PGD description Parameter<br />
description<br />
Default Limits Unit of<br />
measur<br />
ement<br />
Digital output logic Digital outlet logic set- NO NO/NC ---<br />
pCO1OEM 9<br />
up 9<br />
Digital output logic Digital outlet logic setup<br />
NO<br />
NO/NC<br />
---<br />
pCO1OEM 10<br />
10<br />
Digital output logic Digital outlet logic setup<br />
NO NO/NC ---<br />
pCO1OEM 11<br />
11<br />
Digital output logic Digital outlet logic setup<br />
NC NO/NC ---<br />
pCO1OEM 12<br />
12<br />
Supervisory system Serial communication RS485<br />
RS485 ---<br />
protocol type<br />
protocol selection<br />
RS232<br />
Modbus<br />
LonMark<br />
Supervisory system Communication speed 19200(RS485) 1200<br />
bps<br />
speed set-up to supervisor 2400<br />
4800<br />
9600(RS485)<br />
19200(RS485)<br />
Supervisory system Serial identification 1 1-200 ---<br />
identificat.Nr. address set-up<br />
FLRHSMCHIO V. Software version ---<br />
--- ---<br />
visualisation<br />
Please insert unlock Beta versions unlock 0 -32767/32767 ---<br />
code<br />
code<br />
Reset all parameters Start of the memory --- Y/N ---<br />
to default values delete process and<br />
default installation<br />
values<br />
Erase log Start of the alarm log --- Y/N ---<br />
memory delete<br />
process<br />
Insert another Adjust of the 228 0-9999 ---<br />
manufacturer parameters access<br />
password<br />
password<br />
Pump menu<br />
Main pump ON if Main pump working Unit ON Unit ON<br />
mode set-up<br />
Compressor ON<br />
Main pump switching Delay set-up at the 15 0-999 s<br />
off delay time main pump switch-off<br />
Time between main Devices activation 15<br />
0-999 s<br />
pump and delay set-up from the<br />
compressors start start of the main pump<br />
Pumps rotation time Rotation time among 999 0-999 H<br />
the pumps<br />
Test rotation<br />
Activation at the pump N N-Y ---<br />
rotation<br />
Test rotat.time Test<br />
times<br />
pumps rotation 1 0-999 m<br />
Pumps mode Pumps working mode Auto Auto – Only P1 – Only ---<br />
P2<br />
Compressor menu<br />
Minimum compressor Compressor working 60 0-9999 s<br />
<strong>Rhoss</strong> S.p.A. S.A.T.<br />
Rev. 1.0 20/01/05 48