Selection table <strong>Sepam</strong> <strong>1000+</strong> <strong>series</strong> <strong>40</strong><br />

Functions<br />

Type of <strong>Sepam</strong><br />

Substation Transformer Motor<br />

Protection Code ANSI S<strong>40</strong> S41 S42 (1) T<strong>40</strong> (1) T42 (1) M41 (1)<br />

Phase overcurrent 50/51 4 4 4 4 4 4<br />

Earth fault, sensitive earth fault 50N/51N 4 4 4 4 4 4<br />

Breaker failure 50BF 1 (1) 1 (1) 1 1 1 1<br />

Negative sequence / unbalance 46 2 2 2 2 2 2<br />

Directional phase overcurrent 67 2 2<br />

Directional earth fault 67N/67NC 2 2 2 2<br />

Active overpower 32P 1 (1) 1 1<br />

Thermal overload 49RMS 2 2 2<br />

Phase undercurrent 37 1<br />

Locked rotor, excessive starting time 48/51LR 1<br />

Starts per hour 66 1<br />

Positive sequence undervoltage 27D/47 2<br />

Remanent undervoltage 27R 1<br />

Phase-to-phase undervoltage 27 (6) 2 2 2 2 2 2<br />

Phase-to-neutral undervoltage 27S (6) 2 2 2 2 2 2<br />

Phase-to-phase overvoltage 59 (6) 2 2 2 2 2 2<br />

Neutral voltage displacement 59N 2 2 2 2 2 2<br />

Negative sequence overvoltage 47 1 1 1 1 1 1<br />

Overfrequency 81H 2 2 2 2 2 2<br />

Underfrequency 81L 4 4 4 4 4 4<br />

Rate of change of frequency<br />

81R<br />

Recloser (4 cycles) 79 5 5 5<br />

Thermostat / Buchholz 5 5<br />

Temperature monitoring (with MET148, 2 set points per sensor) 38/49T 8/16 8/16 8/16<br />

Metering<br />

Phase current I1, I2, I3 RMS, Residual current Io # # # # # #<br />

Average current I1, I2, I3, Peak demand phase currents # # # # # #<br />

Voltage U21, U32, U13, V1, V2, V3, Residual voltage Vo # # # # # #<br />

Positive sequence voltage Vd / rotation direction # # # # # #<br />

Negative sequence voltage Vi # # # # # #<br />

Frequency # # # # # #<br />

Active and reactive power P and Q, Peak demand P and Q, Power factor # # # # # #<br />

Active and reactive energy (“Wh, “VARh) # # # # # #<br />

Temperature measurement 5 5 5<br />

Network and machine diagnosis<br />

Tripping current I1, I2, I3, Io # # # # # #<br />

Tripping context # # # # # #<br />

Unbalance ratio / negative sequence current Ii # # # # # #<br />

Phase angle ϕo, ϕ1, ϕ2, ϕ3 # # # # # #<br />

Disturbance recording # # # # # #<br />

Thermal capacity used # # #<br />

Remaining operating time before overload tripping # # #<br />

Waiting time after overload tripping # # #<br />

Running hours counter / operating time # # #<br />

Starting current and time #<br />

Start inhibit time delay, number of starts before inhibition #<br />

Switchgear diagnosis<br />

Cumulative breaking current # # # # # #<br />

Trip circuit supervision 5 5 5 5 5 5<br />

Number of operations, Operating time, Charging time 5 5 5 5 5 5<br />

CT / VT supervision # (1) # (1) # # # #<br />

Control and monitoring<br />

Circuit breaker / contactor control (2) # # # # # #<br />

Logic discrimination 5 5 5 5 5 5<br />

Switching of setting groups # # # # # #<br />

Program logic parameter setting (Boolean equation editor: AND, OR, …) # (1) # (1) # # # #<br />

Additional modules<br />

8 temperature sensor outputs - MET148 module 5 (4) 5 (4) 5 (4)<br />

1 low level analog output - MSA141 module 5 (1) 5 (1) 5 5 5 5<br />

Logic inputs and ouputs - MES108 module (4I/4O) or MES114 (10I/4O) 5 5 5 5 5 5<br />

RS485 interface - ACE 949-2 (2-wire) or ACE959 (4-wire) module 5 5 5 5 5 5<br />

# standard, 5Ãaccording to parameter setting and MES108, MES114 or MET148 input/output module options<br />

(1) available in 2002.<br />

(2) for shunt trip unit or undervoltage release coil.<br />

(3) exclusive choice between logic discrimination and switching from one 2-relay group of settings to another 2-relay group.<br />

(4) 2 modules possibles.<br />

(5) performs B20 type functions.<br />

(6) exclusive choice, phase-to-neutral or phase-to-phase voltage for each of the 2 relays.<br />