15.01.2015 Views

Manual / Handbuch Spare parts list / Ersatzteilliste - WESCO-Navy

Manual / Handbuch Spare parts list / Ersatzteilliste - WESCO-Navy

Manual / Handbuch Spare parts list / Ersatzteilliste - WESCO-Navy

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Manual</strong> / <strong>Handbuch</strong><br />

<strong>Spare</strong> <strong>parts</strong> <strong>list</strong> / Ersatzteil<strong>list</strong>e<br />

• Equipment Imp.-Exp. GmbH • Zitterpappelweg 9<br />

D - 22391 Hamburg • Tel.: + 49 40 60009468-0 • Fax: + 49 40 536 75 01<br />

E - M a i l : i n f o @ w e s c o - n a v y. c o m • w w w. w e s c o - n a v y. c o m


Contents:<br />

Page<br />

Installation instructions<br />

User instructions<br />

3<br />

4-5<br />

Cleaning/general maintenance 6<br />

Installer’s obligations in connection with<br />

installation 7-8<br />

Figures 9<br />

Trouble Shooting 10<br />

Compressor windings resistance 11<br />

Drawings 12-13<br />

<strong>Spare</strong> part <strong>list</strong> 14<br />

Controller 15-24<br />

Wiring diagram 25<br />

General instructions<br />

1. Read the contents of this manual carefully. It contains important information concerning the installation, use and<br />

maintenance of the equipment.<br />

Keep this manual in a safe place but also ensure that it is available to everyone who will use the equipment.<br />

2. The equipment may only be installed by qualified, authorised personnel in accordance with the manufacturer’s<br />

instructions.<br />

3. If a fault should occur, switch off the power supply immediately and remove the plug from the wall socket.<br />

Contact the manufacturer (during the warranty period) or another person or company authorised by the<br />

manufacturer to repair the equipment.<br />

Use only original <strong>parts</strong> when replacing components.<br />

If the above is not observed, the safety of the equipment may be at risk and it may be more difficult to rely on the<br />

warranty on a subsequent occasion.<br />

The equipment has been tested and certified by SEMKO where CE marking and EMC are concerned.<br />

Or by the manufacturer with reference to the rules and regulations that apply to CE and EMC approval.<br />

2


Installation instructions<br />

Location<br />

• The equipment must be installed in a well-ventilated room (fig. 1), as far as possible from heat sources<br />

and so that good air circulation is achieved, in particular around the part where the compressor unit is<br />

located. The maximum room temperature may not exceed +32 o C and the condensation temperature<br />

may not exceed +45 o C.<br />

• Adjust the height and the horizontal and vertical inclination of the equipment by rotating the adjustable<br />

legs and check that the door can be opened and closed without impediment.<br />

• The equipment must be anchored in a suitable manner to prevent it from tipping over.<br />

• Remove the protective plastic from the external surfaces on models made of stainless sheeting. Pull the<br />

plastic off slowly. If, after the plastic has been removed, there is any glue residue, it can be removed<br />

with a suitable solvent.<br />

Electrical connection<br />

Electrical connections must be made in accordance with all applicable local standards and regulations in<br />

force at the time.<br />

• The electrical connection must be made in accordance with all applicable standards and regulations.<br />

- The equipment works from single-phase 220-240 V AC 50 Hz<br />

- The equipment is connected simply by inserting the plug in the mains socket after checking<br />

that the mains socket can be loaded with the relevant current and has the correct protective<br />

earthing.<br />

- All standard version units are protected with a 10 A delay action fuse.<br />

- A 3 m power cable is supplied. This emerges from the unit or solenoid valve at a height above<br />

the floor of roughly 2000 mm.<br />

• The electrical safety of the equipment can only be guaranteed when it has been correctly connected to<br />

an installation with protective earthing in accordance with applicable safety regulations.<br />

• If you have any doubt about the efficiency of the protective earthing, the installation must be checked<br />

by a qualified engineer.<br />

The manufacturer accepts no liability for the consequences of the above safety measures not being taken.<br />

Page 2<br />

3


User instructions<br />

Comments:<br />

• The equipment may only be used for the purpose for which it was manufactured, which involves the<br />

refrigeration or preservation of food. All other use of the equipment must be regarded as incorrect.<br />

• To ensure that the equipment functions correctly:<br />

- ensure that all food is covered or wrapped<br />

- leave sufficient space between the shelves and the sides of the equipment to maintain<br />

adequate air circulation<br />

- do not leave doors or boxes open for a long time<br />

Control panel (fig. 2), standard version.<br />

A-On/off switch<br />

B-Digital thermostat<br />

Standard models, switching on<br />

Press the switch. A lamp in the switch lights up to show that the unit is switched on.<br />

Set the digital thermostat to the required temperature. Do this as follows:<br />

Press the SET button. The preset temperature is displayed in the display.<br />

Press the button to increase the temperature shown. If you hold the button in, the temperature values will<br />

increase rapidly.<br />

The<br />

button reduces the temperature in the same way.<br />

Five seconds after you release the button, the new value is automatically saved in the memory and the thermostat<br />

displays the temperature inside the refrigeration area. The preset ranges for minimum and maximum<br />

temperatures are:<br />

Refrigeration: Max. setting = +12 o Min. setting = 0 o<br />

Chiller: = +12 o = 0 o<br />

Freezer: = -10 o = -30 o<br />

Cooling: = +12 o = 0 o<br />

When the unit is in operation, the digital thermostat displays the internal temperature.<br />

Press the SET button to display the programmed temperature in the display.<br />

Page 3<br />

4


Defrosting<br />

1. Automatic defrosting<br />

The unit has an automatic defrosting system (not bakery freezers). When this is activated, the DEF indicator<br />

lights up on the digital thermostat. Defrosted water is collected in an electrically heated box beneath the unit<br />

and evaporates there automatically.<br />

2. <strong>Manual</strong> defrosting<br />

Press the SET button for 5 seconds. When the defrosting cycle is activated, the DEF indicator lights up on the<br />

digital thermostat. After you have pressed the manual defrosting button, the interval for the next automatic<br />

defrosting cycle is reset.<br />

Page 4<br />

5


Cleaning and general maintenance<br />

• No cleaning or maintenance work may be carried out before the mains cable has been disconnected.<br />

Internal cleaning of the equipment<br />

• Before the equipment is taken into use, internal <strong>parts</strong> and accessories must be cleaned with hot water<br />

and a neutral detergent. Then rinse them thoroughly and dry them carefully. Do not use solvents or<br />

abrasives.<br />

Do not clean the expansion fittings on the refrigeration benches.<br />

Periodic cleaning<br />

• Clean stainless steel <strong>parts</strong> and surfaces with hot water and a neutral detergent. Then rinse them<br />

thoroughly and dry them carefully.<br />

Never use aggressive solvents, standard steel wool, steel brushes or similar products.<br />

Painted surfaces and <strong>parts</strong> must be cleaned as described above or with Silkonvax.<br />

• The condenser flanges of the refrigeration unit must be cleaned at least once every six months with a<br />

brush or vacuum cleaner (fig. 3).<br />

• Do not use sharp objects when cleaning condenser flanges and pipes.<br />

NB: Never wash the equipment with a water jet.<br />

If the equipment is not used<br />

If the equipment is not to be used for an extended period of time, the following instructions must be followed:<br />

• Remove the plug from the mains socket.<br />

• Remove all products from the refrigeration area and clean the inside and all accessories.<br />

• Leave the doors open so that air can circulate in the refrigeration area, thus preventing the<br />

development of mould and bad air.<br />

• Spread a protective layer of vaseline on stainless surfaces with a damp cloth and check that the<br />

premises are aired regularly.<br />

Page 5<br />

6


Installer’s obligations in connection with the installation of catering equipment<br />

Location<br />

The unit must be located in accordance with our “Installation Instructions”. The air flow through the machine<br />

room must not be reduced, i.e. there must be at least 300 mm free space above the unit.<br />

Electrical connection<br />

The connection voltage must be 220-240 V AC 50 Hz. The unit is protected with a 10 A delay action fuse. A<br />

qualified electrician must connect central refrigeration units to the power supply.<br />

Refrigeration pipe connection<br />

When connecting refrigeration pipes to central refrigeration units, the connection pipes must not contain foreign<br />

objects or have contractions, cracks, etc. Copper pipes must be cut with a pipe cutter and must be deburred.<br />

Suction and liquid pipes must be connected to the cabinet in the upper part of the cabinet and to benches in the<br />

connection area to the right. Connections must be with soldered joints.<br />

Startup<br />

The system is started up without products in the units and must decrease to a stable evaporation temperature to<br />

start the check and adjustment routine.<br />

Adjustment<br />

The control, regulation and safety equipment must be adjusted according to our instructions. On cabinets for<br />

central refrigeration, check the setting of the expansion valve. If necessary, the expansion valve must be adjusted<br />

according to our instructions.<br />

Leak detection<br />

All joints in a central refrigeration system must be checked for leaks, including the connections to the unit<br />

(cabinet, benches). The unit itself need not be checked for leaks if no work has been performed on it. If the<br />

expansion valve is adjusted, the sealing nut above the adjustment screw must be checked for leaks.<br />

Page 6<br />

7


Installer’s obligations in connection with the installation of catering equipment<br />

Checks<br />

• Check that the unit’s operating temperature is correctly set according to our instructions.<br />

• Check that the solenoid valve opens or that the compressor starts (1 min. start delay).<br />

• Check that the fans start.<br />

• Check the evaporation temperature on the central refrigeration system. The pressure must match the<br />

values specified in the Technical Specifications.<br />

• On units with a compressor, the temperature of the supply air must be checked to ensure that it<br />

matches the values specified.<br />

• Check any lighting.<br />

• Check that the door hangs correctly and that the magnetic strip seals properly. If necessary, adjust<br />

the door.<br />

• Carry out manual defrosting and check that it takes place as described in the Technical<br />

Specifications or Installation Instructions.<br />

Page 7<br />

8


Fig. 1<br />

Installation Instructions<br />

The distance to the wall is designed to ensure good air circulation.<br />

The distance between the units is designed to prevent the possibility of moisture<br />

penetration and condensation.<br />

NB. To meet the authorities’ requirements for cleaning access, the dimensions<br />

specified should be increased.<br />

Ventilation requirements: 400 – 1400 m 3 /hour per unit.<br />

When the unit has been installed, wait 4 hours before starting it.<br />

All dimensions are minimum dimensions in millimetres.<br />

_____________________________________________________________________________________<br />

Fig. 2<br />

Control Panel<br />

7.<br />

1.<br />

2.<br />

3.<br />

1. Compressor working 5. Reduce temperature 4. 5. 6.<br />

2. Defrosting 6. Increase temperature<br />

3. Fan 7. On/off switch<br />

4. SET button<br />

_____________________________________________________________________________________<br />

Fig. 3<br />

Cleaning<br />

Condenser<br />

Page 8<br />

_____________________________________________________________________________________<br />

9


TROUBLESHOOTING DIAGRAM. (WARNING)<br />

1. CHECK THAT THE UNIT IS CONNECTED TO THE WALL SOCKET.<br />

2. CHECK THAT THE WALL SOCKET IS LIVE.<br />

3. IF THE UNIT´S OVERHEAT PROTECTION HAS TRIPPED, THIS MAY BE DUE TO<br />

THE FOLLOWING:<br />

3-1: ROOM TEMPERATURE TOO HIGH<br />

3-2. POOR VENTILATION, THE REQUIREMENTS ARE CONTAINED IN<br />

THE TECHNICAL SPECIFICATION.<br />

3-3: MAINS VOLTAGE TOO HIGH OR TOO LOW<br />

4. IF SEVERAL UNITS ARE PLACED IN A LINE NEXT TO ONE ANOTHER, THEN<br />

THE FLOW OF AIR TO AND FROM ALL THE UNITS MUST BE CHECKED<br />

CAREFULLY.<br />

5. ONCE THE ABOVE POINTS HAVE BEEN CHECKED AND DEALT WITH, START<br />

THE UNIT BY PRESSING THE RESET BUTTON LOCATED BEHIND THE FRONT<br />

GRILLE.<br />

6. IF THE UNIT DOES NOT START, PERFORM TROUBLESHOOTING AS PER<br />

TABLE 1. THIS MAY THEN REVEAL FAULTS IN THE COMPRESSOR OR START<br />

EQUIPMENT.<br />

10


SPAREPARTSLIST<br />

MARINE<br />

2006-02-01 FREEZER/REFRIGERATOR 01.01.2009<br />

CKF-<br />

400<br />

CKF-<br />

500<br />

CKF-<br />

550 CKF-7000<br />

Lock G-680 G-680 G-680 G-680<br />

Hinges Marine Marine Marine Marine<br />

Feet AL-M AL-M AL-M AL-M<br />

Rule BL-513 BL-513 BL-513 BL-513<br />

Shelves<br />

450 X<br />

500<br />

450 X<br />

500<br />

650 X<br />

500 650 X 500<br />

Electronic<br />

regulator<br />

FK-<br />

203/211<br />

FK-<br />

203/211<br />

FK-<br />

203/211 FK-20/211<br />

Main power switch UL-070 UL-070 UL-070 UL-070<br />

Tightening<br />

magnetic<br />

<strong>list</strong><br />

BL-400<br />

1/2<br />

BL-500<br />

1/2<br />

BL-550<br />

1/2 BL-700 1/2<br />

Fan motor<br />

evaporator Eco-1 Eco-1 Eco-1 Eco-1<br />

Refr. Machine<br />

SC-<br />

10/TL-5<br />

SC-<br />

10/TL-5<br />

SC-<br />

10/TL-5<br />

SC-12/TL-<br />

5<br />

Compressor<br />

SC-<br />

10/TL-5<br />

SC-<br />

10/TL-5<br />

SC-<br />

10/TL-5<br />

SC-12/TL-<br />

5<br />

Fan motor<br />

condensor<br />

16 W/5<br />

W<br />

16 W/5<br />

W<br />

16 W/5<br />

W<br />

16 W/5 W<br />

Condensator D.F-300 D.F 400 D.F 500 D.F 550<br />

Start relay D.F-300 D.F-400 D.F-500 D.F-550<br />

14


EVCO instrument description EVK203<br />

Generella data<br />

*Dimensions front 75 x 33 mm, depth 59 mm * Working range NTC –40.0 to 105.0°C<br />

PTC –50.0 to 150.0°C<br />

*Power supply 230 VAC<br />

* Programming is made in the front of the<br />

instrument<br />

*3 relay, 1 x 16A/250VAC compressor<br />

*Serial port ModBus for connection to<br />

surveillance system or programming key<br />

* Defrost can be programmed for interval, length<br />

and evaporator temperature<br />

2 x 8A/250VAC defrost, Fan<br />

Installation<br />

Panel mounting with click brackets delivered with the instrument, hole dimensions 71x29 mm.<br />

Surrounding temperature should be between 0 and +55 °C.<br />

Avoid placing the instrument where it is exposed to high humidity or condense and there should be ventilation<br />

around the instrument for cooling.<br />

Wiring diagram<br />

15


As soon as the instrument has power supply, a self check will be done at which all indicator LEDs will flashes.<br />

There after the instrument will be in starting mode and will show the room temperature. The output relay has<br />

voltage free contacts.<br />

Maximum load for the built-in compressor relay is 16A/250V. For greater load an external contactor is needed.<br />

Display<br />

With parameter P5 you can select what should be shown in the display:<br />

P5=0= cabinet probe value<br />

P5=1=working setpoint<br />

P5=2=evaporator probe (if P4=1 or 2)<br />

P5=3= cabinet probe value – evaporator probe<br />

Show the condenser temperature<br />

Make sure the keyboard is not locked.<br />

Press and hold for 2s until display shows Pb1 or Pb3.<br />

Use or to select probe.<br />

Pb1= cabinet probe<br />

Pb3= Aux-probe. Only active probes are shown.<br />

Press to show temperature on selected probe.<br />

Press again to select other probe.<br />

To quit, use or brows to normal operation and wait 60s, the instrument will return to normal display.<br />

Activate defrost by hand<br />

Check that the keyboard is not locked. Activate by pressing 4s.<br />

Defrost by hand can not be done if the function stop defrost at<br />

temperature (par d2) is activated and the evaporator probes temperature<br />

is above the stop temperature.<br />

Lock / un-lock the keyboard<br />

Press and at the same time 2s. Loc shows in the display.<br />

The keyboard becomes locked and no other functions than lighting can be activated.<br />

To un-lock the keyboard press and at the same time 2s. shows in the display.<br />

Buzzer<br />

Press any key to silence the buzzer.<br />

Working setpoint<br />

Press and then let go, starts to flash and current working setpoint is shown in the display.<br />

Use or to change the working setpoint.<br />

Press or wait 15s. The instrument will return to normal operation with the new working setpoint.<br />

Setting configuration parameters<br />

To get to the parameter <strong>list</strong>:<br />

Press and at the same time 4 s. PA shows in the display.<br />

Press then let go and use or to set –19.<br />

Press or wait 15s until PA shows in the display.<br />

Press and at the same time 4 s. until the first parameter SP shows.<br />

To select parameter:<br />

• Press or to brows the parameter <strong>list</strong>.<br />

To modify a parameter:<br />

• Press then let go and use or keys to get the value.<br />

To quit:<br />

16


• Press and at the same time 4 s. or wait 60 s.<br />

Switch on/off the power supply to the instrument after modification to carry out changes.<br />

Restoring the default values of configuration parameters<br />

Press and at the same time 4 s . PA shows in the display.<br />

Press and use or to set 743.<br />

Press or wait 15 s until PA shows.<br />

Press and at the same time ca 4 s . dEF shows in the display.<br />

Press and use or to set 149.<br />

Press or wait 15s. The instrument will flash dEF for 4s and then return to normal operation with default values<br />

Make sure the default value of the parameter is appropriate, in particular if the probes are PTC probes.<br />

Note that also the values for probe type will change if PTC probes are installed.<br />

Signaler<br />

LED compressor<br />

If it is lit, the compressor will be turned on.<br />

Flashes at modification of working setpoint or at delay, see par C0, C1, C2 and i7<br />

LED defrost<br />

If it is lit, the defrost will be running. Flashes at delay, see par C0, C1, C2, d7 and dA<br />

LED fan<br />

If it is lit, the evaporator fan will be turned on.<br />

Flashes when delay is activated, see par F3<br />

LED alarm<br />

If it is lit, an alarm will be running.<br />

Loc<br />

Is shown in the display when the keyboard is locked, see par r3 and the section about locked keyboard.<br />

- - - - Is shown in the display when the value is not available (for example if a probe is deactivated).<br />

Alarm<br />

AL = Low temperature alarm (see A0, A1 and A2)<br />

AH = High temperature alarm (see A3, A4 and A5)<br />

ld = Door switch input alarm (only if P4=3 and i0=3) (see i0 and i1) The compressor will be stopped.<br />

IA = Multipurpose input alarm (only if P4=3 and i0=0)(see i1 and i5).<br />

If i5=4 the compressor will be stopped.<br />

lSd = Instrument locked (only if P4=3 and i0=0) (see i1, i5, i7, i8 and i9)<br />

Compressor will be stopped.<br />

COH = Overheated condenser alarm (only if P4=2) (see C6)<br />

CSd = Compressor locked (only if P4=2)(see C7) Compressor will be stopped.<br />

Pr1 = Cabinet probe error (see P0)<br />

The compressor depends on par C4 and C5.<br />

Pr2 = Condenser probe error (see P0)<br />

If P4=1 Defrost uses time set by par d3.<br />

If P4=1 and d8=2 the instrument works as if d8 has the value 0.<br />

If P4=2 the condenser alarm Will not be activated.<br />

17


Configuration parameters EVK 203<br />

PA Min Max Unit EVK203<br />

SP Working setpoint r1 r2 °C/°F 0.0<br />

PROBE<br />

CA1 cabinet probe offset -25.0 25.0 °C/°F 0.0<br />

CA2 Evaporator probe offset -25.0 25.0 °C/°F 0.0<br />

P0 Kind of probe, 0=PTC, 1=NTC 0 1 - - - 1<br />

P1 Show point Celsius degree 0=No, 1=Yes 0 1 - - - 0<br />

P2 Celsius/Farenheit ( 0=°C, 1=°F) 0 1 - - - 0<br />

P3 Evaporator probe function<br />

0=not enabled<br />

1=defrost probe and thermostat probe for the evaporator<br />

fan<br />

2=thermostat probe for the evaporator fan<br />

0 2 - - - 1<br />

P5<br />

Quantity to show during normal operation 0=Cabinet<br />

temperature<br />

1=working setpoint, 2=evaporator temperature,<br />

3=cabinet temperature – evaporator temperature (P4=1<br />

or 2)<br />

0 3 - - - 0<br />

MAIN REGULATOR<br />

r0 Working setpoint differential 0.1 15.0 °C/°F 2.0<br />

r1 Minimum working setpoint -99.0 r2 °C/°F -30.0<br />

r2 Maximum working setpoint r1 99.0 °C/°F -10.0<br />

r3 Locking the working setpoint modification 0=No, 1= 0 1 - - - 0<br />

Yes<br />

COMPRESSOR PROTECTION<br />

C0 Compressor delay since you turn on the instrument 0 240 min 1<br />

C1 Minimum time between two activations in succession of<br />

the compressor, also compressor delay since the end of 0 240 min 0<br />

the cabinet probe error<br />

C2 Minimum time the compressor remains turned off 0 240 min 0<br />

C3 Minimum time the compressor remains turned on 0 240 sek 0<br />

C4 Time the compressor remains turned off during probe<br />

error<br />

0 240 min 10<br />

C5 Time the compressor remains turned on during probe<br />

error<br />

0 240 min 10<br />

DEFROST<br />

d0 Defrost interval<br />

(0= No defrost)<br />

0 99 tim 8<br />

d1 Kind of defrost 0 1 - - - 0<br />

0=Electric defrost, 1=Hot gas defrost<br />

d2 Defrost cutoff temperature. (if P3=1) -99.0 99.0 °C/°F 10<br />

d3 Maximum defrost duration (0= No defrost) 0 99 min 30<br />

d4 Defrost when you turn the instrument on, 0=No, 1=<br />

Yes<br />

0 1 - - - 0<br />

d5 Defrost delay when you turn the instrument on (if d4=1,<br />

see i5)<br />

0 99 min 0<br />

d6 Temperature locked for showing during defrost, 0=No, 1= 0 1 - - - 0<br />

Yes<br />

d7 Dripping duration. Compressor and fan off. 0 15 Min 1<br />

18


d8 Kind of defrost interval (see d0)<br />

0= The defrost will be activated when the instrument will<br />

have remained turned on d0<br />

1= The defrost will be activated when the compressor will<br />

have remained turned on d0<br />

2= the defrost will be activated when the evaporator<br />

temperature will have remained below the temperature d9<br />

the time d0<br />

d9 Evaporator temperature above which the count of the<br />

defrost interval is suspended (if d8=2)<br />

dA Minimum time the compressor must be turned on in order<br />

for the defrost to be activated. (if d1=1)<br />

0 2 - - - 0<br />

-99.0 99.0 °C/°F 0.0<br />

0 99 Min 0<br />

19


Configuration parameters EVK 203<br />

PA Min Max Unit EVK203<br />

ALARM<br />

A0 Probe that activates lower temperature alarm<br />

0=Cabinet probe, 1=Evaporator probe<br />

0 1 - - - 0<br />

A1 Working setpoint for lower temperature alarm -99.0 99.0 °C/°F 0<br />

A2 Kind of lower temperature alarm<br />

0=Alarm not enabled, 1=Relative to the working setpoint<br />

(SP-A1),<br />

2=Absolute (A1)<br />

0 2 - - - 0<br />

A4 Working setpoint upper temperature alarm -99.0 99.0 °C/°F 20.0<br />

A5 Kind of upper temperature alarm, 0=Alarm not enabled,<br />

1=Relative to the working setpoint (SP+A4), 2=Absolute<br />

(A4)<br />

0 2 - - - 0<br />

A6 Upper temperature alarm delay since you turned the<br />

instrument on<br />

0 240 min 120<br />

A7 Temperature alarm delay 0 240 min 15<br />

A8 Delay of upper temperature alarm after dripping 0 240 min 15<br />

EVAPORATOR FAN<br />

F0 Evaporator fan activity during normal operation 0 4 - - - 1<br />

0=off, 1=on, 2=according to the compressor, 3=According<br />

to F1, 4=According to F1 and F2 if the compressor is on,<br />

else off.<br />

F1 Evaporator temperature above which the evaporator fan is<br />

turned off<br />

-99,0 99,0 °C/°F -2,0<br />

F2 Evaporator fan activity during defrost and dripping 0 2 - - - 0<br />

0=Off, 1=On, 2=According to F0<br />

F3 Time which the fan will be off after dripping 0 15 min 2<br />

SERIAL NETWORK<br />

LA Instrument address 1 247 - - - 247<br />

Lb Baud rate<br />

0=2400, 1=4800, 2=9600 and 3=19200<br />

LP Parity<br />

0=None, 1=Odd, 2=Even<br />

0 3 - - - 2<br />

0 2 - - - 2<br />

20


EVCO – instrument description EVK211<br />

General data<br />

*dimensions front 75 x 33 mm, depth 59mm *Working range NTC –40,0 to 105,0°C<br />

PTC –50,0 to 150,0°C<br />

*Power supply 230Vac or 12-24Vac/dc *Possible to defrost through compressor stop<br />

*Programming is made in the front of the<br />

instrument<br />

*Defrost can be programmed for interval and<br />

length<br />

* compressor relay 16A/250VAC<br />

Installing the instrument<br />

Panel mounting with click brackets delivered with the instrument, hole dimensions 71x29 mm.<br />

Surrounding temperature should be between 0 and +55 °C.<br />

Avoid placing the instrument where it is exposed to high humidity or condense and there should be ventilation<br />

around the instrument for cooling.<br />

Wiring diagram<br />

21


As soon as the instrument has power supply, a self check will be done at which all indicator LEDs will flashes.<br />

There after the instrument will be in starting mode and will show the room temperature. The output relay has<br />

voltage free contacts.<br />

Maximum load for the built-in compressor relay is 16A/250V. For greater load an external contactor is needed.<br />

Display<br />

During normal operation the display will show cabinet probe value in the display.<br />

Activating the defrost by hand<br />

Activate by pressing 4s.<br />

Buzzer<br />

Press any key to silence the buzzer.<br />

Working setpoint<br />

Press then let it go, LED will flash and current working setpoint will be shown in the display.<br />

Press or to change working setpoint.<br />

Press or wait 15s. The instrument will return to normal operation with the new working setpoint.<br />

Setting the working setpoint<br />

To go to the parameter <strong>list</strong>:<br />

Press and at the same time for 4 s. PA shows in the display.<br />

Press let go and use or to set the value –19.<br />

Press let go or wait 15s until PA shows in the display.<br />

Press and at the same time 4 s. until the first parameter SP shows in the display.<br />

To select parameter:<br />

• Press or to browse in the parameter <strong>list</strong>.<br />

To modify a parameter:<br />

• Press let go and use or to get the value.<br />

To quit the procedure:<br />

Press and at the same time 4 s. or wait 60 s.<br />

Restoring the default value of configuration parameters<br />

Press and at the same time 4 s . PA shows in the display.<br />

Press and use or to set 743.<br />

Press or wait 15 s until PA shows.<br />

Press and at the same time ca 4 s . dEF shows in the display.<br />

Press and use or to set 149.<br />

Press or wait 15s. The instrument will flash dEF for 4s and then return to normal operation with default values.<br />

Make sure the default value of the parameter is appropriate, in particular if the probes are PTC probes.<br />

Note that also the values for probe type will change if PTC probes are installed.<br />

22


Signals<br />

LED compressor.<br />

If it is lit, the compressor will be turned on.<br />

Flashes at modification of working setpoint or at delay, see par C0 and C2.<br />

LED defrost.<br />

If it is lit, the defrost will be running.<br />

Alarm<br />

LED alarm.<br />

If it is lit, an alarm will be running.<br />

Pr1<br />

Cabinet probe error.<br />

Check the connection, Check parameter P0<br />

The compressor actively will depend on parameters C4 and C5<br />

Configuration parameters EVK211<br />

PA Min Max Unit EVK211<br />

SP Working setpoint r1 r2 °C/°F (1) 0.0<br />

CALIBRATE<br />

CA1 Cabinet probe offset -25.0 25.0 °C/°F (1) 0.0<br />

PROBE<br />

P0 Kind of probe, 0=PTC, 1=NTC 0 1 - - - 1<br />

P1 Decimal point Celsius degree<br />

0 1 - - - 0<br />

0=No, 1=Yes<br />

P2 Celsius/Fahrenheit, 0=°C 1=°F 0 1 - - - 0<br />

P5 Quantity to show during normal operation<br />

0 1 ---- 0<br />

0=cabinet temperature<br />

1=working setpoint<br />

MAIN REGULATOR<br />

r0 Working setpoint differential 0.1 15.0 °C/°F (1) 2.0<br />

r1 Minimum working setpoint -99.0 r2 °C/°F (1) 0<br />

r2 Maximum working setpoint r1 99.0 °C/°F (1)<br />

r3 Locking the working setpoint<br />

0 1 --- 12<br />

1= Yes<br />

COMPRESSOR PROTECTIONS<br />

C0 Delay since you turned on the instrument 0 240 min 0<br />

C1 Compressor delay between on/off also minimum time 0 240 min 0<br />

between two activations in succession of the compressor<br />

C2 Minimum time the compressor remains turned off 0 240 min 0<br />

C3 Minimum time the compressor remains turned on 0 240 s 0<br />

C4 Time the compressor remains turned off during the<br />

0 240 min 10<br />

cabinet probe error; also look at C5<br />

C5 Time the compressor remains turned on during the<br />

0 240 min 10<br />

cabinet probe error; also look at C4<br />

DEFROST<br />

d0 Defrost interval (0=defrost never activated) 0 99 tim 12<br />

d3 Defrost duration (0= defrost never activated) 0 99 min 30/60<br />

d4 Defrost when you turn on the instrument<br />

0 1 - - - 0<br />

0=No, 1=Yes<br />

d5 Defrost delay when you turn on the instrument<br />

0 99 min 0<br />

(Only if d4=1)<br />

d6 Temperature locked during defrost<br />

0=No, 1=yes<br />

0 1 - - - 1<br />

23


d8 Kind of defrost interval<br />

0 1 --- 0<br />

0= defrost never activated when the instrument will have<br />

remained turned on the time d0<br />

1= defrost activated when the compressor will have<br />

remained turned on the time d0<br />

TEMPERATURE ALARMS<br />

A1 Temperature below which the lower temperature alarm is -99 99 °C/°F (1) 0<br />

activated, also look at A2 (4)<br />

A2 Kind of lower temperature alarm<br />

0 2 --- 0<br />

0= alarm not enabled<br />

1= relative to the working setpoint (or working setpoint -<br />

A1)<br />

2= absolute (or A1)<br />

A4 Temperature above which the upper temperature alarm is -99 99 °C/°F (1) 20.0<br />

activated, also look at A5 (4)<br />

A5 Kind of upper temperature alarm<br />

0 2 --- 0<br />

0= alarm not enabled<br />

1= relative to the working setpoint (or working setpoint -<br />

A4)<br />

2= absolute (or A4)<br />

A6 Upper temperature alarm delay since you turn on the 0 240 min 120<br />

instrument<br />

A7 Temperature alarm delay 0 240 min 15<br />

A8 Upper temperature alarm delay since the end of defrost 0 240 min 15<br />

SERIAL NETWORK<br />

LA Instrument address 1 247 --- 247<br />

Lb Baud rate<br />

0 3 --- 2<br />

0= 2,400 baud<br />

1= 4,800 baud<br />

2= 9,600 baud<br />

3= 19,200 baud<br />

LP Parity<br />

0= none<br />

1= odd<br />

2= even<br />

0 2 --- 2<br />

24

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!