38CM Air Conditioning Unit Wiring Diagrams - Carrier
Wiring Diagrams
38CM
Air Conditioning Unit
CH (NOTE #9)
RED or BLK
RED or BLK
COMP BLU
L1
BLK C S H
208/23010
L2 11 21
POWER
YEL R C
SUPPLY
23 23
YEL
F
EQUIP
CONT
GND
OFM BRN
BLK
BLU
(SEE NOTE #14)
BLU
BLU
Y
G
CONNECTION DIAGRAM
LLS
R
YEL
CAP
BLK
VIO
BRN
YEL
BLK
BLU
BLU
YEL
BRN
SC
(NOTE #8)
BRN
HPS DTS LPS
T2
BLU BLU BLK BLK YEL YEL
LOGIC
T1 T3
BLK
BLK
IFR
CTD
C
R
ST
1 2
5
SR
EXTERNAL
POWER
SUPPLY
24 V
(NOTES #3 & #6)
CONT
CAP
CH
COMP
CTD
DTS
HPS
IFR
LLS
LPS
OFM
SC
SR
ST
- LEGEND -
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONTACTOR
CAPACITOR (DUAL RUN)
CRANKCASE HEATER
COMPRESSOR
COMPRESSOR TIME DELAY
DISCHARGE TEMP. SWITCH
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQ. LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
START CAPACITOR
START RELAY
START THERMISTOR
INDOOR
THERMOSTAT
(NOTE #5)
INDOOR
BLOWER
MOTOR
MAY BE FACTORY OR FIELD
INSTALLED
EQUIP
GND
Y
G
R
L1
INDOOR
THERMOSTAT
CH
CONT
11 21
5 2
1
SR
(SEE NOTE #14)
SCHEMATIC DIAGRAM
(LADDER FORM)
SC
HPS DTS LPS
IFR
R C
OFM
LLS
EXTERNAL
POWER
SUPPLY 24 V
R
C
H
S
C
F
CAP
COMP
CTD
ST
T2
LOGIC
T1 T3
L2
CONT
23 23
CONT
NOTES:
1. SYMBOLS ARE ELECTRICAL
REPRESENTATIONS ONLY.
2. COMPRESSOR AND FAN MOTOR FURNISHED
WITH INHERENT THERMAL PROTECTION.
3. TO BE WIRED IN ACCORDANCE WITH
NATIONAL ELECTRIC N.E.C. CODE AND
LOCAL CODES.
4. N.E.C. CLASS 2, 24 V CIRCUIT, MIN. 40 VA
REQUIRED, 60 VA ON UNITS INSTALLED
WITH LLS.
5. USE COPPER CONDUCTORS ONLY.
6. CONNECTION FOR TYPICAL COOLING ONLY
THERMOSTAT. FOR OTHER ARRANGEMENTS,
SEE INSTALLATION INSTRUCTIONS.
7. IF INDOOR SECTION HAS A TRANSFORMER
WITH A GROUNDED SECONDARY, CONNECT
THE GROUNDED SIDE TO THE BRN LEAD.
8. WHEN START RELAY AND START
CAPACITOR ARE INSTALLED, START
THERMISTOR IS NOT USED.
9. CH NOT USED ON ALL UNITS.
10.IF ANY OF THE ORIGINAL WIRE, AS
SUPPLIED, MUST BE REPLACED, USE THE
SAME OR EQUIVALENT WIRE.
11.CHECK ALL ELECTRICAL CONNECTIONS
INSIDE CONTROL BOX FOR TIGHTNESS.
12.DO NOT ATTEMPT TO OPERATE UNIT UNTIL
SERVICE VALVES HAVE BEEN OPENED.
13.DO NOT RAPID CYCLE COMPRESSOR.
COMPRESSOR MUST BE OFF 3 MINUTES TO
ALLOW PRESSURES TO EQUALIZE
BETWEEN HIGH AND LOW SIDE BEFORE
STARTING.
14.WIRE NOT PRESENT IF HPS, LPS, DTS OR
CTD ARE USED.
317738 - 401 REV. B
Fig. 1—38CM018-048 208-230v, 1 Phase, 60 Hertz
A93410
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 101 Catalog No. 563-781 Printed in U.S.A. Form 38CM-1W Pg 1 1-94 Replaces: New
Tab 3a 2a
CH (NOTE #9)
RED or BLK
RED or BLK
COMP BLU
CONT
L1
BLK C S H
208/23010
L2 11 21
POWER
R C
SUPPLY
13 23 YEL
YEL F
EQUIP
GND
OFM BRN
BLK
BLU
(SEE NOTE #14)
BLU
BLU
Y
G
CONNECTION DIAGRAM
LLS
R
BLK
VIO
HPS DTS LPS
BLU BLU BLK BLK YEL YEL
BLK
BLK
YEL
IFR
CAP
BRN
YEL
BLK
BLU
BLU
YEL
BRN
SC
(NOTE #8)
BRN
T2
LOGIC
T1 T3
CTD
C
R
ST
1 2
5
SR
EXTERNAL
POWER
SUPPLY
24 V
(NOTES #3 & #6)
CONT
CAP
CH
COMP
CTD
DTS
HPS
IFR
LLS
LPS
OFM
SC
SR
ST
- LEGEND -
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONTACTOR
CAPACITOR (DUAL RUN)
CRANKCASE HEATER
COMPRESSOR
COMPRESSOR TIME DELAY
DISCHARGE TEMP. SWITCH
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
LIQ. LINE SOLENOID VALVE
LOW PRESSURE SWITCH
OUTDOOR FAN MOTOR
START CAPACITOR
START RELAY
START THERMISTOR
INDOOR
THERMOSTAT
(NOTE #5)
INDOOR
BLOWER
MOTOR
MAY BE FACTORY OR FIELD
INSTALLED
EQUIP
GND
Y
G
R
L1
INDOOR
THERMOSTAT
CH
CONT
11 21
5 2
1
SR
(SEE NOTE #14)
SCHEMATIC DIAGRAM
(LADDER FORM)
SC
HPS DTS LPS
IFR
R C
OFM
LLS
EXTERNAL
POWER
SUPPLY 24 V
R
C
S
H
C
F
COMP
CAP
CTD
ST
T2
LOGIC
T1 T3
L2
CONT
23 13
CONT
NOTES:
1. SYMBOLS ARE ELECTRICAL
REPRESENTATION ONLY.
2. COMPRESSOR AND FAN MOTOR FURNISHED
WITH INHERENT THERMAL PROTECTION.
3. TO BE WIRED IN ACCORDANCE WITH
NATIONAL ELECTRIC N.E.C. AND LOCAL
CODES.
4. N.E.C. CLASS 2, 24 V CIRCUIT, MIN 40 VA
REQUIRED, 60 VA ON UNITS INSTALLED
WITH LLS.
5. USE COPPER CONDUCTORS ONLY.
6. CONNECTION FOR TYPICAL COOLING ONLY
THERMOSTAT. FOR OTHER
ARRANGEMENTS SEE INSTALLATION
INSTRUCTIONS.
7. IF INDOOR SECTION HAS A TRANSFORMER
WITH A GROUNDED SECONDARY, CONNECT
THE GROUNDED SIDE TO THE BRN LEAD.
8. WHEN START RELAY AND START
CAPACITOR ARE INSTALLED, START
THERMISTOR IS NOT USED.
9. CH NOT USED ON ALL UNITS.
10.IF ANY OF THE ORIGINAL WIRE, AS
SUPPLIED, MUST BE REPLACED, USE THE
SAME OR EQUIVALENT WIRE.
11.CHECK ALL ELECTRICAL CONNECTIONS
INSIDE CONTROL BOX FOR TIGHTNESS.
12.DO NOT ATTEMPT TO OPERATE UNIT UNTIL
SERVICE VALVES HAVE BEEN OPENED.
13.DO NOT RAPID CYCLE COMPRESSOR.
COMPRESSOR MUST BE OFF 3 MINUTES TO
ALLOW PRESSURES TO EQUALIZE
BETWEEN HIGH AND LOW SIDE BEFORE
STARTING.
14.WIRE NOT PRESENT IF HPS, LPS, DTS OR
CTD ARE USED.
320848 - 401 REV. A
Fig. 2—38CM060 208-230v, 1 Phase, 60 Hertz
A93422
Copyright 1993 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231
13165c
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 101 Catalog No. 563-781 Printed in U.S.A. Form 38CM-1W Pg 2 1-94 Replaces: New
Tab 3a 2a