26.11.2012 Views

CQI-9 Special Process: Heat Treat System Assessment, 2 Edition ...

CQI-9 Special Process: Heat Treat System Assessment, 2 Edition ...

CQI-9 Special Process: Heat Treat System Assessment, 2 Edition ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>CQI</strong>-9 <strong>Special</strong> <strong>Process</strong>: <strong>Heat</strong> <strong>Treat</strong> <strong>System</strong> <strong>Assessment</strong>, 2 nd <strong>Edition</strong> Errata Sheet<br />

Page Item # Original Language (see BOLD) Corrected Version Language (see highlight)<br />

17 3.5.5 • Section 3.5.5 – Initial TUS<br />

– Minimum and maximum temperature<br />

ranges shall be tested per AMS 2750D.<br />

Exception: If the operating range of the<br />

Qualified Work Zone is equal to or less<br />

than 85 o C (153 o F) then only one<br />

temperature is required to be tested. The<br />

temperature shall be within the operating<br />

range of the Qualified Work Zone.<br />

17 3.5.6 • Section 3.5.6 – Periodic TUS (For <strong>CQI</strong>-9,<br />

a minimum of once per year periodic TUS<br />

is required)<br />

- Minimum and maximum temperature<br />

ranges shall be tested per AMS 2750D.<br />

Exception: If the operating range of the<br />

Qualified Work Zone is equal to or less than<br />

85 o C (153 o F) then only one temperature is<br />

required to be tested. The temperature<br />

shall be within the operating range of the<br />

Qualified Work Zone.<br />

43 A1.9 All hardness test equipment (for each scale<br />

used) shall be calibrated semi-annually<br />

minimum, and verified daily minimum per<br />

the applicable ASTM standard.<br />

48 B1.7<br />

54 C1.3<br />

58 D1.2<br />

All hardness test equipment (for each scale<br />

used) shall be calibrated semi-annually<br />

minimum, and verified daily minimum per<br />

the applicable ASTM standard.<br />

All hardness test equipment (for each scale<br />

used) shall be calibrated semi-annually<br />

minimum, and verified daily minimum per<br />

the applicable ASTM standard.<br />

All hardness test equipment (for each scale<br />

used) shall be calibrated semi-annually<br />

minimum, and verified daily minimum per<br />

the applicable ASTM standard.<br />

62 E1.8 All hardness test equipment (for each scale<br />

used) shall be calibrated semi-annually<br />

minimum, and verified daily minimum per<br />

the applicable ASTM standard.<br />

• Section 3.5.5 – Initial TUS<br />

– Minimum and maximum temperature ranges<br />

shall be tested per AMS 2750D. Exception: If the<br />

operating range of the Qualified Work Zone is<br />

equal to or less than 170 o C (306 o F) then only<br />

one temperature is required to be tested. The<br />

temperature shall be within the operating range<br />

of the Qualified Work Zone.<br />

• Section 3.5.6 – Periodic TUS (For <strong>CQI</strong>-9, a<br />

minimum of once per year periodic TUS is<br />

required)<br />

65 E4.2 Every 2 hours minimum Every 4 hours minimum<br />

– Minimum and maximum temperature ranges shall<br />

be tested per AMS 2750D. Exception: If the<br />

operating range of the Qualified Work Zone is equal<br />

to or less than 170 o C (306 o F) then only one<br />

temperature is required to be tested. The<br />

temperature shall be within the operating range of<br />

the Qualified Work Zone.<br />

All hardness test equipment (for each scale used)<br />

shall be calibrated annually minimum, and verified<br />

daily minimum per the applicable ASTM standard.<br />

All hardness test equipment (for each scale used)<br />

shall be calibrated annually minimum, and verified<br />

daily minimum per the applicable ASTM standard.<br />

All hardness test equipment (for each scale used)<br />

shall be calibrated annually minimum, and verified<br />

daily minimum per the applicable ASTM standard.<br />

All hardness test equipment (for each scale used)<br />

shall be calibrated annually minimum, and verified<br />

daily minimum per the applicable ASTM standard.<br />

All hardness test equipment (for each scale used)<br />

shall be calibrated annually minimum, and verified<br />

daily minimum per the applicable ASTM standard.


General Notes for AMS 2750D<br />

CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"<br />

PAGES 16 & 17, <strong>CQI</strong>-09 2 nd <strong>Edition</strong><br />

AMS 2750D is referenced in the Pyrometry Section (Section 2.0) of the <strong>Process</strong> Tables. <strong>Heat</strong> treat suppliers<br />

are not required to comply to all sections of AMS 2750D. <strong>Heat</strong> treat suppliers shall comply to the sections<br />

of AMS 2750D that are given below. These sections reference thermocouples, the calibration of<br />

thermocouples and instrumentation, and the procedure for conducting furnace temperature uniformity<br />

surveys (TUS).<br />

Thermocouples and Instrumentation<br />

- Section 3.1 – Temperature Sensors (Thermocouples)<br />

- Section 3.2 – Instrumentation - Note: Frequency reductions per AMS 2750D are not<br />

allowed by <strong>CQI</strong>-9<br />

Compliance to the following sections in 3.2, are not required by <strong>CQI</strong>-9<br />

Section Number Explanation<br />

3.2.5.1 & 2 Temperature controlling instruments purchased prior to 1 year after<br />

the release of AMS 2750D are exempt of 3.2.5.1 and 3.2.5.2.<br />

3.2.5.3.1 One point sensor input is acceptable.<br />

3.2.5.5 Sensitivity checks during calibration are not required.


CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"<br />

PAGES 16 & 17, <strong>CQI</strong>-09 2 nd <strong>Edition</strong><br />

<strong>System</strong> Accuracy Test (SAT) Procedure (Section 3.4)<br />

NOTE: Refer to AMS 2750D as directed<br />

- SAT shall be performed by one of the two methods listed below:<br />

1) Probe Method: The temperature indication of the furnace control instrument connected to the<br />

control sensor (CS) shall be within +/- 5C (or +/- 10F) of the corrected temperature<br />

indication of the test sensor (TS) on a test instrument. This test shall be performed monthly<br />

at a typical operating temperature utilizing the procedures detailed in AMS 2750D Section<br />

3.4.4, <strong>System</strong> Accuracy Test Procedure.<br />

SAT Frequency:<br />

o Equipment operating at or above 760C (1400F) shall be checked monthly.<br />

o Equipment operating below 760C (1400F) shall be checked quarterly.<br />

Example of Probe Method<br />

Lead Wire<br />

Test Instrument<br />

Chart Recorder<br />

B<br />

Note: The test sensor can be a<br />

resident thermocouple, refer to<br />

AMS 2750 D section 3.4.4.2.1<br />

Control Instrument<br />

EXAMPLE OF SYSTEM ACCURACY TEST (SAT)<br />

CONTROL<br />

INSTRUMENT<br />

TEMPERATURE<br />

INDICATION<br />

(A)<br />

900 o C<br />

(1652 o F)<br />

TEST<br />

INSTRUMENT<br />

TEMPERATURE<br />

INDICATION<br />

(B)<br />

901.5 o C<br />

(1655 o F)<br />

A<br />

TEST SENSOR<br />

CORRECTION<br />

FACTOR<br />

(C)<br />

-0.5 o C<br />

(-1.0 o F)<br />

1500<br />

1501<br />

Control Sensor<br />

Over Temp Test Sensor<br />

Protection Furnace Wall<br />

TEST<br />

INSTRUMENT<br />

CORRECTION<br />

FACTOR<br />

(D)<br />

+0.1 o C<br />

(+0.2 o F)<br />

Over-Temp Sensor<br />

Furnace<br />

Work Zone<br />

Part or Raw<br />

Material<br />

TRUE TEST<br />

TEMPERATURE<br />

(E)=(B)+(C)+(D)<br />

901.1 o C<br />

(1654.2 o F)<br />

SAT<br />

DIFFERENCE<br />

(A) – (E)<br />

-1.1 o C<br />

(-2.2 o F)


CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"<br />

PAGES 16 & 17, <strong>CQI</strong>-09 2 nd <strong>Edition</strong><br />

2) Comparative Method: The relationship between the control system (sensor, leadwire, control<br />

instrument) and any other permanently installed monitoring system such as over temperature<br />

control system (sensor, leadwire, over temp instrument) or a load monitoring system (sensor,<br />

leadwire, recording instrument) etc. at the time of the most recent conforming instrument<br />

calibration test shall be established. This established relationship shall not differ by more<br />

than +/-1C (or +/-2F) when checked weekly at a typical operating temperature.<br />

Example of Comparative<br />

Method<br />

Chart Recorder<br />

Control Instrument<br />

1500<br />

1501<br />

Control Sensor<br />

Over Temp<br />

Protection Furnace Wall<br />

Other permanently installed thermocouple<br />

(If utilized)<br />

Over-Temp Sensor<br />

Furnace<br />

Work Zone<br />

Part or Raw<br />

Material<br />

Note: It is strongly recommended that<br />

the comparative check be performed at or near the original temperature<br />

temperature<br />

- Any actions to correct a failing reading or validate a test result shall be documented.<br />

- Control Sensors (CS) failing to meet the requirements of SAT method 1 shall be changed. A<br />

new TUS is not required unless the position of the control sensor changes. If new<br />

thermocouple(s) are required in Test method 2, a new relationship must be established.<br />

- Thermocouple Replacement Schedule:<br />

o Base metal sensors (e.g. Type K, N, J, E) thermocouples shall be changed when needed<br />

or annually at a minimum for equipment operating at or above 760C (1400F).<br />

o Base metal sensors (e.g. Type K, N, J, E) thermocouples shall be changed when needed<br />

or every two years at a minimum for equipment operating below 760C (1400F).<br />

o Noble metal sensors (e.g. Type R and S) thermocouples shall be changed when needed<br />

or every two years at a minimum for equipment operating at or above 760C (1400F).<br />

o Note: A new TUS is not required for any thermocouple replacement unless the position<br />

of the control sensor(CS) is changed (CS)


CLARIFICATION TO "GENERAL NOTES FOR AMS 2750D"<br />

PAGES 16 & 17, <strong>CQI</strong>-09 2 nd <strong>Edition</strong><br />

Furnace Temperature Uniformity Survey (TUS)<br />

o Section 3.5.2 – Multiple Qualified Operating Temperature Ranges<br />

o Section 3.5.3 – Furnace Modifications<br />

o Section 3.5.4 – Furnace Repairs<br />

o Section 3.5.5 – Initial TUS<br />

� Minimum and maximum temperature ranges shall be tested per AMS 2750D.<br />

Exception: If the operating range of the Qualified Work Zone is equal to or less<br />

than 170 o C (306 o F) then only one temperature is required to be tested. The<br />

temperature shall be within the operating range of the Qualified Work Zone.<br />

o Section 3.5.6 – Periodic TUS (For <strong>CQI</strong>-9, a minimum of once per year periodic<br />

TUS is required)<br />

� Minimum and maximum temperature ranges shall be tested per AMS 2750D.<br />

Exception: If the operating range of the Qualified Work Zone is equal to or less<br />

than 170 o C (306 o F) then only one temperature is required to be tested. The<br />

temperature shall be within the operating range of the Qualified Work Zone.<br />

o Section 3.5.8 – Furnace Parameters During TUS<br />

o Section 3.5.9 – Furnace Temperature at Insertion of TUS Sensors (Thermocouples)<br />

o Section 3.5.10 – Load Condition<br />

o Section 3.5.11 – Furnace Atmosphere During TUS<br />

o Section 3.5.13 – Batch Furnaces, Salt Baths, Controlled Temperature Liquid Baths, and<br />

Fluidized Bed Furnaces EXCEPT:<br />

� 3.5.13.3.2: <strong>CQI</strong>-9 requires that data from the TUS sensors is automatically<br />

recorded.<br />

o Section 3.5.14 – Continuous and Semi-Continuous Furnaces<br />

o Section 3.5.15 – Alternative Testing Methods for Continuous and Semi-Continuous<br />

Furnaces or Furnaces with Retorts or Muffles<br />

o Section 3.5.16 – Temperature Uniformity Survey Sensor Failures<br />

o Section 3.5.18 – Relocation of Hot or Cold Recording Sensors for Class A or C<br />

Instrumentation<br />

o Section 3.5.20 – Temperature Uniformity Survey Instrumentation<br />

o Section 3.5.21 – Temperature Uniformity Survey Report

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!