8.2.5.4.2. Delay after error in communication with SLAVE<br />
Function - Defines (in seconds) delay before reestablishing reading of<br />
registers in peripheral Slave devices after transmission errors.<br />
Time is counted independently for each defined area (Slave<br />
device) and reduces only the frequency of querying for areas with<br />
communication errors.<br />
Data type - number<br />
Range - 1…65535 [s]<br />
Default value 15 [s]<br />
Comments - Increasing this value reduces influence of malfunctioning devices<br />
on communication with other devices but decreases statistic time<br />
to reestablish communication after removal of error cause.<br />
8.2.5.4.3. Data block 1...16<br />
The table defining sequential data blocks read from attached to PORT2 peripheral Slave<br />
devices allows defining of 1 to 16 independent blocks in one or more devices. Consecutive<br />
blocks may encompass registers from different spaces and be refreshed at different<br />
intervals.<br />
8.2.5.4.3.1. Modbus ID of Slave device<br />
Function - Defines Modbus ID of Slave device from which configured data<br />
block is to be read<br />
Data type - number<br />
Range - 0…255<br />
Default value - 0<br />
Comments - setting Modbus ID to 0 (zero) switches the mapping off<br />
8.2.5.4.3.2. Space<br />
Function - selects Modbus space mapped from peripheral Slave device<br />
attached to PORT2<br />
Data type - selection list<br />
List - Bi In<br />
Binary inputs (1xxx), read-only<br />
Bi Out<br />
Binary outputs (0xxx), read and write<br />
Inp. Reg.<br />
Input Registers (3xxx), read-only<br />
Hold. Reg.<br />
Internal Registers (4xxx), read and write<br />
Default value - Bi In<br />
Comments - writing into registers mapping read-only spaces does not cause an<br />
error. Values will be replaced by next error-free reading from<br />
peripheral device.<br />