HPC-NNBOSL-U0-000-RES-000034 Version 2.0<br />

<strong>PSA</strong> <strong>of</strong> <strong>Accidents</strong> <strong>in</strong> <strong>the</strong> <strong>Spent</strong> <strong>Fuel</strong> <strong>Pool</strong><br />

NOT PROTECTIVELY MARKED<br />

5.3.4 Risk <strong>of</strong> <strong>Fuel</strong> Damage follow<strong>in</strong>g a break <strong>of</strong> Pipework Connected<br />

to <strong>the</strong> <strong>Fuel</strong> Build<strong>in</strong>g <strong>Pool</strong>s<br />

The follow<strong>in</strong>g table presents <strong>the</strong> risk <strong>of</strong> fuel damage due to <strong>the</strong>se <strong>in</strong>itiat<strong>in</strong>g events <strong>in</strong> this<br />

group.<br />

Nature and Position <strong>of</strong> Break Plant State Equivalent<br />

Diameter<br />

Risk <strong>of</strong> <strong>Fuel</strong><br />

Damage (/r.y)<br />

Guillot<strong>in</strong>e break on <strong>the</strong> suction <strong>of</strong> a ma<strong>in</strong> PTR<br />

[FPCS] tra<strong>in</strong><br />

A - D DN300 1.64E-10<br />

E DN300 1.26E-11<br />

F DN300 2.23E-11<br />

Guillot<strong>in</strong>e break on <strong>the</strong> discharge <strong>of</strong> a ma<strong>in</strong><br />

PTR [FPCS] tra<strong>in</strong><br />

A - D DN300 2.12E-10<br />

E DN300 1.68E-11<br />

F DN300 3.11E-11<br />

Guillot<strong>in</strong>e break on <strong>the</strong> suction <strong>of</strong> fuel build<strong>in</strong>g<br />

purification<br />

A - D DN150 0<br />

E DN150 < 1E-12<br />

F DN150 0<br />

Guillot<strong>in</strong>e break on <strong>the</strong> discharge <strong>of</strong> fuel<br />

build<strong>in</strong>g purification<br />

A - D DN150 0<br />

E DN150 < 1E-12<br />

F DN150 0<br />

Guillot<strong>in</strong>e break on <strong>the</strong> suction <strong>of</strong> <strong>the</strong> third<br />

PTR [FPCS] tra<strong>in</strong><br />

Guillot<strong>in</strong>e break on <strong>the</strong> discharge <strong>of</strong> <strong>the</strong> third<br />

PTR [FPCS] tra<strong>in</strong><br />

Break on <strong>the</strong> dra<strong>in</strong><strong>in</strong>g pip<strong>in</strong>g <strong>of</strong> <strong>the</strong> fuel<br />

build<strong>in</strong>g transfer compartment to <strong>the</strong> IRWST<br />

A - D DN300 7.52E-10<br />

A - D DN300 1.06E-09<br />

A - D DN50 < 1E-12<br />

5.3.5 Risk <strong>of</strong> <strong>Fuel</strong> damage follow<strong>in</strong>g an Alignment Error on Pipework<br />

Connected to <strong>the</strong> Reactor Build<strong>in</strong>g <strong>Pool</strong>s<br />

The follow<strong>in</strong>g table presents <strong>the</strong> risk <strong>of</strong> fuel damage due to <strong>the</strong> <strong>in</strong>itiat<strong>in</strong>g events <strong>of</strong> this<br />

group.<br />

Description <strong>of</strong> Initiat<strong>in</strong>g Event Flow Rate ( m 3 /h) Risk <strong>of</strong> <strong>Fuel</strong><br />

Damage (/r.y)<br />

Spurious open<strong>in</strong>g <strong>of</strong> a zero flow pressure l<strong>in</strong>e LHSI/RHR 106 < 1E-12<br />

Dra<strong>in</strong><strong>in</strong>g via <strong>the</strong> unload<strong>in</strong>g l<strong>in</strong>e RCV [CVCS] < 72 < 1E-12<br />

Voluntary dra<strong>in</strong><strong>in</strong>g <strong>of</strong> <strong>the</strong> reactor build<strong>in</strong>g pool, <strong>Spent</strong> <strong>Fuel</strong> <strong>Pool</strong><br />

not isolated<br />

Spurious open<strong>in</strong>g <strong>of</strong> <strong>the</strong> dra<strong>in</strong><strong>in</strong>g valve <strong>of</strong> <strong>the</strong> reactor build<strong>in</strong>g<br />

compartments to <strong>the</strong> IRWST<br />

180 < 1E-12<br />

< 880 < 1E-12<br />

UNCONTROLLED WHEN PRINTED<br />

NOT PROTECTIVELY MARKED<br />

Page 30 <strong>of</strong> 37