MiniSteam Instruction Manual - HygroMatik
MiniSteam Instruction Manual - HygroMatik
MiniSteam Instruction Manual - HygroMatik
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Type Standard Main Power SupplyHY05 - HY451 x 400V/3Phase/NHY60 - HY116 2 x 400V/3Phase/NC01, C02 1 x 230/1Phase/NC06 - C581 x 400V/3Phase/NMS5, MS101 x 400V/3Phase/NMS51 x 230/1Phase/NDBE 21 x 230V/1PhaseDBE 6-451 x 400V/3Phase/NOther voltages are available on request.We recommend employing medium blow main fuses (applicableonly to the grid voltages above). See table below indicating maximumpower usage for each circuit protection:When using fault current circuit breakers please use a separateone for the humidifier.HyLine:Type Power Usage Circuit ProtectionHY05 5,4 A 3 x 6AHY08 8,7 A 3 x 10AHY13 14,1 A 3 x 16 AHY17 18,4 A 3 x 20 AHY23 24,9 A 3 x 35 AHY30 32,5 A 3 x 35 AHY45 48,8 A 3 x 63 AHY60 2 x 32,5 A 6 x 35 AHY90 2 x 48,8 A 6 x 63 AHY116 2 x 62,8 A 6 x 63 ACompactLine:Type Power Usage Circuit ProtectionC01 3,3A 1 x 6AC02 6,5A 1 x 10AC06 6,5 A 3 x 10 AC10 10,8 A 3 x 16 AC17 18,4 A 3 x 20 AC22 23,8 3 x 35 AC30 32,5 A 3 x 35 AC45 48,8 A 3 x 63 AC58 62,8 A 3 x 63 APage 24