20.01.2015 Views

8 3RW3 semiconductor motor control unit (soft starter) - Siemens ...

8 3RW3 semiconductor motor control unit (soft starter) - Siemens ...

8 3RW3 semiconductor motor control unit (soft starter) - Siemens ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>3RW3</strong> <strong>semiconductor</strong> <strong>motor</strong> <strong>control</strong> <strong>unit</strong><br />

Conductor cross-sections<br />

Screw-type terminals<br />

Auxiliary conductors:<br />

(1 or 2 conductors connectable) Single-core mm 2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) in acc. with IEC 60 947; max. 2 x (0.75 to 4)<br />

for standard screwdrivers<br />

Finely stranded with wire mm 2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5)<br />

end ferrule<br />

size 2 and Pozidriv 2<br />

AWG cables,<br />

single- or multi-core AWG 2 x (18 to 14)<br />

- Terminal screws M 3<br />

- Tightening torque Nm<br />

lb.in<br />

Main conductors:<br />

0.8 to 1.0<br />

7.1 to 8.9<br />

Single-core mm 2 2 x (0.75 to 16)<br />

Finely stranded with wire<br />

end ferrule<br />

mm 2 2 x (0.75 to 16)<br />

1 x (0.75 to 25)<br />

Multi-core mm 2 2 x (0.75 to 25)<br />

1 x (0.75 to 35)<br />

AWG cables,<br />

single- or multi-core AWG 2 x (18 to 3)<br />

1 x (18 to 2)<br />

2 x (10 to 50)<br />

1 x (10 to 70)<br />

2 x (10 to 1/0)<br />

1 x (10 to 2/0)<br />

- Terminal screws M 6, box terminal, PZ2 M6 (Allan screw)<br />

- Tightening torque Nm<br />

lb.in<br />

3 to 4.5<br />

27 to 40<br />

4 to 6<br />

35 to 53<br />

General specifications<br />

Standard<br />

Parameters<br />

EMC noise imm<strong>unit</strong>y<br />

Electrostatic discharge (ESD) IEC 1000-4-2, Severity 3: 6/8 kV<br />

El. magn. RF fields IEC 1000-4-3 Frequency range: 80 to 1000 MHz with 80 % at 1 kHz<br />

Severity 3, 10 V/m<br />

Conducted RF disturbance IEC 61000-4-6<br />

EN 60 947-4-2<br />

SN-IACS<br />

Frequency range: 80 MHz to 1000 MHz with 80 %<br />

at 1 kHz<br />

10 V at 0.15 MHz to 80 MHz<br />

3 V at 10 kHz to 80 MHz<br />

Burst IEC 1000-4-4 Severity 3: 1/2 kV<br />

Surge IEC 1000-4-5 Severity 3: 1/2 kV<br />

EMC emitted interference<br />

EMC radio interference intensity CISPR 11/09.1990 Limit value of class B at 30 MHz to 1000 MHz<br />

Radio interference voltage CISPR 11/09.1990<br />

EN 60 947-4-2<br />

(0.15 MHz to 30 MHz): device class A (industry)<br />

1 ) IP20 only with attached box terminal (delivery state). Without box terminal IP00.<br />

2 ) Device class B (public power supply networks) is complied with only in the case of variants <strong>3RW3</strong>.-1AB0. with <strong>control</strong> supply voltage UC<br />

of 24 V. For the <strong>3RW3</strong>.-1A.1. variants with a <strong>control</strong> supply voltage UC of 110 V to 230 V, single-stage filters (e.g. type B84143-A...) must be<br />

connected upstream.<br />

SIRIUS System Manual<br />

8-44 GWA 4NEB 430 0999-02c