catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
catalog TELE - CONTA-CLIP
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
OVER<br />
UNDER<br />
WIN<br />
Overcurrent monitoring<br />
Undercurrent monitoring<br />
Monitoring the window between Min and Max<br />
Functions<br />
Sensing & Monitoring Relays Series GAMMA<br />
Current monitoring in 1-phase mains<br />
OVER+Latch<br />
UNDER+Latch<br />
WIN+Latch<br />
Overcurrent monitoring with fault latch<br />
Undercurrent monitoring with fault latch<br />
Monitoring the window between Min and Max with fault latch<br />
< Overcurrent monitoring (G2IO)<br />
< UNDERcurrent monitoring (G2IU)<br />
< Supply voltage via PowerModules or DC power supply<br />
< 1 CO contact<br />
< Width 22,5mm<br />
< Industrial design<br />
Measuring range 20mA AC/DC,<br />
supply voltage: 24V AC/DC<br />
Measuring range 5A AC/DC with<br />
Powermodule 400V AC<br />
Measuring range 2A AC/DC,<br />
supply voltage: 24V AC/DC<br />
Connections<br />
G2IM5AL20<br />
G2IM5AL10<br />
G2IM2AL20 24-240V<br />
types G2IO10A10 G2IO5A10 G2IU10A10 G2IU5A10<br />
24VAC/DC<br />
15<br />
25<br />
15<br />
25<br />
16 18<br />
26 28<br />
16 18<br />
26 28<br />
Art.No. (PQ1) 2390408 2390403 2390409 2390404<br />
Art.No. (PQ10) - - - -<br />
EAN13-Code 900866200271 900866200266 900866200272 900866200267<br />
Width 22.5mm<br />
Dimensions<br />
Measured variable<br />
Measuring ranges<br />
Current AC/DC<br />
AC Sinus (48 to 63Hz)<br />
100mA AC/DC; terminals K-I1(+)<br />
1A AC/DC; terminals K-I2(+)<br />
10A AC/DC; terminals K-I3(+)<br />
Current AC/DCAC Sinus (48 to<br />
63Hz)<br />
20mA AC/DC; terminals K-I1(+)<br />
1A AC/DC; terminals K-I2(+)<br />
5A AC/DC; terminals K-I3(+)<br />
Current AC/DC<br />
AC Sinus (48 to 63Hz)<br />
100mA AC/DC; terminals K-I1(+)<br />
1A AC/DC; terminals K-I2(+)<br />
10A AC/DC; terminals K-I3(+)<br />
Current AC/DC<br />
AC Sinus (48 to 63Hz)<br />
20mA AC/DC; terminals K-I1(+)<br />
1A AC/DC; terminals K-I2(+)<br />
5A AC/DC; terminals K-I3(+)<br />
Controls max • min • Delay max • min • Delay max • min • Delay max • min • Delay<br />
Indicators (LEDs) U • max • min • R U • max • min • R U • max • min • R U • max • min • R<br />
Functions OVER OVER UNDER UNDER<br />
Switching threshold max. 10% to 100% from I N<br />
10% to 100% from I N<br />
10% to 100% from I N<br />
10% to 100% from I N<br />
Switching threshold min. 5% to 95% from I N<br />
5% to 95% from I N<br />
5% to 95% from I N<br />
5% to 95% from I N<br />
Tripping delay 0,2s to 10s 0,2s to 10s 0,2s to 10s 0,2s to 10s<br />
Start-up<br />
suppression time<br />
- - - -<br />
Fault latch - - - -<br />
Supply<br />
PowerModule TR2 or SNT2<br />
terminals A1-A2<br />
PowerModule TR2 or SNT2<br />
terminals A1-A2<br />
PowerModule TR2 or SNT2<br />
terminals A1-A2<br />
PowerModule TR2 or SNT2<br />
terminals A1-A2<br />
Output<br />
1 CO contact<br />
250V, 5A AC<br />
1 CO contact<br />
250V, 5A AC<br />
1 CO contact<br />
250V, 5A AC<br />
1 CO contact<br />
250V, 5A AC<br />
Width 22,5mm 22,5mm 22,5mm 22,5mm<br />
Certificates CE • cULus • GOST CE • cULus • GOST CE • cULus • GOST CE • cULus • GOST<br />
Mechanical<br />
design<br />
Self-extinguishing plastic housing, IP rating IP40 • Mounted on DIN-Rail TS 35 in accordance with EN 60715 • Mounting position any •<br />
Shockproof terminal connection according to VBG 4 (PZ1 required) • IP rating IP20 • Tightening torque max. 1Nm<br />
Terminal capacity<br />
1 x 0,5 to 2,5mm² with/without multicore cable end • 1 x 4mm² without multicore cable end • 2 x 0,5 to 1,5mm² with/without multicore cable end<br />
• 2 x 2,5mm² flexible without multicore cable end<br />
Ambient<br />
conditions<br />
Ambient temperature: -25 to 55°C (in accordance with IEC 60068-1); -25 to 40°C (in accordance with UL 508) • Storage temperature: -25 to<br />
+70°C • Transport temperature: -25 to +70°C • relative humidity: 15% to 85% (in accordance with IEC 60721-3-3 class 3K3) • Pollution degree:<br />
3 (in accordance with IEC 60664-1) • Vibration resistance: 10 to 55Hz 0,35mm (in accordance with IEC 60068-2-6) • Shock resistance: 15g<br />
11ms (in accordance with IEC 60068-2-27)<br />
Accessories<br />
PowerModules TR2 (12 to 440V AC) • DC power supply SNT2 24V DC • Current Transformers Series DSW and WSW • sealable intervention<br />
protection shield FA-G2<br />
Page 36<br />
www.tele-online.com<br />