17.11.2012 Views

The ABC's of Fire Alarm Systems - Part XI - IMSA

The ABC's of Fire Alarm Systems - Part XI - IMSA

The ABC's of Fire Alarm Systems - Part XI - IMSA

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>The</strong> ABC’s <strong>of</strong> <strong>Fire</strong> <strong>Alarm</strong> <strong>Systems</strong> - <strong>Part</strong> <strong>XI</strong><br />

By Anthony J. Shalna © 2009 Principal <strong>IMSA</strong> Representative to the Automatic <strong>Fire</strong> <strong>Alarm</strong> Association<br />

President: Southeastern Signalmen <strong>of</strong> Massachusetts<br />

Retired Approvals Manager: Gamewell-FCI by Honeywell<br />

MASTER BOXES<br />

proved for a shunt trip to manual<br />

stations and waterflow switches.<br />

<strong>The</strong> use <strong>of</strong> dry, control panel contacts<br />

for setting <strong>of</strong>f shunt trip is also<br />

not permitted as supervision is impossible<br />

with this arrangement.<br />

In the last installment we discussed<br />

how a typical municipal fire alarm<br />

system works. Electromechanical<br />

street boxes which contain a clockwork<br />

mechanism having normally<br />

closed contacts are connected in series<br />

in a series circuit, also known as<br />

a “balloon loop”, since this is what<br />

the circuit resembles. In smaller<br />

systems, other devices may be intermingled<br />

with the boxes. <strong>The</strong> loop<br />

may include fire stations containing<br />

single stroke gongs, punch registers<br />

or solenoid valves that operate air<br />

horns. When a box is pulled, the<br />

pull hook pushes a trip lever on<br />

the mechanism downward, starting<br />

the mechanism that contains<br />

holding coils that enable it to send<br />

its code without interference from<br />

other boxes. <strong>The</strong> gongs also sound<br />

in accordance with the code, as do<br />

the other devices. Thus the code<br />

sounds on the gongs in remote fire<br />

stations eliminating the need for<br />

headquarters to relay the alarm to<br />

other stations. A break in the loop<br />

sounds a single blow on all devices<br />

to indicate a trouble condition. Any<br />

boxes placed into alarm during a<br />

loop break will signal their code via<br />

ground and the intact portion <strong>of</strong> the<br />

loop (if the main switchboard is so<br />

conditioned).<br />

<strong>The</strong> city Master Box is basically a<br />

street box equipped with a “trip”<br />

unit which is a sort <strong>of</strong> rotary solenoid.<br />

An extension is also placed<br />

on the box trip lever, and extra<br />

terminals are provided for the connections<br />

to the trip unit.<br />

<strong>The</strong>re are two types <strong>of</strong> trip units:<br />

the Shunt trip and the Local Energy<br />

trip. <strong>The</strong>ir appearances are similar.<br />

<strong>The</strong> trip unit is spring loaded and<br />

mechanically set by rotating the trip<br />

lever. This “cocks” the mechanism<br />

in much the same manner as a revolver,<br />

which is then set <strong>of</strong>f by pulling<br />

a trigger. <strong>The</strong> “trigger” in this<br />

case is energization <strong>of</strong> the magnetic<br />

trip coil. <strong>The</strong> spring lets go and the<br />

trip lever rotates rapidly, physically<br />

hitting the trip lever extension on<br />

the box mechanism, and thus starting<br />

the box.<br />

<strong>The</strong> shunt trips were the first to be<br />

invented and have become obsolescent.<br />

<strong>The</strong> coil in the shunt trip<br />

is actually placed in series with the<br />

city circuit. This coil is shunted out<br />

<strong>of</strong> the city circuit by normally closed<br />

contacts <strong>of</strong> the initiating device.<br />

When the initiating device goes into<br />

alarm, the contacts open and allow<br />

city current to flow through the<br />

trip coil, energizing it and starting<br />

the box.<br />

<strong>The</strong> National <strong>Fire</strong> Code, NFPA 72,<br />

limited the initiating devices ap-<br />

<strong>The</strong> shunt trip proved exceedingly<br />

popular about 0 to 7 years ago,<br />

when it was combined with a sprinkler<br />

waterflow switch to provide<br />

building protection. No control<br />

panel was required, and the city circuit<br />

furnished the operating current,<br />

having it’s own battery standby.<br />

<strong>The</strong>re were no evacuation signals,<br />

<strong>of</strong> course, but property protection<br />

was secured. A few panels were<br />

developed for use with a shunt<br />

trip but they usually had either<br />

unsupervised, or AC operated notification<br />

appliance circuits at best,<br />

and were quite primitive by today’s<br />

standards.<br />

<strong>The</strong> biggest drawbacks <strong>of</strong> the shunt<br />

trip are that a tripped shunt mechanism<br />

adds resistance to the city<br />

loop, and also wiring with city current<br />

will be on private property via<br />

the normally closed contacts <strong>of</strong> the<br />

waterflow switch. This means that<br />

city personnel can’t enter private<br />

property to correct any grounds<br />

on that portion <strong>of</strong> the circuit. This<br />

would usually irritate them to no<br />

end. <strong>The</strong> usual fix was to disconnect<br />

the box from the city circuit at<br />

the nearest pole! <strong>The</strong> shunt trip also<br />

contained extra Form “C” contacts<br />

that had to be connected to a reset<br />

supervisory panel, since there was<br />

no other way <strong>of</strong> knowing that the<br />

shunt trip is unset.<br />

To overcome these problems, the<br />

Local Energy trip was developed.<br />

Continued on page 34<br />

Page 2<br />

<strong>IMSA</strong> Journal


<strong>The</strong> ABC’s <strong>of</strong> <strong>Fire</strong> <strong>Alarm</strong> <strong>Systems</strong> – <strong>Part</strong> IX . . . Continued from page 32<br />

This trip unit also contains a coil,<br />

but the coil is connected to a dedicated,<br />

supervised city box circuit <strong>of</strong><br />

a fire alarm control panel listed for<br />

municipal connection. <strong>The</strong> trip coil<br />

acts as an end <strong>of</strong> line device, and<br />

only one trip unit may be connected<br />

to this circuit. <strong>The</strong> LE trip derives its<br />

name from the use <strong>of</strong> “local” energy<br />

from the protected premises control<br />

panel. When the panel goes into<br />

alarm, current is applied to the Local<br />

Energy trip unit, allowing it to rotate<br />

and set <strong>of</strong>f the box mechanism. One<br />

very important thing to remember is<br />

that there is no electrical connection<br />

between a LE trip and the city box<br />

mechanism or circuit. <strong>The</strong> connection<br />

is purely mechanical, as the LE<br />

trip lever spins and physically hits<br />

the box trip lever extension. Reset<br />

supervision is accomplished by<br />

means <strong>of</strong> a set <strong>of</strong> normally closed<br />

contacts in the trip unit in series with<br />

the coil. <strong>The</strong>se contacts are nicknamed<br />

“suicide contacts” and open<br />

when the unit is tripped. <strong>The</strong>y close<br />

when the trip is physically reset.<br />

Hence, when the unit is tripped, it<br />

will create a trouble condition on the<br />

city box circuit until reset. An interesting<br />

fact is that the LE trip unit is<br />

activated by applying current. <strong>The</strong><br />

unit is set to trip at approximately<br />

.2 0 milliamperes, voltage not being<br />

relevant. Hence, it can be tripped by<br />

a 12 or 2 VDC control panel, and is<br />

not involved in battery calculations,<br />

since the suicide contacts immediately<br />

disconnect it from the circuit.<br />

At one time, the trip was also rated<br />

for higher voltage AC use, requiring<br />

1/ amp. <strong>of</strong> AC current.<br />

ELECTRONIC MASTER BOXES<br />

Recently, thanks to the latest electronic<br />

technology, an electronic<br />

master box has been introduced.<br />

This unit connects in place <strong>of</strong> the<br />

old electromechanical unit, <strong>of</strong>ten<br />

in a similar housing. It contains<br />

electronically controlled municipal<br />

signaling contacts and features twowire<br />

initiating circuits with end <strong>of</strong><br />

line resistor that are activated by<br />

dry contacts on the control panel<br />

that short circuit the EOL resistor.<br />

<strong>The</strong> advantage <strong>of</strong> this type <strong>of</strong> box is<br />

that it can send multiple coded signals<br />

that may be used for signaling<br />

trouble, supervisory or zoned alarm<br />

signals, as desired. Its power is obtained<br />

from the protected premises<br />

control panel. <strong>The</strong> current electronic<br />

master box is Listed for use at a great<br />

range <strong>of</strong> temperature and humidity<br />

extremes.<br />

RADIO MASTER BOXES<br />

Keltron Radio Box<br />

SigComm Radio Box<br />

Radio master boxes are somewhat<br />

different from street boxes, since<br />

they are located where plenty <strong>of</strong><br />

power is available. <strong>The</strong>se master<br />

boxes might be located in ordinary<br />

looking sheet metal enclosures and<br />

need not be located outside the<br />

building, since they are not wired<br />

to a city circuit. <strong>The</strong>y somewhat<br />

resemble a conventional fire alarm<br />

control panel except the notification<br />

appliance circuits are replaced by a<br />

radio transmitter and antenna. This<br />

master box could contain any number<br />

<strong>of</strong> Class A or B initiating circuits,<br />

depending on the manufacturer,<br />

and, like the electronic master box,<br />

is capable <strong>of</strong> transmitting multiple<br />

coded signals.<br />

Connections to a radio master box<br />

are similar to those in the electronic<br />

master box. <strong>Alarm</strong>s are created by<br />

shorting the initiating circuit(s) by<br />

means <strong>of</strong> dry contacts in associated<br />

fire alarm control panels or directly<br />

from detectors or stations. <strong>The</strong> radio<br />

master boxes can also send different<br />

zone signals to the central console,<br />

giving the fire department valuable<br />

advance information regarding high<br />

rise fires, special hazards, special occupancies,<br />

etc. Trouble and Supervisory<br />

signals can also be transmitted.<br />

A central <strong>of</strong>fice for radio signaling is<br />

the same as for radio street boxes.<br />

Redundant receiving consoles are<br />

used for “fail-safe” reasons. Test<br />

signals are transmitted periodically<br />

for supervision. A missing test signal<br />

results in a “box missing” signal being<br />

displayed on the console.<br />

With the recent economy problems,<br />

some fire departments are preferring<br />

multiple or zoned alarm signals.<br />

Ordinarily a large response is made<br />

to an alarm <strong>of</strong> fire, <strong>of</strong>ten with ladder<br />

trucks, etc. only to find a small fire<br />

that activated a single heat detector.<br />

Meanwhile resources are limited<br />

in the event <strong>of</strong> a simultaneous or<br />

subsequent alarm that may require<br />

a maximum response. Thus activation<br />

<strong>of</strong> a single device such as a<br />

detector or pull station will allow<br />

the fire dept. to provide a minimum<br />

response and not tie up scarce resources<br />

that might be required to<br />

respond to other alarms. Multiple<br />

zones or devices in alarm would<br />

indicate a large, expanding fire allowing<br />

the fire department adequate<br />

reserves to provide a maximum<br />

response.<br />

Page <strong>IMSA</strong> Journal

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!