Modules<br />

Head modules<br />

PSSu H PLC1 FS SN SD(-T)<br />

PSSu H PLC1 FS SN SD-T: Derating diagram for infeed for module supply: Permitted ambient temperature T dependent<br />

on load current I<br />

T [°C]<br />

100<br />

80<br />

60<br />

40<br />

3.2<br />

20<br />

0<br />

0,2 0,4 0,6 0,8<br />

1 1,2 1,4 1,6 1,8 2<br />

I [A]<br />

SafetyNET p<br />

][Funktionsbeschreibung SN p PLC1<br />

Functions<br />

The SafetyNET p interface enables<br />

safety-related and non-safety-related<br />

data transfer between the PSSu<br />

system and other network subscribers.<br />

The head module receives signals<br />

from other network subscribers; it<br />

processes these signals in the user<br />

program and passes them on to the<br />

connected input/output modules.<br />

The head module receives signals<br />

from the connected input/output<br />

modules; it processes these signals<br />

in the user program and passes<br />

them on to the other network subscribers.<br />

If a fault occurs, the module switches<br />

the connected failsafe outputs to<br />

a safe condition.<br />

MAC address<br />

The MAC address is a factory-set<br />

default. It can found on the labelling<br />

strip on the front of the module.<br />

INFORMATION<br />

Further information on SafetyNET p<br />

can be found in the "PSS 4000 <strong>System</strong><br />

Description".<br />

Wiring<br />

][Verdrahtung Kopf Versorgung<br />

The requirements of the supply<br />

voltages can be found in the chapter<br />

entitled "Technical Details".<br />

Safe electrical isolation must be ensured<br />

for the external power supplies<br />

that generate the supply<br />

voltages. Failure to do so could result<br />

in electric shock.<br />

The external power supplies must<br />

comply with the current applicable<br />

standard EN 60950-1, EN 61140,<br />

EN 50178 or EN 61558-1.<br />

The maximum current load for the<br />

periphery supply on the module bus<br />

is 10 A. Please refer to the derating<br />

diagram in the chapter entitled<br />

"Function Description".<br />

The maximum current load for the<br />

C-rail is 10 A. Please refer to the derating<br />

diagram in the chapter entitled<br />

"Function Description".<br />

Permitted infeed at the C-rail:<br />

– PE<br />

– 0 V<br />

– Shield<br />

– - 30 VDC ... +30 VDC<br />

– - 48 VAC ... + 48 VAC<br />

Earth the 0 V supply on the periphery<br />

supply or monitor each supply<br />

group for earth faults.<br />

The connection of the 0 V supply to<br />

the central earth bar or earth fault<br />

monitor must be in accordance with<br />

the relevant national regulations<br />

(e.g. EN 60204-1, NFPA 79:17-7,<br />

NEC: Article 250).<br />

Details of the minimum range for<br />

cable cross sections on connection<br />

terminals can be found in the section<br />

entitled "Technical Details".<br />

Use copper wiring.<br />

3.2-68<br />

<strong>Pilz</strong> <strong>GmbH</strong> & <strong>Co</strong>. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany<br />

Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de<br />

PSSu-2011-01