1,000 – 13,000 m 3 /h<br />
<strong>GEA</strong> Unit Heaters > For retail und industry<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> ®<br />
Flexible, powerful, and diversified – for all requirements<br />
[130 kW]<br />
<strong>GEA</strong> Heat Exchangers / HVAC Systems
With <strong>GEA</strong> <strong>MultiMAXX</strong> for optimal solutions<br />
Efficiency and cost-effectiveness for<br />
decentral air treatment<br />
You can achieve your goal only by employing <strong>com</strong>ponents exactly matched to your requirements. The <strong>GEA</strong> <strong>MultiMAXX</strong> family offers<br />
the most reliable, most efficient, and most cost-effective solution for each profile of specifications. The great diversity of the individual<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> air-treatment <strong>com</strong>ponents is your guarantee for the optimal solution.<br />
Fans<br />
Sickle-blade fan, IP 54 Wide-blade fan, IP 54 Wide-blade fan, EEx Diagonal-blade fan, IP 54<br />
Heat exchangers<br />
Copper/Aluminum Copper/Copper Galvanized steel Stainless steel<br />
2 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> <strong>MultiMAXX</strong> unit heaters<br />
Planning freedom for decentral<br />
air handling<br />
In the planning of a decentral air-handling system, those exercising<br />
responsibility must be sure that carefully targeted<br />
and flawless solutions can be provided for simple as well as<br />
for highly specialized applications. And this is the reason why<br />
so many experts view the <strong>GEA</strong> <strong>MultiMAXX</strong> family as an absolute<br />
essential.<br />
Its name is program. Multifunctional application possibilities,<br />
application-specific materials properties, as well as demand-optimized<br />
air treatment <strong>com</strong>ponents provide the guarantee for the<br />
most efficient and cost-effective solution.<br />
Even the operation of a high-efficiency energy-recuperation system<br />
is a matter without difficulty with employment of the <strong>com</strong>plete<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> Ergo system. For more detailed information<br />
on these possibilities, please see our separate documentation.<br />
The short overview below shows what <strong>GEA</strong> makes possible, in<br />
the individual model ranges HN – HS – HX – HD – HE – HP *<br />
■ Housings – galvanized steel sheet, coated finish, or<br />
stainless steel<br />
■ Motors – IP 54 enclosure-protection class, with EEx e<br />
for enhanced safety, and EEx d in models with pressureresistant<br />
enclosures<br />
■ Fans – wide-, sickle-, and diagonal-blade versions<br />
■ Heat exchangers – Cu-Al, Cu-Cu- galvanized steel, stainless<br />
steel, electro<br />
■ Air-filter pads – filter grades G2 … G4 in accordance with EN 779<br />
■ Air-filter bags – filter grades G2 … F7 in accordance with EN 779<br />
■ Air intake – 23 versions for recirculated-air and mixed-air<br />
modules<br />
■ Air outlet – 13 versions, some with motor drive<br />
■ Heating function – pumped warm water (PWW)<br />
or pumped hot water (PHW)<br />
■ Cooling function – pumped chilled water (PCW),<br />
2-pipe system<br />
■ System control – <strong>GEA</strong> MATRIX<br />
* <br />
The HP sub-range is part of the HN range. HP models are on stock and can be delivered<br />
immediately.<br />
01/2010 – PR-2010-0003-GB · Subject to modification 3
Product overview<br />
Meets all requirements –<br />
For ceiling or wall installation<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> HN – the universal solution<br />
For employment in trade and industrial sectors, with<br />
the functions heating – cooling – ventilation<br />
■ Five model sizes: 1 – 5<br />
■ IP 54 motors – 1-phase, 230 V; 3-phase, 400 V;<br />
3-phase, 500 V; with 1, 2, and 3 speeds<br />
■ Fans – wide-blade and sickle-blade<br />
■ Heat exchangers – Cu-Al, Cu-Cu, galvanized steel,<br />
fully zinc-plated steel<br />
■ Enclosure – design or industrial versions<br />
(zinc-plated or coated)<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> HS – the hygienic solution<br />
For employment in applications with strict hygienic<br />
requirements, with the functions heating – cooling<br />
■ Four model sizes: 1 – 4<br />
■ IP 54 motors – 3-phase, 400 V; with 2 speeds<br />
■ Fans – wide-blade<br />
■ Heat exchangers – galvanized steel, fully zinc-plated steel,<br />
stainless steel<br />
■ Enclosure – industrial version (stainless steel)<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> HX – the ultra-safe solution<br />
For employment in applications in explosion-endangered areas,<br />
with the functions heating – ventilation – cooling<br />
■ Four model sizes: 1 – 4<br />
■ EEx motors – 3-phase, 400 V; 3-phase, 500 V;<br />
with 1 and 2 speeds; enhanced safety features;<br />
with pressure-resistant enclosure<br />
■ Fans – wide-blade<br />
■ Heat exchangers – Cu-Al, Cu-Cu, galvanized steel,<br />
fully zinc-plated steel, stainless steel<br />
■ Enclosure – industrial version (zinc-plated, coated,<br />
or stainless steel)<br />
4 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> <strong>MultiMAXX</strong> HD – the high-pressure solution<br />
For applications with high air-side resistance levels, and<br />
with F7-grade air filtration in accordance with VDI 6022 as<br />
option, with the functions heating – ventilation<br />
■ Four model sizes: 1 – 4<br />
■ IP 54 motors – 3-phase, 400 V; 3 speeds<br />
■ Fans – diagonal-blade<br />
■ Heat exchangers – Cu-Al, Cu-Cu, galvanized steel<br />
■ Enclosure – design or industrial versions (zinc-plated<br />
or coated)<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> HE – the electric unit heater<br />
For employment in areas without supply of warm water,<br />
with the functions heating – ventilation<br />
■ Three model sizes: 1, 2, and 4<br />
■ IP 54 motors – 3-phase, 400 V; 3-phase, 500 V * ;<br />
2 and 3 speeds *<br />
■ Fans – wide-blade and sickle-blade *<br />
■ Heat exchangers – Cu-Al, Cu-Cu, galvanized steel,<br />
fully zinc-plated steel<br />
■ Enclosure – industrial version (coated)<br />
*<br />
3-phase, 500 V only with sickle blades; 3 speeds for model size 2<br />
<strong>GEA</strong> <strong>MultiMAXX</strong> HP –<br />
the fast one, on stock in the logistics center<br />
Same as the <strong>GEA</strong> <strong>MultiMAXX</strong> HN model, but with predefined<br />
technical characteristics featuring only the heating<br />
function<br />
■ Three model sizes: 1 – 3<br />
■ IP 54 motors – 3-phase, 400 V; 2-speed<br />
■ Fans – wide-blade<br />
■ Heat exchanger – Cu-Al<br />
■ Enclosure – industrial versions (zinc-plated)<br />
■ Air outlets – wall basic, wall profile, ceiling basic,<br />
ceiling profile<br />
Since the characteristics of this model are limited as<br />
listed here, fast delivery from the logistics center is<br />
possible.<br />
01/2010 – PR-2010-0003-GB · Subject to modification 5
Thermal air-flow patterns<br />
Maximum efficiency from secondary air<br />
Great thermal lift, without including secondary air<br />
Ceiling temperature = 23 °C; height of hall-type room = 12 m<br />
0.6 m<br />
Limited air-projection range<br />
1.75 m<br />
Time required to heat<br />
up to the required<br />
temperature of 17 °C<br />
Air speed<br />
0.3 m/s<br />
Comfort zone<br />
Flow patterns on the air-outlet side, with standard air outlets<br />
6 01/2010 – PR-2010-0003-GB · Subject to modification
Optimized thermal lift as a result of including secondary air<br />
Ceiling temperature = 19 °C; height of hall-type room = 12 m<br />
0.2 m<br />
Variable air-projection range<br />
Air speed:<br />
variable from 4-10 m/s<br />
1.75 m<br />
Additional<br />
secondary air<br />
Air speed<br />
0.2 m/s<br />
Time required to heat<br />
up to the required<br />
temperature of 17 °C<br />
Comfort zone<br />
Flow patterns on the air-outlet side, with use of a secondary-air louver<br />
01/2010 – PR-2010-0003-GB · Subject to modification 7
<strong>GEA</strong> MATRIX – intelligent control technology<br />
Just the right turn for the right room climate<br />
If requested, the proven <strong>GEA</strong> MATRIX control unit will be integrated<br />
into the <strong>GEA</strong> <strong>MultiMAXX</strong> at the factory. Your benefit:<br />
only <strong>com</strong>pletely tested equipment will be supplied to your<br />
construction site.<br />
<strong>GEA</strong> MATRIX is available in configuration levels 2000, 3000, or<br />
4000, with adaptation to the various possible applications. Most<br />
of the versions are provided with the <strong>GEA</strong> MATRIX.Net dualcable<br />
bus system as default, through which all <strong>GEA</strong> MATRIX<br />
units can <strong>com</strong>municate with each other. As a result, it is simple<br />
to implement daytime and nighttime switching actions, and to<br />
control pumps and collect error messages at a single point. <strong>GEA</strong><br />
MATRIX can also be connected to higher-level bus systems.<br />
In addition, <strong>GEA</strong> MATRIX assures energy-optimized operation<br />
of the <strong>GEA</strong> <strong>MultiMAXX</strong>. By means of the summer <strong>com</strong>pensation<br />
function, <strong>GEA</strong> MATRIX takes into account outside-temperature<br />
influences and therefore prevents energy-intensive climate control.<br />
Comprehensive control possibilities<br />
■ Control functions in various expansion stages<br />
■ Bus interfaces to other equipment units<br />
■ Plug-and-play functionality<br />
■ Energy-optimized equipment operation<br />
■ Equipment ready to operate<br />
■ Highly <strong>com</strong>petent service<br />
■ Global add-on modules<br />
■ LON interface<br />
■ Service tools<br />
Hardware and software are developed entirely at <strong>GEA</strong>. As a result<br />
of close collaboration in the <strong>com</strong>pany, <strong>GEA</strong> engineers can<br />
systematically adjust the control system to match every <strong>com</strong>ponent<br />
– and in turn optimally exploit the possibilities of the units.<br />
<strong>GEA</strong> support staff also profit from this arrangement by being<br />
able to quickly and expertly react in case of any questions.<br />
Numerous additional global modules are available as function<br />
expansions of the standard-version local connections of the MA-<br />
TRIX control system. Examples here are: intra-group operator<br />
panels and clock modules, modules for activation control of exhaust-air<br />
fans and chillers, expansion of analog or digital input<br />
and output signals, 0 … 10-V outputs for valves, and integration<br />
into a LON bus system in accordance with the LonWorks standard.<br />
All modules can be simply integrated via the MATRIX.Net bus<br />
system. In addition, the service tools MATRIX.PDA and MA-<br />
TRIX.PC can be used for parameterization, initial startup, maintenance,<br />
and data recording from the MATRIX control system.<br />
8 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> MATRIX<br />
Operator panels<br />
Operator panel for MATRIX 2000<br />
MATRIX OP 21<br />
– Enclosure without display, pure white<br />
– Recirculated-air operation,<br />
IP 20 enclosure-protection class *<br />
– Desired-temperature setting<br />
– Fan-speed selection switch for permanent<br />
operating mode<br />
– Button for temperature-reduction mode<br />
– LED display: operation / malfunction /<br />
external influence<br />
– Integrated room-temperature sensor<br />
– MATRIX.Net data bus: network interface for MATRIX add-on<br />
module via operator panel OP 21<br />
Operator panels for MATRIX 3000 and MATRIX 4000<br />
Operator panels for MATRIX 3000 and MATRIX 4000<br />
MATRIX OP 31<br />
– Enclosure without display, pure white<br />
– Recirculated-air operation,<br />
IP 20 enclosure-protection class *<br />
– Desired-temperature setting<br />
– Button for temperature-reduction mode<br />
– Fan-speed selection switch for permanent /<br />
automatic operating modes<br />
– LED display: operation / malfunction /<br />
external influence<br />
– Integrated room-temperature sensor<br />
MATRIX OP 44<br />
Same as the OP31 control unit, but with<br />
– Switching for heating / cooling /<br />
automatic modes of operation<br />
– Switching for recirculated-air /<br />
mixed-air modes of operation<br />
All control units are without display.<br />
With protective cover as option.<br />
Operator panels for MATRIX 3000 and MATRIX 4000<br />
MATRIX OP 50 without clock<br />
MATRIX OP 51 with clock<br />
– Enclosure with display, pure white<br />
– Recirculated-air /<br />
mixed-air modes of operation<br />
– IP 20 enclosure-protection class *<br />
– Operation by rotary navigator<br />
– LCD display with plain text<br />
– Status report by pictograms<br />
– Integrated room-temperature sensor<br />
Operator panels for MATRIX 3000 and MATRIX 4000<br />
Example: IP 54 enclosure-protection class<br />
MATRIX OP 51<br />
– Function: same as IP 20 enclosureprotection<br />
class, but with loose enclosed<br />
room-temperature sensor<br />
*<br />
As option: IP 54 enclosure-protection class, with loose enclosed room-temperature sensor<br />
<strong>GEA</strong> Series MC thermostat/fan-speed selection switch<br />
Simple thermostat controls are also available for minimal control-system requirements.<br />
Optional with additional contacts for 2-point control activation of louvers and valves.<br />
MC303 MC303 MC302K MC333 Room thermostat IP 54<br />
01/2010 – PR-2010-0003-GB · Subject to modification 9
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Complete program<br />
Heating / cooling with <strong>GEA</strong> <strong>MultiMAXX</strong><br />
[5 system versions:<br />
HN, HS, HX, HD, HE]<br />
[5 model sizes] [5 – 100 kW]<br />
[1,000 – 13,000 m 3 /h]<br />
Decentral solutions for mixed und outdoor air<br />
With a <strong>com</strong>plete program for each area of operation, the <strong>GEA</strong> <strong>MultiMAXX</strong> system satisfies requirements placed on decentral air handling<br />
by users in trade, <strong>com</strong>merce, and industry. The HN and HX ranges furthermore make cooling operations possible via a 2-conductor<br />
change-over function: for both wall and for ceiling installation.<br />
10 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> MAXX Ergo<br />
System energy recuperation<br />
Energy recuperation with <strong>GEA</strong> MAXX Ergo<br />
[F7 outdoor-air filter]<br />
[7 – 44 kW] [3 model sizes]<br />
[12 duty levels]<br />
[1,000 – 7,700 m 3 /h]<br />
High-efficiency supply-air system with F7 filter<br />
The extraordinary <strong>com</strong>ponent diversity of <strong>GEA</strong> <strong>MultiMAXX</strong> is rounded off by the <strong>GEA</strong> MAXX Ergo, the high-efficiency energy-recuperation<br />
system. The <strong>GEA</strong> MAXX Ergo offers a high-efficiency liquid-coupled energy-recovery system for decentral ventilation of hall-type<br />
buildings: such as production floors, logistics facilities, and many other similar possibilities. Combined with the <strong>GEA</strong> MATRIX control<br />
system, the <strong>GEA</strong> MAXX Ergo implements a maximum of cost efficiency. For detailed information on this possibility, please consult our<br />
separate product brochures at www.gea-airtreatment.<strong>com</strong> This system is provided only as <strong>com</strong>plete assemblies, including extracted-air<br />
unit, hydraulics modules, and the <strong>GEA</strong> MATRIX control system.<br />
01/2010 – PR-2010-0003-GB · Subject to modification 11
HN range: heating<br />
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Model sizes IP 54 sickle-blade fan Duty<br />
1 2 3 4<br />
HN 1 Air flow for basic air outlet m³/h 2,460 2,170 1,970 1,830<br />
Air-projection range for wall installation m 8.4 6.3 5.2 4.5<br />
Heating duty kW 8 12 17 20<br />
Air flow for secondary-air louver m³/h 2,140 1,950 1,810 1,700<br />
Air-projection range for wall installation m 9.7 7.5 6.3 5.5<br />
Heating duty kW 7 12 16 19<br />
HN 2 Air flow for basic air outlet m³/h 3,810 3,630 3,410 3,240<br />
Air-projection range for wall installation m 9.3 7.5 6.5 5.7<br />
Heating duty kW 12 20 26 33<br />
Air flow for secondary-air louver m³/h 3,570 3,400 3,210 3,050<br />
Air-projection range for wall installation m 11.5 9.3 8.1 7.1<br />
Heating duty kW 12 19 25 32<br />
HN 3 Air flow for basic air outlet m³/h 5,890 5,450 5,080 4,770<br />
Air-projection range for wall installation m 10.1 7.9 6.8 5.9<br />
Heating duty kW 19 31 41 50<br />
Air flow for secondary-air louver m³/h 5,400 5,030 4,720 4,470<br />
Air-projection range m 12.4 9.8 8.4 7.4<br />
Heating duty kW 18 30 39 48<br />
HN 4 Air flow for basic air outlet m³/h 9,170 8,340 7,680 7,170<br />
Air-projection range for wall installation m 11.4 8.8 7.4 6.4<br />
Heating duty kW 29 47 61 76<br />
Air flow for secondary-air louver m³/h 8,250 7,610 7,100 6,700<br />
Air-projection range for wall installation m 13.5 10.6 9.0 7.9<br />
Heating duty kW 27 45 58 72<br />
HN 5 Air flow for basic air outlet m³/h 12,570 11,500 10,790 9,970<br />
Air-projection range for wall installation m 12.3 9.6 8.2 7.1<br />
Heating duty kW 39 63 84 104<br />
Air flow for secondary-air louver m³/h 11,420 10,580 10,020 9,330<br />
Air-projection range for wall installation m 15.2 12.0 10.4 9.0<br />
Heating duty kW 38 61 80 100<br />
System characteristics<br />
Sickle-blade fan<br />
3-speed motor; 3-phase 400 V; IP 54<br />
Fan-speed ranges: MAX – MED – MIN<br />
Technical data for MAX speed level<br />
Heat exchanger: Cu/Al<br />
Heating medium: PWW 70/50 °C; air entry 18 °C<br />
Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />
design enclosures width height depth weight level (Lw) level (Lp) 1<br />
Wall installation mm mm mm kg dB(A) dB(A)<br />
HN 1 642 642 571 34 … 38 72 58<br />
HN 2 738 738 586 41 … 47 75 60<br />
HN 3 866 866 587 58 … 68 73 59<br />
HN 4 1,026 1,026 667 82 … 98 78 64<br />
HN 5 1,154 1,154 649 108 … 129 80 66<br />
1<br />
Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />
12 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
HN range: heating or cooling<br />
Model sizes IP 54 wide-blade fan Duty<br />
1 2 3 4<br />
HN 1 Air flow for basic air outlet m³/h 1,900 1,640 1,460 1,330<br />
Air-projection range for wall installation m 6.7 5.6 4.1 3.5<br />
Heating / cooling duty kW 7/3 11/4 14/6 16/8<br />
Air flow for secondary-air louver m³/h 1,610 1,440 1,310 1,220<br />
Air-projection range for wall installation m 7.6 5.9 4.9 4.3<br />
Heating / cooling duty kW 6/2 10/4 13/6 15/8<br />
HN 2 Air flow for basic air outlet m³/h 3,160 2,780 2,470 2,220<br />
Air-projection range for wall installation m 7.9 6.0 5.0 4.3<br />
Heating / cooling duty kW 11/5 18/7 22/9 26/13<br />
Air flow for secondary-air louver m³/h 2,740 2,430 2,190 2,010<br />
Air-projection range for wall installation m 9.2 7.1 6.0 5.2<br />
Heating / cooling duty kW 11/4 16/6 20/8 24/12<br />
HN 3 Air flow for basic air outlet m³/h 4,860 4,350 3,940 3,620<br />
Air-projection range for wall installation m 8.6 6.6 5.5 4.8<br />
Heating / cooling duty kW 17/7 28/11 35/15 41/20<br />
Air flow for secondary-air louver m³/h 4,300 3,900 3,580 3,330<br />
Air-projection range for wall installation m 10.2 7.9 6.7 5.9<br />
Heating / cooling duty kW 16/7 26/10 33/14 39/19<br />
HN 4 Air flow for basic air outlet m³/h 7,680 6,990 6,390 5,870<br />
Air-projection range for wall installation m 9.8 7.2 6.4 5.5<br />
Heating / cooling duty kW 26/11 43/17 55/23 66/32<br />
Air flow for secondary-air louver m³/h 6,920 6,310 5,810 5,390<br />
Air-projection range for wall installation m 11.6 9.6 7.7 6.7<br />
Heating / cooling duty kW 25/10 41/16 51/22 62/31<br />
HN 5 Air flow for basic air outlet m³/h 9,210 8,630 8,030 7,530<br />
Air-projection range for wall installation m 9.4 7.6 6.5 5.7<br />
Heating / cooling duty kW 34/14 55/21 70/30 85/42<br />
Air flow for secondary-air louver m³/h 8,440 7,970 7,460 7,050<br />
Air-projection range for wall installation m 11.8 9.5 8.2 7.3<br />
Heating / cooling duty kW 33/13 53/21 67/29 82/40<br />
System characteristics<br />
Wide-blade fan<br />
2-speed motor; 3-phase 400 V; IP 54<br />
Fan-speed ranges: MED – MIN<br />
Technical data for MED speed level<br />
Heat exchanger: Cu/Al<br />
Heating medium: PWW 70/50 °C; air entry 18 °C<br />
Cooling medium: PCW 6 / 12 °C; air entry 27 °C / 46 %<br />
Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />
design enclosures width height depth weight level (Lw) level (Lp) 1<br />
Wall installation mm mm mm kg dB(A) dB(A)<br />
HN 1 642 665 631 33 ... 37 66 51<br />
HN 2 738 761 646 40 ... 46 67 53<br />
HN 3 866 889 647 57 ... 66 68 54<br />
HN 4 1,026 1,049 727 80 ... 96 73 59<br />
HN 5 1,154 1,177 709 106 ... 126 71 57<br />
1<br />
Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />
01/2010 – PR-2010-0003-GB · Subject to modification 13
HS range: heating<br />
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Model sizes IP 54 wide-blade fan Duty<br />
1 * 2 * 3 *<br />
HS 1 Air flow for basic air outlet m³/h 2,590 1,810 1,840<br />
Air-projection range for wall installation m 10.2 5.3 6.3<br />
Heating duty kW 5 12 7<br />
Air flow for profile-louver air outlet m³/h 2,280 1,710 1,730<br />
Air-projection range for wall installation m 11.1 6.1 7.2<br />
Heating duty kW 4 12 7<br />
Maximum weight kg 47 81 75<br />
HS 2 Air flow for basic air outlet m³/h 4,180 2,920 3,000<br />
Air-projection range for wall installation m 11.7 6.1 7.1<br />
Heating duty kW 8 20 13<br />
Air flow for profile-louver air outlet m³/h 3,690 2,730 2,800<br />
Air-projection range for wall installation m 12.7 6.9 8.0<br />
Heating duty kW 8 19 13<br />
Maximum weight kg 58 106 100<br />
HS 3 Air flow for basic air outlet m³/h 6,130 4,200 4,300<br />
Air-projection range for wall installation m 12.0 6.1 7.1<br />
Heating duty kW 13 31 22<br />
Air flow for profile-louver air outlet m³/h 5,380 3,940 4,020<br />
Air-projection range for wall installation m 13.0 7.0 8.0<br />
Heating duty kW 12 29 21<br />
Maximum weight 86 153 146<br />
HS 4 Air flow for basic air outlet m³/h 10,400 7,030 7,190<br />
Air-projection range for wall installation m 14.1 7.2 8.3<br />
Heating duty kW 22 52 36<br />
Air flow for profile-louver air outlet m³/h 9,000 6,620 6,740<br />
Air-projection range for wall installation m 15.0 8.1 9.4<br />
Heating duty kW 20 50 35<br />
Maximum weight kg 122 208 206<br />
System characteristics<br />
Wide-blade fan<br />
2-speed motor; 3-phase 400 V; IP 54<br />
Fan-speed ranges: MAX – MED<br />
Technical data for MAX speed level<br />
*<br />
LG 1 = heat exchanger 1RR, zinc-plated steel, with 6.0-mm louvers<br />
*<br />
LG 2 = heat exchanger 2RR, zinc-plated steel, with 3.0-mm louvers<br />
*<br />
LG 3 = heat exchanger 3RR, stainless steel V4a, with 2.8-mm louvers<br />
Heating medium: PWW 70/50 °C; air entry 18 °C<br />
Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />
industrial enclosures width height depth weight level (Lw) level (Lp) 1<br />
Wall installation mm mm mm kg dB(A) dB(A)<br />
HS 1 642 520 521 47 ... 81 71 67<br />
HS 2 738 616 536 58 ... 106 76 62<br />
HS 3 866 744 537 86 ... 153 76 62<br />
HS 4 1,026 904 617 122 ... 298 81 67<br />
1<br />
Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />
14 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
HX range: heating<br />
Model sizes IP 54 wide-blade fan EEx Duty<br />
1 2 3 4<br />
HX 1 Air flow for basic air outlet m³/h 2,660 2,340 2,130 1,980<br />
Air-projection range for wall installation m 9.0 6.7 5.5 4.8<br />
Heating duty kW 8 13 17 21<br />
Air flow for profile-louver air outlet m³/h 2,330 2,120 1,970 1,860<br />
Air-projection range for wall installation m 9.6 7.4 6.2 5.5<br />
Heating duty kW 7 12 17 20<br />
HX 2 Air flow for basic air outlet m³/h 4,300 3,990 3,710 3,450<br />
Air-projection range for wall installation m 10.3 8.1 6.9 6.0<br />
Heating duty kW 13 21 28 35<br />
Air flow for profile-louver air outlet m³/h 3,910 3,650 3,410 3,200<br />
Air-projection range for wall installation m 11.4 9.1 7.8 6.8<br />
Heating duty kW 12 20 26 33<br />
HX 3 Air flow for basic air outlet m³/h 5,800 5,190 4,740 4,390<br />
Air-projection range for wall installation m 10.0 7.6 6.4 5.6<br />
Heating duty kW 19 30 39 47<br />
Air flow for profile-louver air outlet m³/h 5,180 4,730 4,380 4,100<br />
Air-projection range for wall installation m 10.9 8.5 7.2 6.3<br />
Heating duty kW 18 29 37 45<br />
HX 4 Air flow for basic air outlet m³/h 9,190 8,230 7,530 6,990<br />
Air-projection range for wall installation m 11.4 8.7 7.3 6.3<br />
Heating duty kW 29 47 60 75<br />
Air flow for profile-louver air outlet m³/h 8,210 7,510 6,980 6,550<br />
Air-projection range for wall installation m 12.4 9.6 8.2 7.2<br />
Heating duty kW 27 44 57 71<br />
System characteristics<br />
Wide-blade fan EEx-e (safety class EEx-d upon request)<br />
2-speed motor; 3-phase 400 V – EEx-e<br />
Fan-speed ranges: MAX – MED<br />
Technical data for MAX speed level<br />
Heat exchanger: Cu/Al<br />
Heating medium: PWW 70/50 °C; air entry 18 °C<br />
Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />
industrial enclosures width height depth weight level (Lw) level (Lp) 1<br />
Wandmontage mm mm mm kg dB(A) dB(A)<br />
HX 1 642 520 521 32 … 36 71 57<br />
HX 2 738 616 536 40 … 46 75 61<br />
HX 3 866 744 537 57 … 67 73 59<br />
HX 4 1,026 904 617 83 … 99 80 66<br />
1<br />
Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />
01/2010 – PR-2010-0003-GB · Subject to modification 15
HD range: heating<br />
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Model sizes IP 54 diagonal-blade fan Duty<br />
1 2 3 4<br />
HD 1 Air flow for basic air outlet m³/h 2,800 2,600 2,440 2,430<br />
Air-projection range for wall installation m 9.4 7.3 6.1 5.6<br />
Heating duty kW 8 14 19 25<br />
Air flow for secondary-air louver m³/h 2,570 2,420 2,280 2,270<br />
Air-projection range for wall installation m 11.3 8.9 7.5 6.9<br />
Heating duty kW 8 13 18 23<br />
HD 2 Air flow for basic air outlet m³/h 4,680 4,350 4,080 3,850<br />
Air-projection range for wall installation m 11.1 8.8 7.5 6.5<br />
Heating duty kW 13 22 29 37<br />
Air flow for secondary-air louver m³/h 4,310 4,040 3,820 3,630<br />
Air-projection range for wall installation m 13.6 10.8 9.3 8.2<br />
Heating duty kW 13 21 28 36<br />
HD 3 Air flow for basic air outlet m³/h 6,610 6,340 6,100 5,880<br />
Air-projection range for wall installation m 11.2 9.0 7.8 7.0<br />
Heating duty kW 20 34 45 57<br />
Air flow for secondary-air louver m³/h 6,310 6,070 5,850 5,650<br />
Air-projection range for wall installation m 14.1 11.4 10.0 8.9<br />
Heating duty kW 19 33 44 56<br />
HD 4 Air flow for basic air outlet m³/h 13,350 12,610 11,980 11,430<br />
Air-projection range for wall installation m 15.7 12.4 10.7 9.3<br />
Heating duty kW 33 57 78 102<br />
Air flow for secondary-air louver m³/h 12,530 11,900 11,360 10,890<br />
Air-projection range for wall installation m 19.4 15.3 13.2 11.6<br />
Heating duty kW 32 56 76 99<br />
System characteristics<br />
Diagonal-blade fan<br />
3-speed motor; 3-phase 400 V; IP 54<br />
Fan-speed ranges: MAX – MED – MIN<br />
Technical data for MAX speed level<br />
Heat exchanger: Cu/Al<br />
Heating medium: PWW 70/50 °C; air entry 18 °C<br />
Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />
design enclosures width height depth weight level (Lw) level (Lp) 1<br />
Wall installation mm mm mm kg dB(A) dB(A)<br />
HD 1 642 642 852 54 … 58 77 63<br />
HD 2 738 738 975 76 … 83 79 65<br />
HD 3 866 866 1,076 103 … 114 84 70<br />
HD 4 1,026 1,026 1,236 159 … 175 89 75<br />
1<br />
Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />
HD range with high-efficiency energy recuperation via a liquid-coupled system, together with the <strong>GEA</strong> RoofJETT.<br />
For more details, please see the separate <strong>GEA</strong> MAXX Ergo documentation.<br />
Ceiling installation Model sizes Max. air flow (m³/h) Heat-recovery efficiency Ergo duty (kW)<br />
HD 2 2,300 63 % 36<br />
HD 3 3,800 54 % 52<br />
HD 4 7,700 50 % 65<br />
Data for the Ergo duty: taken from separate <strong>GEA</strong> MAXX Ergo documentation<br />
16 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
HE range: heating<br />
Model sizes IP 54 wide-blade fan Duty (heating levels)<br />
1 2 3<br />
HE 1 Air flow for basic air outlet m³/h 2,470 2,470 2,470<br />
Air-projection range for wall installation m 8.2 8.2 8.2<br />
Heating duty kW 4 8 12<br />
Air flow for profile-louver air outlet m³/h 2,200 2,200 2,200<br />
Air-projection range for wall installation m 8.8 8.8 8.8<br />
Heating duty kW 4 8 12<br />
Air flow for secondary-air louver m³/h 2,180 2,180 2,180<br />
Air-projection range for wall installation m 9.5 9.5 9.5<br />
Heating duty kW 4 8 12<br />
HE 2 Air flow for basic air outlet m³/h 3,980 3,980 3,980<br />
Air-projection range for wall installation m 9.3 9.3 9.3<br />
Heating duty kW 7 14 21<br />
Air flow for profile-louver air outlet m³/h 3,560 3,560 3,560<br />
Air-projection range for wall installation m 10.0 10.0 10.0<br />
Heating duty kW 7 14 21<br />
Air flow for secondary-air louver m³/h 3,520 3,520 3,520<br />
Air-projection range for wall installation m 10.8 10.8 10.8<br />
Heating duty kW 7 14 21<br />
HE 4 Air flow for basic air outlet m³/h 9,900 9,900 9,900<br />
Air-projection range for wall installation m 12.3 12.3 12.3<br />
Heating duty kW 14 28 42<br />
Air flow for profile-louver air outlet m³/h 8,800 8,800 8,800<br />
Air-projection range for wall installation m 13.1 13.1 13.1<br />
Heating duty kW 14 28 42<br />
Air flow for secondary-air louver m³/h 8,710 8,710 8,710<br />
Air-projection range for wall installation m 14.1 14.1 14.1<br />
Heating duty kW 14 28 42<br />
System characteristics<br />
Wide-blade fan<br />
2-speed motor; 3-phase 400 V; IP 54<br />
Fan-speed ranges: MAX – MED<br />
Technical data for MAX speed level<br />
Heat exchanger: electric heating battery<br />
Heating medium: 3-phase 400 V; operating range = -5 °C … +40 °C<br />
IP 42 enclosure-protection class (as per EN60529)<br />
Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />
industrial enclosures width height depth weight level (Lw) level (Lp) 1<br />
Wall installation mm mm mm kg dB(A) dB(A)<br />
HP 1 520 642 387 23 … 34 71 56<br />
HP 2 616 738 387 28 … 41 76 61<br />
HP 4 904 1,026 452 53 … 77 81 66<br />
1<br />
Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />
01/2010 – PR-2010-0003-GB · Subject to modification 17
HP range: heating (data from Series HN; delivery ex warehouse)<br />
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Model sizes IP 54 wide-blade fan Duty<br />
1 2<br />
HP 1 Air flow for basic air outlet m 3 /h – 2,200<br />
Air-projection range for wall installation m – 6.4<br />
Heating duty kW – 12<br />
Air flow for profile-louver air outlet m 3 /h – 2,010<br />
Air-projection range for wall installation m – 7.1<br />
Heating duty kW – 12<br />
Air flow for basic air outlet, 2 sides m 3 /h – 2,150<br />
Max. suspension height for ceiling installation m – 7.3<br />
Heating duty kW – 12<br />
HP 2 Air flow for basic air outlet m 3 /h – 3,620<br />
Air-projection range for wall installation m – 7.5<br />
Heating duty kW – 20<br />
Air flow for profile-louver air outlet m 3 /h – 3,280<br />
Air-projection range for wall installation m – 8.3<br />
Heating duty kW – 19<br />
Air flow for basic air outlet, 2 sides m 3 /h – 3,520<br />
Max. suspension height for ceiling installation m – 7.5<br />
Heating duty – 20<br />
HP 3 Air flow for basic air outlet m 3 /h 5,840 5,200<br />
Air-projection range for wall installation m 10.1 7.6<br />
Heating duty kW 19 30<br />
Air flow for profile-louver air outlet m 3 /h 5,180 4,720<br />
Air-projection range for wall installation m 10.9 8.5<br />
Heating duty kW 18 29<br />
Air flow for basic air outlet, 2 sides m 3 /h 5,660 5,070<br />
Max. suspension height for ceiling installation m 11.1 7.4<br />
Heating duty kW 18 30<br />
System characteristics<br />
Wide-blade fan<br />
2-speed motor; 3-phase 400 V; IP 54<br />
Fan-speed ranges: MAX – MED<br />
Technical data for MAX speed level<br />
Heat exchanger: Cu/Al<br />
Heating medium: PWW 70/50 °C; air entry 18 °C<br />
Dimensions for Model sizes Max. Max. Max. Max. Sound power Sound pressure<br />
industrial enclosures width height depth weight level (Lw) level (Lp) 1<br />
Wall installation mm mm mm kg dB(A) dB(A)<br />
HP 1 642 520 521 27 … 30 71 57<br />
HP 2 738 616 572 35 … 39 76 62<br />
HP 3 866 744 591 46 … 52 76 62<br />
Selection of available air outlets for Prompt units on stock in the warehouse.<br />
Wall basic Wall profile Ceiling basic Ceiling profile<br />
1<br />
Measuring parameters for the sound pressure level (Lp): interval = 5 m; space volume = 1,500 m³/h; reverberation time = 2 s; directional factor = 2<br />
18 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Wall versions of air outlets<br />
Air outlets for wall installation<br />
Type B<br />
Basic air-outlet louver<br />
Type P<br />
Profile air-outlet louver<br />
Type U<br />
Secondary-air louver<br />
Air outlets<br />
Model sizes Air-projection ranges Air flow V1 ... V9<br />
Wall version V1 V2 V3 V4 V5 V6 V7 V8 V9<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
1 3,000 2,700 2,400 2,100 1,800 1,500 1,200 900 600<br />
Air-projection range m m m m m m m m m<br />
Basic louver, 1-side Type B 9.3 8.7 8.0 7.3 6.6 5.8 5.0 4.1 3.2<br />
Profile louver Type P 11.1 10.4 9.6 8.8 7.9 7.0 6.0 5.0 3.8<br />
Secondary-air louver Type U 12.1 11.2 10.4 9.5 8.6 7.6 6.5 5.4 4.1<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
2 5,000 4,500 4,000 3,500 3,000 2,500 2,000 1,500 1,000<br />
Air-projection range m m m m m m m m m<br />
Basic louver, 1-side Type B 11.0 10.3 9.5 8.7 7.8 6.9 6.0 4.9 3.7<br />
Profile louver Type P 13.2 12.3 11.4 10.4 9.4 8.3 7.2 5.9 4.5<br />
Secondary-air louver Type U 14.4 13.4 12.4 11.3 10.2 9.1 7.8 6.4 4.9<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
3 7,000 6,300 5,600 4,900 4,200 3,500 2,800 2,100 1,400<br />
Air-projection range m m m m m m m m m<br />
Basic louver, 1-side Type B 11.2 10.4 9.6 8.8 7.9 7.0 6.0 5.0 3.8<br />
Profile louver Type P 13.4 12.5 11.5 10.6 9.5 8.4 7.3 6.0 4.6<br />
Secondary-air louver Type U 14.7 13.7 12.6 11.6 10.4 9.2 7.9 6.6 5.0<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
4 13,000 11,700 10,400 9,100 7,800 6,500 5,200 3,900 2,600<br />
Air-projection range m m m m m m m m m<br />
Basic louver, 1-side Type B 14.0 13.0 12.0 11.0 9.9 8.8 7.6 6.2 4.8<br />
Profile louver Type P 16.7 15.6 14.4 13.2 11.9 10.5 9.0 7.5 5.7<br />
Secondary-air louver Type U 18.2 16.9 15.6 14.3 12.9 11.4 9.8 8.1 6.2<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
5 13,000 11,700 10,400 9,100 7,800 6,500 5,200 3,900 2,600<br />
Air-projection range m m m m m m m m m<br />
Basic louver, 1-side Type B 12.3 11.5 10.6 9.7 8.7 7.7 6.7 5.5 4.2<br />
Profile louver Type P 14.7 13.7 12.6 11.6 10.4 9.2 7.9 6.6 5.0<br />
Secondary-air louver Type U 16.5 15.4 14.2 13.0 11.7 10.4 8.9 7.4 5.6<br />
The data on air-projection ranges applies to a warm-air flow that is 10 K above room temperature.<br />
01/2010 – PR-2010-0003-GB · Subject to modification 19
Ceiling versions of air outlets<br />
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Ceiling air outlets<br />
Type Z<br />
Basic air-outlet louver<br />
Type P<br />
Profile air-outlet louver<br />
Type C<br />
Secondary-air louver<br />
Air outlets<br />
Model sizes Suspension heights Air flow V1 ... V9<br />
Ceiling version V1 V2 V3 V4 V5 V6 V7 V8 V9<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
1 3,000 2,700 2,400 2,100 1,800 1,500 1,200 900 600<br />
Suspension height m m m m m m m m m<br />
Basic louver, 2-side Type Z 11.0 9.9 8.8 7.7 6.6 5.5 4.4 3.3 2.2<br />
Profile louver Type P 14.7 13.2 11.7 10.3 8.8 7.3 5.9 4.4 2.9<br />
Secondary-air louver Type C 20.2 18.2 16.2 14.2 12.1 10.1 8.1 6.1 4.0<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
2 5,000 4,500 4,000 3,500 3,000 2,500 2,000 1,500 1,000<br />
Suspension height m m m m m m m m m<br />
Basic louver, 2-side Type Z 13.7 12.3 11.0 9.6 8.2 6.9 5.5 4.1 2.7<br />
Profile louver Type P 18.3 16.5 14.7 12.8 11.0 9.2 7.3 5.5 3.7<br />
Secondary-air louver Type C 25.2 22.7 20.2 17.6 15.1 12.6 10.1 7.6 5.0<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
3 7,000 6,300 5,600 4,900 4,200 3,500 2,800 2,100 1,400<br />
Suspension height m m m m m m m m m<br />
Basic louver, 2-side Type Z 13.5 12.2 10.8 9.5 8.1 6.8 5.4 4.1 2.7<br />
Profile louver Type P 18.0 16.2 14.4 12.6 10.8 9.0 7.2 5.4 3.6<br />
Secondary-air louver Type C 24.8 22.4 19.9 17.4 14.9 12.4 9.9 7.5 5.0<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
4 13,000 11,700 10,400 9,100 7,800 6,500 5,200 3,900 2,600<br />
Suspension height m m m m m m m m m<br />
Basic louver, 2-side Type Z 17.9 16.1 14.3 12.5 10.7 8.9 7.2 5.4 3.6<br />
Profile louver Type P 24.0 21.6 19.2 16.8 14.4 12.0 9.6 7.2 4.8<br />
Secondary-air louver Type C 32.8 29.6 26.3 23.0 19.7 16.4 13.1 9.9 6.6<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
5 13,000 11,700 10,400 9,100 7,800 6,500 5,200 3,900 2,600<br />
Suspension height m m m m m m m m m<br />
Basic louver, 2-side Type Z 14.3 12.9 11.5 10.0 8.6 7.2 5.7 4.3 2.9<br />
Profile louver Type P 19.3 17.4 15.4 13.5 11.6 9.7 7.7 5.8 3.9<br />
Secondary-air louver Type C 26.5 23.8 21.2 18.5 15.9 13.2 10.6 7.9 5.3<br />
The data on suspension heights applies to a warm-air flow that is 10 K above room temperature.<br />
20 01/2010 – PR-2010-0003-GB · Subject to modification
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Ceiling versions of air outlets<br />
Ceiling air outlets<br />
Type L<br />
Air-deflection louver<br />
Type V<br />
Air outlet unit, 4 sides<br />
Type A<br />
Air outlet nozzle, square<br />
Type T<br />
Air outlet nozzle, rectangular<br />
Air outlets<br />
Model sizes Suspension heights Air flow V1 ... V9<br />
Ceiling version V1 V2 V3 V4 V5 V6 V7 V8 V9<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
1 3,000 2,700 2,400 2,100 1,800 1,500 1,200 900 600<br />
Suspension height m m m m m m m m m<br />
Air-deflection louver Type L 8.9 8.0 7.1 6.2 5.3 4.4 3.5 2.7 1.8<br />
Outlet to 4 sides Type V 6.2 5.6 4.9 4.3 3.7 3.1 2.5 1.9 1.2<br />
Square nozzle Type A 16.8 15.1 13.4 11.7 10.1 8.4 6.7 5.0 3.4<br />
Rectangular nozzle Type T 16.8 15.1 13.4 11.7 10.1 8.4 6.7 5.0 3.4<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
2 5,000 4,500 4,000 3,500 3,000 2,500 2,000 1,500 1,000<br />
Suspension height m m m m m m m m m<br />
Air-deflection louver Type L 11.0 9.9 8.8 7.7 6.6 5.5 4.4 3.3 2.2<br />
Outlet to 4 sides Type V 7.7 7.0 6.2 5.4 4.6 3.9 3.1 2.3 1.5<br />
Square nozzle Type A 21.0 18.9 16.8 14.7 12.6 10.5 8.4 6.3 4.2<br />
Rectangular nozzle Type T 21.0 18.9 16.8 14.7 12.6 10.5 8.4 6.3 4.2<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
3 7,000 6,300 5,600 4,900 4,200 3,500 2,800 2,100 1,400<br />
Suspension height m m m m m m m m m<br />
Air-deflection louver Type L 10.9 9.8 8.7 7.6 6.5 5.5 4.4 3.3 2.2<br />
Outlet to 4 sides Type V 7.7 6.9 6.1 5.4 4.6 3.8 3.1 2.3 1.5<br />
Square nozzle Type A 20.8 18.7 16.6 14.6 12.5 10.4 8.3 6.2 4.2<br />
Rectangular nozzle Type T 20.8 18.7 16.6 14.6 12.5 10.4 8.3 6.2 4.2<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
4 13,000 11,700 10,400 9,100 7,800 6,500 5,200 3,900 2,600<br />
Suspension height m m m m m m m m m<br />
Air-deflection louver Type L 14.5 13.0 11.6 10.1 8.7 7.2 5.8 4.3 2.9<br />
Outlet to 4 sides Type V 10.1 9.0 8.0 7.0 6.0 5.0 4.0 3.0 2.0<br />
Square nozzle Type A 27.5 24.7 22.0 19.2 16.5 13.7 11.0 8.2 5.5<br />
Rectangular nozzle Type T 27.5 24.7 22.0 19.2 16.5 13.7 11.0 8.2 5.5<br />
m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h m 3 /h<br />
5 13,000 11,700 10,400 9,100 7,800 6,500 5,200 3,900 2,600<br />
Suspension height m m m m m m m m m<br />
Air-deflection louver Type L 11.6 10.4 9.3 8.1 6.9 5.8 4.6 3.5 2.3<br />
Outlet to 4 sides Type V 8.1 7.3 6.5 5.7 4.9 4.0 3.2 2.4 1.6<br />
Square nozzle Type A 22.1 19.9 17.6 15.4 13.2 11.0 8.8 6.6 4.4<br />
Rectangular nozzle Type T 22.1 19.9 17.6 15.4 13.2 11.0 8.8 6.6 4.4<br />
The data on suspension heights applies to a warm-air flow that is 10 K above room temperature.<br />
01/2010 – PR-2010-0003-GB · Subject to modification 21
Versions of air-intake units<br />
<strong>GEA</strong> <strong>MultiMAXX</strong><br />
Air-intake modules<br />
Mat-filter module Bag-filter module Mixed-air module Blocking louvre, outdoor air<br />
Flexible intake connector<br />
Rectangular duct Duct bend Wall intake hood<br />
Wall weather-protection grate<br />
Spacer for<br />
wall openings<br />
Roof duct<br />
Roof air-intake hood<br />
Flat roof-duct base<br />
22 01/2010 – PR-2010-0003-GB · Subject to modification
Image broschure<br />
Application broschures<br />
Product broschures<br />
Data & Facts, as well as operation<br />
manuals (available only as PDF files)<br />
You are on this level of our documentation structure. From info@gea-airtreatment.<strong>com</strong><br />
you can order printed copies at no cost from the top three levels. Under www.geaairtreatment.<strong>com</strong><br />
you can download all brochures as PDF files.<br />
01/2010 – PR-2010-0003-GB · Subject to modification 23
w w w . g e a - a i r t r e a t m e n t . c o m