8.2.5.4.2. Delay after error in communication with SLAVE<br />

Function - Defines (in seconds) delay before reestablishing reading of<br />

registers in peripheral Slave devices after transmission errors.<br />

Time is counted independently for each defined area (Slave<br />

device) and reduces only the frequency of querying for areas with<br />

communication errors.<br />

Data type - number<br />

Range - 1…65535 [s]<br />

Default value 15 [s]<br />

Comments - Increasing this value reduces influence of malfunctioning devices<br />

on communication with other devices but decreases statistic time<br />

to reestablish communication after removal of error cause.<br />

8.2.5.4.3. Data block 1...16<br />

The table defining sequential data blocks read from attached to PORT2 peripheral Slave<br />

devices allows defining of 1 to 16 independent blocks in one or more devices. Consecutive<br />

blocks may encompass registers from different spaces and be refreshed at different<br />

intervals.<br />

8.2.5.4.3.1. Modbus ID of Slave device<br />

Function - Defines Modbus ID of Slave device from which configured data<br />

block is to be read<br />

Data type - number<br />

Range - 0…255<br />

Default value - 0<br />

Comments - setting Modbus ID to 0 (zero) switches the mapping off<br />

8.2.5.4.3.2. Space<br />

Function - selects Modbus space mapped from peripheral Slave device<br />

attached to PORT2<br />

Data type - selection list<br />

List - Bi In<br />

Binary inputs (1xxx), read-only<br />

Bi Out<br />

Binary outputs (0xxx), read and write<br />

Inp. Reg.<br />

Input Registers (3xxx), read-only<br />

Hold. Reg.<br />

Internal Registers (4xxx), read and write<br />

Default value - Bi In<br />

Comments - writing into registers mapping read-only spaces does not cause an<br />

error. Values will be replaced by next error-free reading from<br />

peripheral device.<br />