<strong>SIMOVERT</strong> <strong>MV</strong>Engineering informationSystem componentsCircuit-breaker (continued)¦ Since many circuit-breakershave no mechanically leadingcontact, this contact may berealized in various ways:1.) If a digital overcurrent relayis used, all power-offconditions of the circuitbreaker(internal and external,e.g. Buchholz release,...) must be recordedand programmed ontwo release contacts withequivalent function. Onerelease contact is wired <strong>to</strong>the “leading contact” inpu<strong>to</strong>f the drive converter, thesecond <strong>to</strong> the undervoltagerelease of the circuitbreaker.2.) The voltage at the undervoltagecoil is checked bymeans of an op<strong>to</strong>coupler.The op<strong>to</strong>coupler output iswired <strong>to</strong> the “leading contact”input. Recommendedop<strong>to</strong>coupler: e.g.Phoenix ST-OE 3 withshort-circuit-proof 24 VDC output, the exact typeis determined by the auxiliaryvoltage of the switchingunit (input dataof the op<strong>to</strong>coupler,see Fig. 6/11).! 8 ! $ 8 ! # $ 0 )` CircuitbreakerON