<strong>NX</strong>W REVERSIBLE CHILLER INSTALLATION MANUAL<br />
Field Connected Water Piping cont.<br />
Before final connection to the unit, the supply and return<br />
hose kits must be connected to each other, bypassing<br />
the unit, and the system flushed to remove dirt, piping<br />
chips and other foreign material. Normally, a combination<br />
balancing and close-off (ball) valve is installed at the return,<br />
and a rated gate or ball valve is installed at the supply. The<br />
return valve can be adjusted to obtain the proper water<br />
flow. The valves allow the unit to be removed for servicing.<br />
Earth Coupled Systems<br />
All supply and return water piping should be insulated to<br />
prevent excess condensation from forming on the water<br />
lines. Ensure pumping system is capable of providing<br />
adequate flow rate at the system pressure drop, 3.0 GPM<br />
per ton [0.054 LPS per kW] (source side) is recommended.<br />
Antifreeze in the loop is strongly recommended.<br />
The proper water flow must be delivered to each unit<br />
whenever the unit heats or cools. The proper flow rate<br />
cannot be accurately set without measuring the water<br />
pressure drop through the refrigerant-to-water heat<br />
exchanger. A 3 GPM flow rate per ton [0.054 LPS per kW]<br />
of cooling capacity (2.25 GPM per ton [0.0404 LPS per<br />
kW] minimum) is required.<br />
NOTE: The placement and connection of the water<br />
circulating pump(s) must be taken into consideration prior<br />
to designing the final water piping systems.<br />
Closed Loop Tower/Boiler Systems<br />
The water loop is usually maintained between 60°F [15.5°C]<br />
and 90°F [32.2°C] for proper heating and cooling operation.<br />
This is accomplished with a cooling tower and a boiler.<br />
To reject excess heat from the condenser water loop, the<br />
use of a closed-circuit evaporative cooler or an open type<br />
cooling tower with a secondary heat exchanger between<br />
the tower and the condenser water loop is recommended.<br />
If an open type cooling tower is used without a secondary<br />
heat exchanger, continuous chemical treatment and filtering<br />
of the water must be performed to ensure the water is free<br />
from damaging materials.<br />
CAUTION: Water piping exposed to outside<br />
temperature may be subject to freezing.<br />
Open Loop Well Water Systems<br />
<strong>Installation</strong> of an open loop system is not recommended<br />
without using a secondary heat exchanger unless water<br />
quality guidelines are met.<br />
11