Connection schemes Sepam 1000+ series 40 - Trinet
Connection schemes Sepam 1000+ series 40 - Trinet
Connection schemes Sepam 1000+ series 40 - Trinet
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Selection table <strong>Sepam</strong> <strong>1000+</strong> <strong>series</strong> <strong>40</strong><br />
Functions<br />
Type of <strong>Sepam</strong><br />
Substation Transformer Motor<br />
Protection Code ANSI S<strong>40</strong> S41 S42 (1) T<strong>40</strong> (1) T42 (1) M41 (1)<br />
Phase overcurrent 50/51 4 4 4 4 4 4<br />
Earth fault, sensitive earth fault 50N/51N 4 4 4 4 4 4<br />
Breaker failure 50BF 1 (1) 1 (1) 1 1 1 1<br />
Negative sequence / unbalance 46 2 2 2 2 2 2<br />
Directional phase overcurrent 67 2 2<br />
Directional earth fault 67N/67NC 2 2 2 2<br />
Active overpower 32P 1 (1) 1 1<br />
Thermal overload 49RMS 2 2 2<br />
Phase undercurrent 37 1<br />
Locked rotor, excessive starting time 48/51LR 1<br />
Starts per hour 66 1<br />
Positive sequence undervoltage 27D/47 2<br />
Remanent undervoltage 27R 1<br />
Phase-to-phase undervoltage 27 (6) 2 2 2 2 2 2<br />
Phase-to-neutral undervoltage 27S (6) 2 2 2 2 2 2<br />
Phase-to-phase overvoltage 59 (6) 2 2 2 2 2 2<br />
Neutral voltage displacement 59N 2 2 2 2 2 2<br />
Negative sequence overvoltage 47 1 1 1 1 1 1<br />
Overfrequency 81H 2 2 2 2 2 2<br />
Underfrequency 81L 4 4 4 4 4 4<br />
Rate of change of frequency<br />
81R<br />
Recloser (4 cycles) 79 5 5 5<br />
Thermostat / Buchholz 5 5<br />
Temperature monitoring (with MET148, 2 set points per sensor) 38/49T 8/16 8/16 8/16<br />
Metering<br />
Phase current I1, I2, I3 RMS, Residual current Io # # # # # #<br />
Average current I1, I2, I3, Peak demand phase currents # # # # # #<br />
Voltage U21, U32, U13, V1, V2, V3, Residual voltage Vo # # # # # #<br />
Positive sequence voltage Vd / rotation direction # # # # # #<br />
Negative sequence voltage Vi # # # # # #<br />
Frequency # # # # # #<br />
Active and reactive power P and Q, Peak demand P and Q, Power factor # # # # # #<br />
Active and reactive energy (“Wh, “VARh) # # # # # #<br />
Temperature measurement 5 5 5<br />
Network and machine diagnosis<br />
Tripping current I1, I2, I3, Io # # # # # #<br />
Tripping context # # # # # #<br />
Unbalance ratio / negative sequence current Ii # # # # # #<br />
Phase angle ϕo, ϕ1, ϕ2, ϕ3 # # # # # #<br />
Disturbance recording # # # # # #<br />
Thermal capacity used # # #<br />
Remaining operating time before overload tripping # # #<br />
Waiting time after overload tripping # # #<br />
Running hours counter / operating time # # #<br />
Starting current and time #<br />
Start inhibit time delay, number of starts before inhibition #<br />
Switchgear diagnosis<br />
Cumulative breaking current # # # # # #<br />
Trip circuit supervision 5 5 5 5 5 5<br />
Number of operations, Operating time, Charging time 5 5 5 5 5 5<br />
CT / VT supervision # (1) # (1) # # # #<br />
Control and monitoring<br />
Circuit breaker / contactor control (2) # # # # # #<br />
Logic discrimination 5 5 5 5 5 5<br />
Switching of setting groups # # # # # #<br />
Program logic parameter setting (Boolean equation editor: AND, OR, …) # (1) # (1) # # # #<br />
Additional modules<br />
8 temperature sensor outputs - MET148 module 5 (4) 5 (4) 5 (4)<br />
1 low level analog output - MSA141 module 5 (1) 5 (1) 5 5 5 5<br />
Logic inputs and ouputs - MES108 module (4I/4O) or MES114 (10I/4O) 5 5 5 5 5 5<br />
RS485 interface - ACE 949-2 (2-wire) or ACE959 (4-wire) module 5 5 5 5 5 5<br />
# standard, 5Ãaccording to parameter setting and MES108, MES114 or MET148 input/output module options<br />
(1) available in 2002.<br />
(2) for shunt trip unit or undervoltage release coil.<br />
(3) exclusive choice between logic discrimination and switching from one 2-relay group of settings to another 2-relay group.<br />
(4) 2 modules possibles.<br />
(5) performs B20 type functions.<br />
(6) exclusive choice, phase-to-neutral or phase-to-phase voltage for each of the 2 relays.<br />
Schneider Electric<br />
9