AIR BLUE - Chiller
AIR BLUE - Chiller
AIR BLUE - Chiller
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>AIR</strong><br />
<strong>BLUE</strong><br />
a i r c o n d i t i o n i n g<br />
Hydronic Domestic Line<br />
5 ÷ 16 kW<br />
The most practical,<br />
modern solution<br />
for domestic and<br />
residential air<br />
conditioning<br />
systems.
Technical<br />
Characteristics<br />
FREEZY water chiller<br />
UNIT FRAME<br />
the unit frame is made of galvanized steel with<br />
baked epoxy-polyester powder enamel to<br />
ensure the best resistance to the weather even<br />
in sea climates; the colour is RAL 7032.<br />
COMPRESSOR<br />
scroll type with thermal overload protection by<br />
a klixon embedded in the motor winding and<br />
rubber vibration absorbers.<br />
The three-phase voltage units are equipped<br />
with an electronic safety device (phase<br />
sequence relay) that prevents the scroll<br />
compressor from rotating in reverse, and a<br />
crankcase heater.<br />
CONDENSER<br />
coils consist of seamless copper tubes<br />
mechanically expanded into aluminium fins.<br />
The condenser coils are protected by a<br />
galvanized metal mesh.<br />
FANS<br />
of the axial type, directly driven by 6 pole<br />
electric motors. IP 54 motor protection grading.<br />
A safety fan guard is fitted.<br />
EVAPORATOR<br />
of the coaxial type with condensation-insulated<br />
accumulation tank in closed cell expanded<br />
material, chilled water pump and flow switch.<br />
REFRIGERANT CIRCUIT<br />
with charging connection dehydrate filter, sight<br />
glass (on models 410-610-810 only), thermal<br />
expansion valve, melting plug.<br />
ELECTRIC PANEL<br />
This includes:<br />
- main switch<br />
(only on models 410 - 610 - 810)<br />
- protections on compressors and auxiliaries<br />
- compressor contactor<br />
- transformer 230÷24 V<br />
- MICROPROCESSOR to control the following<br />
functions:<br />
- water temperature control<br />
- antifreeze protection<br />
- compressor delay relay<br />
- alarm reset<br />
- buzzer alarm<br />
- digital remote inlet ON-OFF<br />
- potential free contact for<br />
remote general alarm<br />
visual signalling on display of:<br />
- inlet and outlet water temperature<br />
- set point and differential setting<br />
- compressor and pump operating time<br />
- alarm codes<br />
- summer and winter operation green led<br />
- compressor running green led<br />
OTHER CONTROLS<br />
- manual reset high pressure switch<br />
- automatic reset low pressure switch<br />
- flow switch fitted on the evaporator<br />
hydraulic circuit<br />
TESTS<br />
The units are factory tested and supplied<br />
charged with R 22 refrigerant and synthetic<br />
antifoaming oil.<br />
Other versions<br />
FREEZY reversible heat pump<br />
In addition to the components in the basic<br />
version, it comprises:<br />
REFRIGERANT CIRCUIT:<br />
4-way diversion valve, suction liquid receiver,<br />
check valve, second expansion valve.<br />
ELECTRIC PANEL:<br />
- MICROPROCESSOR also controlling the<br />
following functions:<br />
- summer/winter changeover switch<br />
- automatic defrost<br />
Accessories:<br />
• remote control<br />
• RS485 serial line board<br />
• rubber anti-vibration isolators<br />
• special power supplies:<br />
400V/3pH/50Hz for models from 210 to 360<br />
• fan speed regulator.
Technical<br />
Data<br />
FREEZY<br />
FREEZY HP<br />
Unit size 210 310 360<br />
COOLING<br />
Nominal capacity (1) kW 4,9 7,6 9,0<br />
HEATING<br />
Nominal capacity (2) kW 5,6 8,5 10,2<br />
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50<br />
COMPRESSOR<br />
Quantity n° 1 1 1<br />
Cooling power input (1) kW 1,5 2,2 2,6<br />
Heating power input (2) kW 1,6 2,4 2,8<br />
Pump nominal power kW 0,37 0,37 0,37<br />
Flow rate l/s 0,234 0,363 0,430<br />
Available pressure kPa 137 115 100<br />
Heat exchanger volume litri 11 11 11<br />
FANS<br />
Air flow m 3 /s 0,83 0,83 0,83<br />
N° x nominal input n° x kW 1x0,14 1x0,14 1x0,14<br />
R 22 refrigerant charge<br />
<strong>Chiller</strong> version kg 1,7 2,0 2,1<br />
Heat pump version kg 2,2 2,5 2,6<br />
Oil charge kg 1,0 1,1 1,1<br />
Noise level (3) dB(A) 36 37 37<br />
Shipping weight (4) kg 135 138 140<br />
1 Ambient air 32°C; evaporator water temperature in/out 12-7°C<br />
2 Ambient air 8°C DB, 6°C WB; evaporator water temperature in/out 40/45°C<br />
3 Noise level pressure detected in free field at a distance of 10 m from the unit.<br />
4 Shipping weight: for the heat pump unit weight increase 10%.<br />
Dimensions, clearances and hydraulic connections.<br />
WATER INLET 1” BSP-F<br />
REAR VIEW<br />
WATER OUTLET 1” BSP-F<br />
RIGHT VIEW<br />
REMOVABLE PANEL<br />
PROTECTION GRID<br />
OPTIONAL CONDENSATION DRAIN PIPE ø 22<br />
POWER SUPPLY INLET ø 36<br />
*<br />
4 holes ø 12<br />
TOP VIEW<br />
FOOTPRINT<br />
*<br />
A CONDENSATE DRAIN PAN IS<br />
AVAILABLE ON REQUEST FOR THE<br />
HEAT PUMP VERSION
410 610 810 Unit size<br />
COOLING<br />
10,9 13,3 16,1 kW Nominal capacity (1)<br />
HEATING<br />
12,3 14,9 18,3 kW Nominal capacity (2)<br />
400/3+N/50 400/3+N/50 400/3+N/50 V/ph/Hz Power supply<br />
COMPRESSOR<br />
1 1 1 n° Quantity<br />
3,1 3,7 4,6 kW Cooling power input (1)<br />
3,3 3,9 4,9 kW Heating power input (2)<br />
0,37 0,37 0,37 kW Pump nominal power<br />
0,521 0,635 0,769 l/s Flow rate<br />
160 135 105 kPa Available pressure<br />
33 33 33 litri Heat exchanger volume<br />
FANS<br />
1,80 1,80 1,80 m 3 /s Air flow<br />
1x0,37 1x0,37 1x0,37 n° x kW N° x nominal input<br />
R 22 refrigerant charge<br />
3,0 3,2 3,7 kg <strong>Chiller</strong> version<br />
4,0 4,2 4,7 kg Heat pump version<br />
1,85 1,55 1,65 kg Oil charge<br />
42 42 42 dB(A) Noise level (3)<br />
175 177 180 kg Shipping weight (4)<br />
1 Ambient air 32°C; evaporator water temperature in/out 12-7°C<br />
2 Ambient air 8°C DB, 6°C WB; evaporator water temperature in/out 40/45°C<br />
3 Noise level pressure detected in free field at a distance of 10 m from the unit.<br />
4 Shipping weight: for the heat pump unit weight increase 10%.<br />
Dimensions, clearances and hydraulic connections.<br />
REAR VIEW<br />
WATER INLET 1” BSP-F<br />
WATER OUTLET 1” BSP-F<br />
RIGHT VIEW<br />
REMOVABLE PANEL<br />
PROTECTION GRID<br />
OPTIONAL CONDENSATION DRAIN PIPE ø 22<br />
POWER SUPPLY INLET ø 36<br />
*<br />
4 holes ø 12<br />
,TOP VIEW<br />
FOOTPRINT<br />
*<br />
A CONDENSATE DRAIN PAN IS<br />
AVAILABLE ON REQUEST FOR THE<br />
HEAT PUMP VERSION
Air Blue<br />
Microprocessor,<br />
“Compact”<br />
Version.<br />
The Air Blue Microprocessor, “Compact” Version, is a small, compact electronic control unit created<br />
to operate chillers and single-compressor heat pumps.<br />
The control unit manages all the functions of a chiller or heat pump, such as activities, timing and<br />
alarms.<br />
Digital display visualization<br />
The display is made up of three figures, and<br />
normally indicates the temperature measured by the<br />
regulator probe (that is to say the evaporator water<br />
inlet temperature). It is also possible to display: the<br />
water outlet temperature, the set point and<br />
differential setting, the compressor and pump<br />
operating times and alarm codes. Four LEDs<br />
comp<br />
PRG<br />
mute<br />
clear<br />
SEL<br />
x 100<br />
indicate: the machine operating mode (summer/winter), the status of the compressor (on/off) and the<br />
compressor working hours (x 100).<br />
Key to indicator LEDs Led Flashing Fixed<br />
Compres. Request for Compressor Compressor actuated<br />
Summer / Cooling mode<br />
Winter / Heating mode<br />
x 100 / Value displayed x 100<br />
Control buttons Button Status of the unit Effect after pressing the button<br />
SEL 1. Normal operating mode After 5” DIRECT parameters<br />
(the display shows the evaporator are displayed<br />
input water temperature).<br />
2. List of codes Displays value<br />
3. Displays values Displays list of codes<br />
PRG 1. Normal After 5” password for USER<br />
parameters<br />
2. List of codes Stores parameters in<br />
Eeprom, then displays the<br />
evaporator inlet water<br />
temperature<br />
3. Displays values Stores parameters in<br />
Eeprom, then displays the<br />
evaporator inlet water<br />
temperature<br />
4. Buzzer on Turns the buzzer off<br />
1. Normal After 5” enables/disables<br />
cooling mode<br />
2. List of codes Displays the parameter<br />
codes<br />
3. Displays values Increases value<br />
1. Normal After 5” enables/disables<br />
heating mode<br />
2. Code list Displays the parameter<br />
codes<br />
3. Value display Decreases value<br />
PRG + SEL 1. Normal After 5” displays FACTORY<br />
parameters<br />
SEL + 1. Normal After 5” forces a manual defrosting<br />
cycle (if temperature<br />
conditions permit)<br />
+ 1. Normal After 5” performs manual alarm<br />
reset<br />
2. Display timer Zeroes hour counter
Easy<br />
to use.<br />
The “clock” of a switch,<br />
an action as simple<br />
as turning on a light,<br />
is enough to obtain,<br />
and enjoy,<br />
the ideal conditions<br />
in just a few minutes.<br />
Air Blue units are extremely easy to use.<br />
We have taken great pains to find ways of creating<br />
advanced products made to suit everybody’s pocket.<br />
Clean, filtered air, at the required temperature and<br />
humidity: in your home at least these are dreams that<br />
can now come true.<br />
Our air-conditioning system is based on the simple<br />
circulation of water inside the indoor units, which<br />
can be either chilled or warmed by the base unit.<br />
This means there is no need to call in a refrigeration<br />
expert, and your usual plumber can install the Air<br />
Blue units quite simply and safely.<br />
Easy<br />
to install.<br />
All Air Blue’s packaged units,<br />
with integrated pump and tank,<br />
only need to be<br />
plumbed in.<br />
The ideal<br />
conditions<br />
in every room.<br />
With Air Blue’s Distributed Air<br />
Conditioning system<br />
you can have the temperature and<br />
humidity you want<br />
when you are actually in the room,<br />
without wasting energy.<br />
Well-being<br />
and energy<br />
saving.<br />
Why cool or warm all rooms in the same way if you<br />
are only going to use some of them during certain<br />
hours of the day or night?<br />
With Air Blue’s Distributed Air Conditioning system<br />
you can have the conditions you want in each room:<br />
but only when you need them, giving a considerable<br />
saving of energy.This method, which is already widely<br />
used for air conditioning systems in large<br />
environments (such as hotels and hospitals), is<br />
completely new for small and medium size premises.<br />
In any room, by keeping the temperature and<br />
humidity under control, you can change air<br />
that is far too humid (in the Summer)<br />
or too dry (in the Winter) for<br />
conditions that are ideal<br />
whatever the season.<br />
Energy consumption and costs increase visibly if airconditioning<br />
is the same in every room.<br />
All Air Blue’s indoor units - one for each room - each have<br />
their own thermostat to control the conditions in the room<br />
in which they are installed.<br />
At night, for instance, the temperature in the dining room<br />
will be different from that in the bedrooms. And even<br />
here, according to your personal preference, you can have<br />
different temperatures in each bedrooms.What we are<br />
offering you is an efficient system which, by means of a<br />
simple command, will provide you with the conditions<br />
most suited to your particular needs.<br />
Why waste money and energy<br />
unnecessarily?<br />
With Air Blu’s Distributed Air<br />
Conditioning system you can save up to<br />
50% or more!<br />
<strong>BLUE</strong> BOX Condizionamento<br />
<strong>AIR</strong> <strong>BLUE</strong> Air Conditioning<br />
<strong>BLUE</strong> FROST Refrigeration<br />
are trademarks of the<br />
<strong>BLUE</strong> BOX GROUP<br />
<strong>BLUE</strong> BOX GROUP s.r.l. Via E. Mattei, 20 35028 Piove di Sacco PD Italy Tel. +39.049.9716300 Fax. +39.049.9704105<br />
PBCT0700 – Issue 10.99 / Supersedes 11.98 - Technical data may change without notice<br />
Is member of the Piove Clima Syndicate