Cooling filler panels - Fatra

fatra.cz

Cooling filler panels - Fatra

COOLING

FILLER

PANELS

www.fatra.cz

Coupled block

of panels

cooling filler

INSPIRED BY NATURE

IMPROVED BY TECHNOLOGY


Panels serve as filler in cooling towers with a view to extend inside surface and thus increase cooling efficiency. The filler

may also be used for bio-filtration of polluted air, desulphurization of biogas, waste water purification, etc.

It is a plastic moulding with shaped channels designed for discharge of the cooled medium (water), this medium

subsequently cools down industrial or power-station facilities.

Panels are moulded mechanically from non-plasticized PVC of black to dark grey colour, thickness 0.35-0.45 mm.

CFPs are manufactured in various profile types and sizes.

Panel coupling methods:

• by gluing • mechanically (using jointing components) • by welding

DCHV 20 a dCHV 20 b dCHV 20 C dCHV 25 A

Labelling of individual CFP types is based on:

a) abbreviated title of the cooling filler panel

b) nominal dimensions in v mm

c) profile type indicated with capital letter

d) design characterised by initial thickness of the material in mm stated behind the slash

Labelling example:

DCHV 1000 x 500 x 20 C / 0,35

length 1000 mm width 500 mm profile height 20 mm profile type primary material thickness 0,35 mm

Benefits of cooling filler (with vertical flow for mass and energy transfer):

• Low pressure loss • Easy installation • Long durability • High efficiency

Basic technical data:

DCHV 20 A DCHV 20 B DCHV 20 C DCHV 25 A

Material PVC PVC PVC PVC

Foil thickness 0,35–0,45 mm 0,35–0,45 mm 0,35–0,45 mm 0,35–0,45 mm

Thermal stability -40 °C to +60 °C -40 °C to +60 °C -40 °C to +60 °C -40 °C to +60 °C

Wave height 20 mm 20 mm 20 mm 25 mm

Block length 1000–2400 mm 1000–2400 mm 1000–2400 mm 1000–2000 mm

Block width 500 mm (250 mm) 500 mm (250 mm) 500 mm (250 mm) 500 mm (250 mm)

Foil connection method by gluing by gluing by gluing or mechanically by gluing

Packaging 1000 pieces 1000 pieces 1500 pieces 1000 pieces

Heat-exchange surface 146 m 2 /m 3 152 m 2 /m 3 130 m 2 /m 3

Panels are resistant against water, alcohols, paraffin hydrocarbons, inorganic acids (e.g. HCl, HF, H 2

SO 4

) and alkalis (e.g. NaOH,

KOH), unless they have oxidizing effect. They swell in organic acids.

Contact: Fatra, a. s., třída Tomáše Bati 1541, CZ-763 61 Napajedla

Plant: Komenského 75, CZ-768 11 Chropyně, tel.: +420 573 329 386, email: info@fatra.cz, www.fatra.cz