The DataSafe ® HX range of valve regulated lead acid batteries has been

specifically designed to provide the highest levels of reliability and security

for mission critical applications. DataSafe HX batteries are the ideal source

of power to protect vital Uninterruptible Power Supply (UPS) systems and

incorporate select design features that maximise reliability while ensuring

superior performance and an excellent service life.

The 12HX380 monobloc is the latest addition to the successful high power

density DataSafe HX battery range from EnerSys ® . Built on advanced

electrochemistry and backed by over 100 years experience in battery technology

and manufacture, the 12HX380 offers unrivalled performances for short

duration, high-rate discharge applications. In addition, its compact footprint has

been specially chosen to satisfy the requirements of the European market.

For high power density, performances and reliability, there is no substitute to

DataSafe HX batteries.

Features & Benefits

12V, 380 Watts per Cell (15min/1.67Vpc/20°C)

Specifically designed for high-rate discharge

applications

Conforms to industry standard dimensions

High volumetric energy density

Strong ABS plastic

Classified as “High Performance” (Eurobat)

Manufactured in EnerSys ISO 9001:2000 and

ISO 14001:2004 certified production facilities

RESERVE

POWER

INTRODUCTION TO

THE 12HX380

MONOBLOC

®


Construction

• High performance positive plates designed

for long life and efficient recharge

• Negative plates provide perfect balance

with positive plates to ensure optimum

recombination efficiency

• Separators in low resistance microporous

glass fibre. The electrolyte is absorbed

within this material, preventing acid spills

in case of accidental damage

• Electrolyte - high grade dilute sulphuric

acid absorbed into separator material

• Containers and lids in strong, highly

impact-resistant ABS plastic

• High integrity dual pillar seal design to

ensure leak-free operation

• Self regulating pressure relief valves -

prevent ingress of atmospheric oxygen

General Specifications

Watts/Cell

Constant Power Discharge Data (Watts per cell, 20°C)

EnerSys

P.O. Box 14145

Reading, PA 19612-4145

USA

Tel: +1-610-208-1991

+1-800-538-3627

Installation & Operation

• Monoblocs are designed for installation in

cabinets or on stands, close to the point of

use. A separate battery room is not

necessary

• It is recommended that DataSafe ®

12HX380 monoblocs are installed on their

base

• Recommended float charge voltage:

2.280Vpc at 20°C (68°F)

2.265Vpc at 25°C (77°F)

• Six months shelf life at 20°C

• Reduced maintenance:

no water addition required

• Operating temperature range:

-20°C to +50°C

EnerSys Europe

Zurich, Switzerland

Nominal Dimensions

Standby Time (Minutes)

Vpc 5 10 15 20 25 30 35 40 45 50 55 60

1.60 710 502 384 310 270 236 209 188 171 158 145 135

1.63 705 498 384 310 270 235 209 188 171 157 145 135

1.65 690 493 382 308 267 233 207 187 170 156 145 135

1.67 673 485 380 305 265 231 205 185 169 155 144 134

1.70 647 459 367 299 261 228 202 183 167 153 142 133

1.75 594 435 348 295 252 221 196 179 162 149 139 131

EnerSys Ltd.

Rake Lane,

Clifton Junction,

Swinton, Manchester

M27 8LR, UK

Tel: +44 (0)161 794 4611

Standards

• Designed to be compliant with the

requirements of international standard

IEC 60896-21/22

• Classified as “High Performance”

according to Eurobat Guide 1999

• Approved to be shipped as non-hazardous

cargo in accordance with the requirements

of IMDG (International Maritime code for

Dangerous Goods) and ICAO

(International Civil Aviation Organisation)

• Manufactured in EnerSys ® ISO 9001:2000

and ISO 14001:2004 certified production

facilities

15min rate Overall Typical Internal

Nominal

Voltage (V)

to 1.67Vpc

@ 20°C

Length

mm in

Width

mm in

Height

mm in

Weight

kg lbs

Short Circuit

Current (A)

Resistance

(mΩ)

Terminals

12HX380 12 380 299 11.8 175 6.89 225 8.86 35.0 77.2 2400 5.20 M6 F

Outline Drawings

225

(8.86)

175

(6.89)

EnerSys Asia

Guangdong, China

Fax: +1-610-372-8613 Tel: +86-755-2689 3639 Fax: +44 (0)161 727 3809

www.enersys-emea.com Publication

299

(11.8)

Contact:

© 2009 EnerSys. All rights reserved.

Trademarks and logos are the property of

EnerSys and its affiliates unless otherwise noted.

No. EN-HX380-SS-001 - March 2009 - Subject to revisions without prior notice. E.&O.E.

More magazines by this user
Similar magazines