GRUNDFOS CIM 300 BACnet MS/TP

BACnet Protocol Implementation Conformance Statement

Grundfos CIM 300 BACnet MS/TP for Grundfos pumps and boosters

001101010011110001011101010101110000101010011001010001010100101110010101010101010101


GRUNDFOS CIM 300 BACnet MS/TP

Grundfos CIM 300 BACnet MS/TP for pumps

Document date: September 7 th , 2011

Vendor Name: Grundfos

Product Name: CIM

Product Model Number: 300 BACnet MS/TP

Application Software: V01.14

Firmware Revision: V01.14

BACnet Protocol Rev.: 1.4

Product Description:

The CIM 300 BACnet MS/TP interface from Grundfos enables BACnet communication with Grundfos pumps that have a GENIbus interface. The

communication interface module can either be installed directly in the Grundfos pump / system to enable BACnet MS/TP communication, or in an

external power supply unit (called CIU) connected to the pump / booster. In both cases, the communication interface module is the same.

Note: The CIM 300 BACnet MS/TP has passed the BTL test in June 2010.

BACnet Standardized Device Profile (Annex L):

� BACnet Operator Workstation (B-OWS)

� BACnet Building Controller (B-BC)

� BACnet Advanced Application Controller (B-AAC)

� BACnet Application Specific Controller (B-ASC)

� BACnet Smart Sensor (B-SS)

� BACnet Smart Actuator (B-SA)

CIU

CIM 300

BACnet MS/TP


GRUNDFOS CIM 300 BACnet MS/TP

BACnet Interoperability Building Blocks Supported:

Data sharing services:

Name

ReadProperty

ReadPropertyMultiple

WriteProperty

WritePropertyMultiple

SubscribeCOV

ConfirmedCOVNotification

UnconfirmedCOVNotification

Device management services:

Name

Who-is / I-am

Who-has / I-have

DeviceCommunicationControl

BACnet BIBB

DS-RP-B

DS-RPM-B

DS-WP-B

DS-WPM-B

DS-COV-B

BACnet BIBB

DM-DDB-A

DM-DDB-B

DM-DOB-B

DM-DCC-B

Segmentation Capability:

� Segmented requests supported Window Size

� Segmented responses supported Window Size

Note: Segmentation is not supported


GRUNDFOS CIM 300 BACnet MS/TP

Standard Object Types Supported:

Object type

Analog input

Analog output

Analog value

Binary input

Binary output

Multistate input

Multistate output

Device

Supported









Dynamically

Createable









Dynamically

Deletable






Data Link Layer Options:

� BACnet IP, (Annex J)

� BACnet IP, (Annex J), Foreign Device

� ISO 8802-3, Ethernet (Clause 7)

� ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)

� ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s) ____________

� MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800

� MS/TP slave (Clause 9), baud rate(s):

� Point-To-Point, EIA 232 (Clause 10), baud rate(s):

� Point-To-Point, modem, (Clause 10), baud rate(s):

� LonTalk, (Clause 11), medium: __________

� Other:




GRUNDFOS CIM 300 BACnet MS/TP

Device Address Binding:

Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)

�Yes � No

Networking Options:

� Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.

� Annex H, BACnet Tunneling Router over IP

� BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by Foreign Devices? � Yes � No

Character Sets Supported:

Indicating support for multiple character sets does not imply that they can all be supported simultaneously.

� ANSI X3.4 � IBM/Microsoft DBCS � ISO 8859-1 � UTF-8

� ISO 10646 (UCS-2) � ISO 10646 (UCS-4) � JIS C 6226

Types of non-BACnet equipment supported:

Grundfos MAGNA circulators *

Grundfos UPE Series 2000 (UPE 80-120 and 100-120) circulators

Grundfos CRE, CRNE, CRIE, MTRE, CME (single-phase and three-phase, up to 11 kW + three-phase, 11-22 kW)

Grundfos TPE, TPE Series 2000, NBE, NKE (single-phase and three-phase, up to 11 kW + three-phase, 11-22 kW)

Grundfos CUE frequency converter (all versions, 0.55 - 250 kW).

Grundfos CU 351 Hydro MPC * and Multi-E boosters

Grundfos CU 351 Control MPC * Multi Pump Controller

Grundfos CU 323 Multi-B booster

* = Additional Grundfos GENIbus module required


GRUNDFOS CIM 300 BACnet MS/TP

Complete object list (For pumps)

Object ID

DEVICE

AV, 0

AV, 1

BO, 0

MO, 0

MO, 1

MO, 2

BO, 1

BO, 2

BO, 3

BO, 4

AO, 0

MI, 0

MI, 1

MI, 2

MI, 3

BI, 0

BI, 1

BI, 2

Object_Name

Device Object

Custom device object instance number

BACnet watchdog

Set control source

Set control mode

Set operating mode

Product simulation

Relay 1 control

Relay 2 control

Set direction

Reset fault

Set setpoint

Actual control mode

Actual operating mode

Next bearing-service type

CIM status

Control source status

Actual direction

Rotation status

Object ID

BI, 3

BI, 4

BI, 11

BI, 12

BI, 13

BI, 14

BI, 15

AI, 0

AI, 1

AI, 2

AI, 3

AI, 4

AI, 5

AI, 6

AI, 7

AI, 8

AI, 9

AI, 10

AI, 11

Object_Name

At minimum speed

At maximum speed

Digital input 1 status

Digital input 2 status

Digital input 3 status

Digital output 1 status

Digital output 2 status

Fault code

Warning code

Time to bearing service

Capacity

Head

Flow

Relative performance

Speed

Frequency

Actual setpoint

Motor current

DC link voltage

Note: Not all objects are supported by each pump type. Please contact Grundfos for details.

Object ID

AI, 12

AI, 13

AI, 14

AI, 15

AI, 16

AI, 17

AI, 18

AI, 19

AI, 20

AI, 21

AI, 22

AI, 23

AI, 24

AI, 25

AI, 26

AI, 27

AI, 28

AI, 29

AI, 30

Object_Name

Motor voltage

Power

Remote flow

Inlet pressure

Remote pressure

Level

Power electronic temperature

Motor temperature

Remote temperature

Electronic temperature

Fluid temperature

Bearing temperature drive end

Bearing temperature non-drive end

Auxilary sensor input

Specific energy

Runtime

Total ontime

Torque

Energy consumption


GRUNDFOS CIM 300 BACnet MS/TP

Complete object list (For boosters, page 1 of 2)

Object ID

DEVICE

AV, 0

AV, 1

AV, 4

AV, 5

AV, 6

AV, 7

AV, 8

BO, 0

MO, 0

MO, 1

MO, 2

BO, 4

BO, 5

AO, 0

AO, 1

AO, 2

AO, 3

AO, 4

MI, 0

MI, 1

MI, 3

MI, 4

MI, 5

MI, 6

MI, 7

MI, 8

MI, 9

MI, 10

MI, 11

BI, 0

Object_Name

Device Object

Custom device object instance number

BACnet watchdog

Simulation event code

Simulation device type

Simulation device number

Simulation action type

Simulation reset type

Set control source

Set control mode

Set operating mode

Product simulation

Reset fault

Fault simulation

Set setpoint

Tank filling start limit

Tank filling stop limit

Tank filling alarm high limit

Tank filling warning low limit

Actual control mode

Actual operating mode

CIM status

Subpump 1 control source

Subpump 2 control source

Subpump 3 control source

Subpump 4 control source

Subpump 5 control source

Subpump 6 control source

Application type

Feedback sensor unit

Control source status

Object ID

BI, 2

BI, 3

BI, 4

BI, 5

BI, 6

BI, 7

BI, 8

BI, 9

BI, 10

BI, 11

BI, 12

BI, 13

BI, 14

BI, 15

BI, 16

BI, 17

BI, 18

BI, 19

BI, 20

BI, 21

BI, 22

BI, 23

BI, 24

BI, 25

BI, 26

BI, 27

BI, 28

BI, 32

BI, 33

BI, 34

BI, 35

Object_Name

Rotation status

At minimum speed

At maximum speed

Standby pumps active

Pressure relief active

Soft pressure active

Low flow boost active

Low flow stop active

Alternative setpoint active

Digital input 1 status

Digital input 2 status

Digital input 3 status

Digital output 1 status

Digital output 2 status

Subpump 1 presence

Subpump 1 communication status

Subpump 2 presence

Subpump 2 communication status

Subpump 3 presence

Subpump 3 communication status

Subpump 4 presence

Subpump 4 communication status

Subpump 5 presence

Subpump 5 communication status

Subpump 6 presence

Subpump 6 communication status

Fault simulation status

Subpump 1 auto mode

Subpump 2 auto mode

Subpump 3 auto mode

Subpump 4 auto mode

Note: Not all objects are supported by each booster type. Please contact Grundfos for details.

Object ID

BI, 36

BI, 37

AI, 0

AI, 1

AI, 3

AI, 4

AI, 5

AI, 6

AI, 9

AI, 10

AI, 13

AI, 15

AI, 16

AI, 17

AI, 20

AI, 25

AI, 27

AI, 30

AI, 33

AI, 34

AI, 35

AI, 36

AI, 37

AI, 38

AI, 39

AI, 40

AI, 41

AI, 42

AI, 43

AI, 44

AI, 45

Object_Name

Subpump 5 auto mode

Subpump 6 auto mode

Fault code

Warning code

Capacity

Head

Flow

Relative performance

Actual setpoint

Motor current

Power

Inlet pressure

Remote pressure

Level

Remote temperature

Auxilary sensor input

Runtime

Energy consumption

Ambient temperature

Forward temperature

Return temperature

Differential temperature

Outlet pressure

Feed tank level

Subpump 1 fault code

Subpump 1 runtime

Subpump 1 speed

Subpump 2 fault code

Subpump 2 runtime

Subpump 2 speed

Subpump 3 fault code


GRUNDFOS CIM 300 BACnet MS/TP

Complete object list (For boosters, page 2 of 2)

Object ID

AI, 46

AI, 47

AI, 48

AI, 49

AI, 50

AI, 51

AI, 52

AI, 53

AI, 54

AI, 55

AI, 56

AI, 57

AI, 58

AI, 59

AI, 60

AI, 61

AI, 62

AI, 63

AI, 64

AI, 65

AI, 66

AI, 67

AI, 68

AI, 69

AI, 70

AI, 71

AI, 72

AI, 73

AI, 74

AI, 75

AI, 76

Object_Name

Subpump 3 runtime

Subpump 3 speed

Subpump 4 fault code

Subpump 4 runtime

Subpump 4 speed

Subpump 5 fault code

Subpump 5 runtime

Subpump 5 speed

Subpump 6 fault code

Subpump 6 runtime

Subpump 6 speed

Remote temperature 2

User setpoint

Analogue influence

Power-on counter

Subpump 1 line current

Subpump 1 power consumption

Subpump 1 motor temperature

Subpump 1 number of starts

Subpump 2 line current

Subpump 2 power consumption

Subpump 2 motor temperature

Subpump 2 number of starts

Subpump 3 line current

Subpump 3 power consumption

Subpump 3 motor temperature

Subpump 3 number of starts

Subpump 4 line current

Subpump 4 power consumption

Subpump 4 motor temperature

Subpump 4 number of starts

Object ID

AI, 77

AI, 78

AI, 79

AI, 80

AI, 81

AI, 82

AI, 83

AI, 84

AI, 85

AI, 86

AI, 87

AI, 88

AI, 89

AI, 90

AI, 91

Object_Name

Subpump 5 line current

Subpump 5 power consumption

Subpump 5 motor temperature

Subpump 5 number of starts

Subpump 6 line current

Subpump 6 power consumption

Subpump 6 motor temperature

Subpump 6 number of starts

Minimum of feedback sensor

Maximum of feedback sensor

Tank filling actual tank height

Tank filling actual start limit

Tank filling actual stop limit

Tank filling actual alarm high limit

Tank filling actual warning low limit

Note: Not all objects are supported by each booster type. Please contact Grundfos for details.