<strong>3RW3</strong> <strong>semiconductor</strong> <strong>motor</strong> <strong>control</strong> <strong>unit</strong><br />

8.3.3.4 Combining the 3RT contactor with the 3RB10 electronic overload relay and <strong>3RW3</strong> <strong>soft</strong><br />

<strong>starter</strong><br />

The contactor, electronic overload relay, and <strong>soft</strong> <strong>starter</strong> can be connected in<br />

two ways:<br />

• Combining a 3RT1 contactor with an attached 3 RB10 electronic overload<br />

relay, a connecting lead, and a <strong>3RW3</strong>0/31 <strong>soft</strong> <strong>starter</strong><br />

• Combining a 3RT1 contactor with a connecting lead and a combination of<br />

a <strong>3RW3</strong>0/01 <strong>soft</strong> <strong>starter</strong> with an attached 3RB10 electronic overload relay<br />

3RT + 3RB10 + connecting<br />

lead + <strong>3RW3</strong><br />

Rail 1:<br />

Combination of a 3RT1 contactor and<br />

a 3RB10 electronic overload relay<br />

3RT<br />

3RB10<br />

Rail 2:<br />

<strong>3RW3</strong>0/31 <strong>soft</strong> <strong>starter</strong><br />

Fig. 8-13: 3RT+3RB10+<strong>3RW3</strong> combination<br />

3RW<br />

Connecting<br />

lead<br />

Minimum clearance<br />

For thermal reasons, a minimum clearance is necessary between the contactor/overload<br />

relay combination and the <strong>soft</strong> <strong>starter</strong>, as is a minimum<br />

length of the connecting leads.<br />

The following table specifies the minimum clearances and minimum lengths<br />

of the connecting leads for the various frame sizes:<br />

Frame size<br />

Minimum clearance between<br />

rail 1 and rail 2<br />

(center to center) in mm<br />

Minimum length of the<br />

connecting lead<br />

in mm<br />

S00 160 100<br />

S0 200 150<br />

S2 240 200<br />

S3 300 250<br />

Table 8-11: 3RT + 3RB10 + <strong>3RW3</strong> installation guidelines, minimum clearances/minimum lengths<br />