9 Wiring Design• Restriction of control wiringBe sure to keep the rule of below tables about size and length of control wiring.Central controldeviceU1U3 U2U4Outdoor unitHeaderunitU3 U4U1 U2 U5 U6Super modular multi systemL4Table-1Header Follower Follower Followerunit unit unitunitU3 U4U3 U4U3 U4U3 U4U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6Header Followerunit unitU3 U4U3 U4U1 U2 U5 U6 U1 U2 U5 U6L1L5Table-1Table-2L2L3Indoor unitU1 U2ABU1 U2A BU1 U2A BU1 U2A BU1 U2ABU1 U2A BU1 U2A BU1 U2ABTable-3L7L6RemotecontrollerRemote controllerRemote controllerTable-1 Control wiring between indoor and outdoor units (L1, L2, L3),Central control wiring (L4)Wiring 2-core, non-polarityType Shield wireSize/Length 1.25 mm 2 : Up to 1000 m/2.0 mm 2 : Up to 2000 m (*1)Note (*1): Total length of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4)Table-2 Control wiring between outdoor units (L5)WiringTypeSize/Length2-core, non-polarityShield wire1.25 mm 2 to 2.0 mm 2 /Up to 100 m (L5)Table-3 Remote controller wiring (L6, L7)Wire 2-coreSize 0.5 mm 2 to 2.0 mm 2Length• Up to 500 m (L6 + L7)• Up 400 m in case of wireless remote controller in group control.• Up to 200 m total length of control wiring between indoor units (L6)• Group Operation through a Remote ControllerGroup operation of multiple indoor units (8 units) through a single remote controller switchIndoor unit No.1No.2No.3No.4No.7No.8AB AB AB AB AB ABRemotecontroller(A.B)9 -5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!