CONDITION<br />
3.4 ALTERNATING CURRENT GENERATOR<br />
POSSIBLE CAUSE<br />
REMEDY/<br />
REFERENCE<br />
SECTION<br />
No voltage<br />
Low voltage<br />
Fluctuating voltage (May be indicated<br />
by flickering lights)<br />
Loss of residual magnetism in exciter field<br />
Circuit breaker tripped<br />
Open in stator windings<br />
Open or short in rotating rectifiers<br />
Short circuited<br />
Open in alternator field<br />
Shorted exciter armature<br />
Low engine speed<br />
Excessive load<br />
High resistance connections - connections<br />
warm or hot<br />
Shorted field<br />
Fluctuating speed<br />
Irregular speed of engine<br />
Loose terminal or load connections<br />
Defective bearing causing uneven air gap<br />
4.5.1.a.<br />
Check<br />
4.5.4<br />
4.5.1.c.<br />
4.5.4<br />
4.5.4<br />
4.5.4<br />
4.4.7<br />
Check<br />
Tighten<br />
4.5.4<br />
High voltage Excessive engine speed 4.4.7<br />
4.4.7<br />
Engine Manual<br />
Tighten<br />
4.5.1.4.5.3<br />
Overheating<br />
Mechanical Noise<br />
Generator frame produces shock<br />
when touched<br />
Generator overloaded<br />
Clogged ventilating screens<br />
High temperature surrounding generator<br />
Insufficient circulation<br />
Unbalanced load<br />
Dry bearing<br />
Defective bearing<br />
Rotor scrubbing on stator<br />
Loose laminations<br />
Loose or misaligned coupling<br />
Static charge<br />
Grounded armature of field coil<br />
Check<br />
Clean<br />
4.4.4<br />
4.4.4<br />
Balance<br />
4.5.1.4.5.3<br />
4.5.1.4.5.3<br />
4.5.1.4.5.3<br />
4.5.4<br />
4.5.4<br />
Check ground to<br />
frame<br />
4.5.4<br />
T-266<br />