6-14 General functions <strong>New</strong> <strong>Functions</strong> <strong>19VRS</strong><br />
6.7 Quick stop upon probe detection<br />
Condition<br />
Functional description<br />
The previously existing probe function was enhanced by the function<br />
"Quick stop upon probe detection". The drives are stopped immediately<br />
when approaching the probe to the measuring point. After completion of<br />
the measuring process, the drives are switched on again.<br />
This function is only possible for DIAX04 drives with firmware SSE03 or<br />
higher.<br />
In addition to the previous probe functionality, the function ‘Quick stop<br />
upon probe detection’ can be selected as of version SSE03.<br />
If the value "5“ is set for position value 1/2 with quick stop at positive edge<br />
in P-0-0200, signal selection probe 1, the drive automatically switches<br />
to "zeroing of nominal speed value" when the positive edge is detected.<br />
This drive state is maintained until the probe-1 enable in parameter S-0-<br />
0405, probe 1 enable is deleted by the control. Then, the drive uses<br />
again the nominal control values.<br />
DOK-<strong>MTC200</strong>-NEW*FUN*V19-AW02-EN-P