimum height to toilet paper dispenser.

Toilet paper dispenser provides continuous flow.

Areas not meeting new construction standards:

44” min. clear path provided throughout facility. (39-1/2” (see memo).)

111


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

The toilet paper dispenser is located on the side wall below the grab bar and within 12” of the front of the toilet

seat. (Above.)

Recommendation:

Relocate the toilet paper dispenser away from the top of the grab bars or proposed grab bars.

Relocate the paper towel dispenser / hand dryer.

Photo #UCR P5186 Biological Sciences-72-1 (originally 135-400)

112


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-72-2 (originally 136-400)

113


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

73. Toilet Grab Bars - Women’s Restroom at Biological Science 1st Floor.

Memo:

See Sequence #72 for additional recommendation.

Areas noted in compliance:

1-1/4” to 1-1/2” diameter of bars.

1-1/2” clearance between bars and each wall or partition.

The side grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor.

The rear grab bar is securely attached and is mounted at 33” to the center of the bar above and parallel to the floor (for

tank type toilets, 36” may be allowed if tank obstructs placement of bar).

Side bar has 42” min. length.

Side bar begins a max. of 12” from back wall.

Back bar has 36” min. length.

Back bar begins a max. of 6” from side wall.

Bars are smooth with a min. edge radius of 1/8”.

Grab bars do not rotate within their fittings.

Min. structural strength to support 250 lb. point load.

Surface of wall adjacent to grab bars are free of sharp or abrasive elements.

Areas not meeting new construction standards:

The front of the side grab bar extends 52” from back wall in multiple accommodation restroom. (51”.)

Area directly above grab bars or proposed grab bars is free of protruding obstructions to a height of 18” (recessed

items are allowed). (Toilet paper dispenser.)

Recommendation:

Relocate grab bar.

114


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-73-1 (originally 137-400)

115


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

74. Lavatories - Women’s Restroom at Biological Science 1st Floor.

Memo:

Areas noted in compliance:

30” x 48” min. clear space provided in front of lavatory that allows forward approach (doors may not encroach into this

space).

Required clear space extends 19” max. underneath the lavatory and adjoins or over laps an accessible route.

18” minimum from center of fixture to side wall or partition.

34” max. height to rim or counter above floor surface.

29” min. clearance from bottom of apron to floor surface.

30” wide x 9” high x 17” deep clearance from front of lavatory.

Drain and piping is insulated or configured to prevent contact.

There are no sharp or abrasive elements under lavatory.

Faucets are lever type, electronically activated or approved self closing valves (10 second open flow).

Areas not meeting new construction standards:

27” high x 8” deep knee clearance under front lip. (26-1/2”.)

Recommendation:

Raise/Lower existing multiple lavatory counter.

Photo #UCR P5186 Biological Sciences-74-1 (originally 139-400)

116


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

75. Accessories - Women’s Restroom at Biological Science 1st Floor.

Memo:

Areas noted in compliance:

40” maximum height to bottom of reflective surface of mirror.

height above floor surface is recom-

Coat hooks and shelving are located within appropriate reach ranges (48” max.

mended).

Accessories do not require tight grasping, pinching or twisting of the wrist to operate.

A minimum 30” x 48” minimum clear floor or ground space is provided to allow forward or parallel approach to accessories.

A maximum of 5 lbs. force is required to operate mechanisms.

Areas not meeting new construction standards:

40” max. height to all other fixtures (i.e., soap dispensers, towels, toilet seat covers, auto dryers, sanitary napkins, waste

recepatacles, etc.). (Soap dispenser - 41-1/2”.)

Recommendation:

Relocate the soap dispenser.

Photo #UCR P5186 Biological Sciences-75-1 (originally 139-400)

117


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

Photo #UCR P5186 Biological Sciences-75-2 (originally 140-400)

118


University of California at Riverside

Site Evaluation Survey

Report: UCR P5186 Biological Sciences in Riverside, CA

900 University Avenue

76. Seating, Tables and Work Surfaces - Room 105 Office Support on the

1st Floor.

Memo:

Table is non-compliant and further review is suggested.

Areas noted in compliance:

30” x 48” min. clear floor space is provided.

One full unobstructed side of clear floor space adjoins or overlaps an accessible route or another wheelchair clear floor space.

28” - 34” height of table or work surface that is 36” wide.

Areas not meeting new construction standards:

27” high, 30” wide and 19” deep knee clearance provided. (29” wide.)

Recommendation:

Provide accessible table.

Photo #UCR P5186 Biological Sciences-76-1 (originally 141-400)

119