<strong>NX</strong>W REVERSIBLE CHILLER INSTALLATION MANUAL<br />

Field Connected Water Piping cont.<br />

Before final connection to the unit, the supply and return<br />

hose kits must be connected to each other, bypassing<br />

the unit, and the system flushed to remove dirt, piping<br />

chips and other foreign material. Normally, a combination<br />

balancing and close-off (ball) valve is installed at the return,<br />

and a rated gate or ball valve is installed at the supply. The<br />

return valve can be adjusted to obtain the proper water<br />

flow. The valves allow the unit to be removed for servicing.<br />

Earth Coupled Systems<br />

All supply and return water piping should be insulated to<br />

prevent excess condensation from forming on the water<br />

lines. Ensure pumping system is capable of providing<br />

adequate flow rate at the system pressure drop, 3.0 GPM<br />

per ton [0.054 LPS per kW] (source side) is recommended.<br />

Antifreeze in the loop is strongly recommended.<br />

The proper water flow must be delivered to each unit<br />

whenever the unit heats or cools. The proper flow rate<br />

cannot be accurately set without measuring the water<br />

pressure drop through the refrigerant-to-water heat<br />

exchanger. A 3 GPM flow rate per ton [0.054 LPS per kW]<br />

of cooling capacity (2.25 GPM per ton [0.0404 LPS per<br />

kW] minimum) is required.<br />

NOTE: The placement and connection of the water<br />

circulating pump(s) must be taken into consideration prior<br />

to designing the final water piping systems.<br />

Closed Loop Tower/Boiler Systems<br />

The water loop is usually maintained between 60°F [15.5°C]<br />

and 90°F [32.2°C] for proper heating and cooling operation.<br />

This is accomplished with a cooling tower and a boiler.<br />

To reject excess heat from the condenser water loop, the<br />

use of a closed-circuit evaporative cooler or an open type<br />

cooling tower with a secondary heat exchanger between<br />

the tower and the condenser water loop is recommended.<br />

If an open type cooling tower is used without a secondary<br />

heat exchanger, continuous chemical treatment and filtering<br />

of the water must be performed to ensure the water is free<br />

from damaging materials.<br />

CAUTION: Water piping exposed to outside<br />

temperature may be subject to freezing.<br />

Open Loop Well Water Systems<br />

<strong>Installation</strong> of an open loop system is not recommended<br />

without using a secondary heat exchanger unless water<br />

quality guidelines are met.<br />

11