Accurate, Flexible Protection<br />

While electromechanical overload<br />

relays pass motor current through<br />

heating elements to provide an<br />

indirect imitation of motor heating,<br />

the <strong>C396</strong> electronic overload directly<br />

measures motor current through<br />

integrated current transformers,<br />

more accurately predicting motor<br />

overload potential.<br />

The electronics identify excessive<br />

current or phase loss more accurately<br />

and react to the condition with<br />

greater speed, reliability and<br />

repeatability than a traditional<br />

electromechanical device. Because<br />

the second leading cause of motor<br />

Panel Mounting Adapter (Optional)<br />

Line Terminations<br />

Identification Marking Strip<br />

Tamper Proof Cover<br />

FLA Setting Dial<br />

Mechanical Trip Actuator<br />

Reset Button (Selectable Manual/Automatic)<br />

Trip Status Indicator<br />

Isolated Auxiliary Contacts—1NO/1NC<br />

DIP Switches for Selectable Trip Class<br />

Load Terminations<br />

failure is phase loss, the <strong>C396</strong> has<br />

a phase loss detection circuit that<br />

protects against lengthy motor<br />

overheating and quickly relieves<br />

motor stress. Whereas electromechanical<br />

overloads can take up<br />

to 40 seconds to respond to a<br />

phase loss condition, the average<br />

reaction time for the <strong>C396</strong> is just<br />

3 seconds!<br />

Easy to select and apply, the selfpowered<br />

design means that no<br />

external power source is required,<br />

allowing the <strong>C396</strong> overload to be<br />

installed just like a traditional<br />

electromechanical overload relay.<br />

Device set-up is quick and easy;<br />

simply dial the setting<br />

potentiometer to the motor FLA<br />

rating and the overload is ready to<br />

protect. To further improve<br />

application flexibility, the <strong>C396</strong><br />

comes standard with a selectable<br />

trip class (5, 10, 20, 30) setting and<br />

can be used in single-phase or<br />

three-phase power applications.<br />

There is no need to order different<br />

part numbers—the <strong>C396</strong> can<br />

handle both applications in the<br />

same unit.<br />

Other features that allow<br />

the <strong>C396</strong> to provide highly<br />

accurate protection include:<br />

• Setting accuracy +/– 5%<br />

(electromechanical is<br />

approximately 10–15%)<br />

• Repeat accuracy +/– 1%<br />

• Phase imbalance protection to<br />

maximize permissible motor output<br />

Not only does the <strong>C396</strong> provide<br />

accurate, reliable protection for<br />

your motor, but it allows you the<br />

flexibility you need to keep your<br />

motors running at their highest<br />

possible potential.<br />

EATON CORPORATION <strong>Cutler</strong>-<strong>Hammer</strong> <strong>C396</strong> Electronic Overload • www.eaton.com • 877-ETN CARE<br />