Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
HIMax System 3 Product Description<br />
PTotal = nCPU*35 + nModules*20 + nFans*20 +Pexternal<br />
PTotal : Total required power<br />
nCPU: Number of processor modules in use<br />
NModule: Number of modules used without processor modules<br />
nFans: Number of fans in use. Each fan rack contains 2, 3 or 4 fans.<br />
PExternal: Power delivered from the output modules to the connected actuators.<br />
The following reference values are used in this formula:<br />
� Power consumption of a HIMax processor module: approx. 35 W<br />
� Power consumption of another HIMax module (except for processor module): approx.<br />
20 W<br />
� Power consumption of a fan: approx. 20 W<br />
� Power consumption of the actuators connected to and supplied by the output modules<br />
The power in watts required for one HIMax <strong>system</strong> is the result of this rough calculation.<br />
For an exact calculation of the power required, use the power consumption values of the<br />
individual modules and other consumer loads as specified in the corresponding data sheets<br />
or manuals.<br />
3.2 System Bus<br />
The HIMax <strong>system</strong> operates with two redundant <strong>system</strong> busses, <strong>system</strong> bus A and <strong>system</strong><br />
bus B.<br />
The <strong>system</strong> busses run within a base plate. The module is connected with the <strong>system</strong> busses<br />
by inserting it into the base plate. System busses A and B interconnect the modules via<br />
the <strong>system</strong> bus modules. The failure of one module does not affect the connections to remaining<br />
modules.<br />
The <strong>system</strong> bus connection to the modules are electrically isolated from the base plate. An<br />
insulation voltage of at least 1 500 V in ensured between the processor module and each<br />
I/O module.<br />
A <strong>system</strong> bus module is required to manage a <strong>system</strong> bus. The <strong>system</strong> bus module in slot<br />
1 operates <strong>system</strong> bus A and the <strong>system</strong> bus module in slot 2 operates <strong>system</strong> bus B.<br />
i<br />
If only one <strong>system</strong> bus module is inserted in the base plate, only one <strong>system</strong> bus is available!<br />
If both <strong>system</strong> bus modules are used to operate the HIMax <strong>system</strong>, communication runs on<br />
both <strong>system</strong> busses simultaneously.<br />
If the HIMax <strong>system</strong> is composed of various base plates, use Ethernet patch cables to interconnect<br />
the <strong>system</strong> busses on the base plates. Insert the cables in the RJ-45 socket located<br />
on the connector boards of the <strong>system</strong> bus modules. To do this, connect the UP<br />
socket of one base plate to the DOWN socket of the next base plate. System bus A and<br />
<strong>system</strong> bus B must not be crossed.<br />
Two adjacent base plates can be connected to one base plate.<br />
HI 801 001 E Rev. 3.00 Page 20 of 104