MERLIN GERIN<br />

MERLIN GERIN<br />

MERLIN GERIN<br />

Communication<br />

Description and characteristics<br />

E79288<br />

<strong>Connection</strong> of the ACE949-2<br />

Interface for 2-wire RS 485 network<br />

RS 485<br />

network<br />

A<br />

ACE 949-2<br />

Implementation of the Modbus network<br />

A set of adapted accessories is used for fast, dependable implementation of the<br />

communication network from both the electrical and environmental (electromagnetic<br />

compatibility) viewpoints.<br />

V+<br />

V-<br />

L+<br />

L-<br />

E79287<br />

1<br />

2<br />

E79289<br />

RS 485<br />

network<br />

<strong>Connection</strong> of the ACE959<br />

Interface for 4-wire RS 485 network<br />

B<br />

L-<br />

L+<br />

V- CCA612<br />

V+<br />

to<br />

C<br />

<strong>Sepam</strong><br />

ACE959<br />

A<br />

(1)<br />

V-<br />

V+<br />

Rx+<br />

Rx-<br />

Tx+<br />

Tx-<br />

(1)<br />

V-<br />

V+<br />

Rx+<br />

Rx-<br />

Tx+<br />

Tx-<br />

V-<br />

V+<br />

(2)<br />

B<br />

D<br />

C<br />

CCA612<br />

to<br />

<strong>Sepam</strong><br />

➀ Network connection interface, to be supplied by 12 V DC or 24 V DC distributed<br />

power supply<br />

# ACE949-2 for 2-wire RS 485 network<br />

# or ACE959 for 4-wire RS 485 network.<br />

➁ CCA612 cord for connection of the connection interface to the C port of the<br />

<strong>Sepam</strong> base unit.<br />

➂ Interface for connection of the RS 485 network to the Modbus master, with<br />

distributed power supply to the ACE949-2 or ACE959 interfaces and polarization/<br />

termination of the communication link<br />

# ACE909-2, RS 485 / RS 232 converter<br />

# or ACE919CA (110 V AC or 220 V AC) RS 485/RS485 interface<br />

# or ACE919CC (24 V DC or 48 V DC) RS 485/RS 485 interface.<br />

➃ Modbus network cable<br />

# for 2-wire RS 485 network: two shielded twisted pairs<br />

(1 RS 485 pair, 1 pair for power supply)<br />

# for 4-wire RS 485 network: three shielded twisted pairs<br />

(2 RS 485 pairs, 1 pair for power supply)<br />

# with tinned copper braiding shielding, coverage: > 65 %<br />

# characteristic impedance: 120 Ω<br />

# gauge: AWG 24<br />

# resistance per unit length: < 100 Ω per km<br />

# capacitance between conductors: < 60 pF per m<br />

# capacitance between conductor and shielding: < 100 pF per m<br />

# maximum length: 1300 m.<br />

Example of standard cable (for 2-wire RS 485 network):<br />

# supplier: BELDEN reference: 9842<br />

# supplier: FILOTEX reference: FMA-2PS.<br />

High performance cable (for 2-wire RS 485 network):<br />

# supplier: FILECA reference : F2644-1 (cable distributed by Schneider Electric in<br />

60 m strand, reference CCR301).<br />

For more information, refer to the "<strong>Sepam</strong> – RS 485 network connection guide"<br />

PCRED399074EN.<br />

4<br />

3<br />

Rx+, Rx-: <strong>Sepam</strong> receiving (eq IN+, IN-)<br />

Tx+, Tx-: <strong>Sepam</strong> transmitting (eq OUT+, OUT-)<br />

(1) distributed power supply with separate wiring or included in<br />

the shielded cable (3 pairs).<br />

(2) terminal block for connection of the distributed power supply<br />

module.<br />

Schneider Electric<br />

29