PGD description Parameter<br />

description<br />

Default Limits Unit of<br />

measur<br />

ement<br />

Digital output logic Digital outlet logic set- NO NO/NC ---<br />

pCO1OEM 9<br />

up 9<br />

Digital output logic Digital outlet logic setup<br />

NO<br />

NO/NC<br />

---<br />

pCO1OEM 10<br />

10<br />

Digital output logic Digital outlet logic setup<br />

NO NO/NC ---<br />

pCO1OEM 11<br />

11<br />

Digital output logic Digital outlet logic setup<br />

NC NO/NC ---<br />

pCO1OEM 12<br />

12<br />

Supervisory system Serial communication RS485<br />

RS485 ---<br />

protocol type<br />

protocol selection<br />

RS232<br />

Modbus<br />

LonMark<br />

Supervisory system Communication speed 19200(RS485) 1200<br />

bps<br />

speed set-up to supervisor 2400<br />

4800<br />

9600(RS485)<br />

19200(RS485)<br />

Supervisory system Serial identification 1 1-200 ---<br />

identificat.Nr. address set-up<br />

FLRHSMCHIO V. Software version ---<br />

--- ---<br />

visualisation<br />

Please insert unlock Beta versions unlock 0 -32767/32767 ---<br />

code<br />

code<br />

Reset all parameters Start of the memory --- Y/N ---<br />

to default values delete process and<br />

default installation<br />

values<br />

Erase log Start of the alarm log --- Y/N ---<br />

memory delete<br />

process<br />

Insert another Adjust of the 228 0-9999 ---<br />

manufacturer parameters access<br />

password<br />

password<br />

Pump menu<br />

Main pump ON if Main pump working Unit ON Unit ON<br />

mode set-up<br />

Compressor ON<br />

Main pump switching Delay set-up at the 15 0-999 s<br />

off delay time main pump switch-off<br />

Time between main Devices activation 15<br />

0-999 s<br />

pump and delay set-up from the<br />

compressors start start of the main pump<br />

Pumps rotation time Rotation time among 999 0-999 H<br />

the pumps<br />

Test rotation<br />

Activation at the pump N N-Y ---<br />

rotation<br />

Test rotat.time Test<br />

times<br />

pumps rotation 1 0-999 m<br />

Pumps mode Pumps working mode Auto Auto – Only P1 – Only ---<br />

P2<br />

Compressor menu<br />

Minimum compressor Compressor working 60 0-9999 s<br />

<strong>Rhoss</strong> S.p.A. S.A.T.<br />

Rev. 1.0 20/01/05 48