FDR - Fire Damper for Rectangular and Circular Ducts - Halton

halton.com

FDR - Fire Damper for Rectangular and Circular Ducts - Halton

FDR

Fire Damper for Rectangular and Circular Ducts

20/FDR/3500/0907/EN

• Type-approved and compliant with the EN 1366-2

and EN 13501-3 standards.

• Design for installation in separating concrete and

masonry walls and ceilings and lightweight

plasterboard walls of fire compartments with fire

resistance class EIS 30 to EIS 120.

• Readiness for installation with all wall options as

delivered – no additional frames needed.

• Manufactured in accordance with the ISO 9001

quality system.

• VTT, the Technical Research Centre of Finland, is

responsible for external quality control.

• Installation in rectangular and circular ducts with

diameter 630 to 1000 mm.

• Available with motorised or manual actuator.

• Double sealing, ensuring that the blades are tight

when the fire damper is closed before and during a

fire.

Fire damper casing complying with the tightness

requirements for Class C, EN 1751.

Fire damper tightness meeting smoke damper

requirement S of standard EN 1366-2.

• Suitability for use in ducts with a maximum

pressure of 2800 Pa.

Damper closing tests performed at 15 m/s duct

velocity.

Product models and Accessories

• Models equipped with either manual or electric

actuators.

FDR - Fire Damper for Rectangular and Circular Ducts

136


DIMENSIONS

20/FDR/3500/0907/EN

W/H: 200, 250, 300, 400, 500...1000

When the damper is installed on concrete and

masonry walls or ceilings, the size of the installation

hole is W/H + 100 mm.

When the damper is installed on lightweight walls, the

size of the installation hole is W/H + 110 mm.

FDR Ø BxH D-1 La Lb C L L+2xC

630 600x600 629 266 354 52 620 724

800 800x800 799 366 454 58 820 936

1000 1000x1000 999 466 554 58 1020 1136

Pressure drop and sound data

Sound power level Lw, in in each octave band is

computed bu adding the corresponding correction

factor, Kok, to the sound pressure level in the

selection chart according to the following equation.

Lw = LpA + Kok

The corresponding factor Kok is the average of the

FDR operating area.

f / [Hz] 125 250 500 1k 2k 4k 8k

kok 10 5 0 -3 -3 -11 -20

l / dB +/- 2 +/- 2 +/- 2 +/- 2 +/- 2 +/- 2 +/- 3

FDR - Fire Damper for Rectangular and Circular Ducts

137


Material and finishing

The FDR fire damper casing, installation flange, and

installation frame are made of galvanised steel. The

closing blade is made of calcium silicate and equipped

with a flexible silicone seal as well as a graphite mass

seal that expands at high temperatures.

Product options and Accessories

Function

The FDR is a fire damper of class EIS 30 to EIS 120

for circular or rectangular ducts, which prevents fire

and smoke from spreading in ventilation ducts. The fire

damper is equipped with either a motorised actuator

or manual actuation arrangement. Both actuators

have a visual position indicator. If the power in the

motorised actuator system is switched off, the blade

closes automatically.

20/FDR/3500/0907/EN

Actuators

Manual actuator, MA (spring return)

Electrical actuators

Models for Europe and Russia:

Belimo BF24-T-2 HL, operating voltage AC/DC 24 V (72

ºC, contains a microswitch), B1

Belimo BF230-T-2 HL, operating voltage AC 230 V (72

ºC, contains a microswitch), B2

Model for Sweden:

Belimo BF24 HL, operating voltage AC/DC 24 V (no

fuse, contains a microswitch), B5

Belimo BF230 HL, operating voltage AC 230 V (no

fuse, contains a microswitch), B6

Accessories

Safety mesh on one side, N1

Safety mesh on both sides, N2

Manual actuator accessories

Fuse release temperatures, FU = 50 ºC, 65 ºC, 72 ºC,

100 ºC

Limit switches, open and closed position, MS

Europe and Russia models:

In both actuator options, a fuse reacts to a rise in

temperature, causing a spring-return blade to close.

The motorised fire damper is delivered complete with

a spring-return actuator and a fuse that is activated at

72 ºC.

Sweden model:

The electrical motor option is without thermal fuse

and shall be connected to an automatic alarm system.

The fire damper is made of fireproof materials. Once

the fire damper has closed, the double sealing closes

the duct tightly, effectively preventing the spreading

of flue gases in the ventilation ductwork. The flexible

seal of the double sealing system operates at lower

temperatures, while the graphite mass seal expands

to insulate the system at temperatures above 150 ºC.

The FDR fire damper can be connected to the MSH

control and testing system for fire dampers. The

MSH unit enables the use of smoke detectors in the

ductwork or rooms. The FDR fire damper can also

be connected to other common building automation

systems.

FDR - Fire Damper for Rectangular and Circular Ducts

138


Installation

Installation on masonry walls

When the fire damper is installed on concrete

and masonry walls and ceilings between fire

compartments, the blade shaft is always horizontal.

An opening is always left in the separating element

for the fire damper, and the product is subsequently

grouted into this.

To make installation easier, all products come with

an installation flange, which is used to fasten the fire

damper to the concrete surface with screws before

grouting.

During installation, the fire damper and actuator must

be protected with, e.g., a plastic cover.

The correct operation of the fire damper must be

ensured before and after grouting.

When the damper is installed for concrete and

masonry walls and ceilings, the size of the installation

hole is W/H + 100 mm.

Installation on lightweight plasterboard walls

When the fire damper is installed on lightweight

plasterboard walls between fire compartments,

an opening for the fire damper must be left on the

plasterboard in which the installation frame (included

in the delivery) is first mounted. The blade shaft must

always be horizontal. To make installation easier, the

fire damper comes with an installation flange, which

is used to fasten the fire damper to, e.g., the steel

frame of the panel wall. The space between the fire

damper and the installation frame is filled with a fire

prevention mastic. During installation, the fire damper

and actuator must be protected with. e.g., a plastic

cover. The correct operation of the fire damper must

be ensured after application of the fire prevention

mastic.

For lightweight walls, the size of the installation hole

is W/H+110 mm; consult the section ‘Documents /

Installation Instructions’ for the size of the installation

holes.

20/FDR/3500/0907/EN

Detailed installation instructions, as well as an

installer’s installation certificate form, are supplied

with each product. See also the section ‘Documents /

Installation Instructions’.

Electric actuator wiring diagram

-

~

+

-

~

+

Manual actuator wiring diagram (limit switches,

MS)

1 2

S1 S2 S3 S4 S5 S6

1 2

S1 S2 S3 S4 S5 S6

< 5

< 80

< 5 < 80

K1

K1

K1

Tf1 Tf2 Tf3 LED BAE72B-S

BF24-HI

BF230-HI

BF24-T HI

BF230-T HI

Damper open Damper drives Damper closed

K1:13/14 closed K1: 13/14 open K1: 13/14 open

21/22 open 21/22 closed 21/22 closed

K2: 13/14 open K2: 13/14 open K2: 13/14 closed

21/22 closed 21/22 closed 21/22 open

FDR - Fire Damper for Rectangular and Circular Ducts

139


Suggested specifications

A fire damper of class EIS 30 to EIS 120 shall have

a double sealing solution that ensures fire-gas

resistance at all temperatures when the fire damper is

closed.

In motorised models, the fuse shall be activated at 72

°C (E and R models).

In the manually operated system, the fuse activation

temperature corresponds to the specifications (50, 65,

72, 100 °C).

The fuse shall be located inside the damper, and it

shall be possible to replace it from the outside.

The fire damper shall have means for external opening

/ triggering of the release and closing. The fire damper

shall include a position indicator.

The fire damper shall be suitable for vertical and

horizontal installation on concrete and masonry walls

and on ceilings or lightweight plasterboard walls

between fire compartments (EIS 30 to EIS 120).

The technical properties of the type-approved fire

damper shall conform to the EN 1366-2 and EN

13501-3 standards.

The internal quality control of the fire damper

manufacturer shall be based on the ISO 9001

quality system system, and the operations of the

manufacturer shall be subject to external third-party

quality control.

20/FDR/3500/0907/EN

Product code

S = Model

E Europe

S Sweden

R Russia

A = Type of duct connections

R Rectangular

A Duct connection 630

B Duct connection 800

C Duct connection 1000

Specifics and Accessories

RE = Release type

MA Spring release

B1 BF24-T-2 HL fuse 72 °C (E and R

models)

B2 BF230-T-2 HL fuse 72 °C (E and R

models)

B5 BF24 HL, no fuse (S model)

B6 BF230 HL, no fuse (S model)

W = Width

A = R: 200, 250, 300, 400, 500, 600, 700,

800, 900, 1000

A = A: 600

A = B: 800

A = C: 1000

H = Height

A = R: 200, 250, 300, 400, 500, 600, 700,

800, 900, 1000

A = A: 600

A = B: 800

A = C: 1000

FU = Fuse release temperature (°C)

50 °C, 65 °C, 72 °C, 100 °C

AC = Accessories

MS Limit switches

N1 Safety mesh, 1 side, installed in

actuator side

N2 Safety mesh, 2 sides

Code example

FDR/E-R-200-200, RE=MA, FU=72

FDR - Fire Damper for Rectangular and Circular Ducts