HIMax System 3 Product Description<br />

PTotal = nCPU*35 + nModules*20 + nFans*20 +Pexternal<br />

PTotal : Total required power<br />

nCPU: Number of processor modules in use<br />

NModule: Number of modules used without processor modules<br />

nFans: Number of fans in use. Each fan rack contains 2, 3 or 4 fans.<br />

PExternal: Power delivered from the output modules to the connected actuators.<br />

The following reference values are used in this formula:<br />

� Power consumption of a HIMax processor module: approx. 35 W<br />

� Power consumption of another HIMax module (except for processor module): approx.<br />

20 W<br />

� Power consumption of a fan: approx. 20 W<br />

� Power consumption of the actuators connected to and supplied by the output modules<br />

The power in watts required for one HIMax <strong>system</strong> is the result of this rough calculation.<br />

For an exact calculation of the power required, use the power consumption values of the<br />

individual modules and other consumer loads as specified in the corresponding data sheets<br />

or manuals.<br />

3.2 System Bus<br />

The HIMax <strong>system</strong> operates with two redundant <strong>system</strong> busses, <strong>system</strong> bus A and <strong>system</strong><br />

bus B.<br />

The <strong>system</strong> busses run within a base plate. The module is connected with the <strong>system</strong> busses<br />

by inserting it into the base plate. System busses A and B interconnect the modules via<br />

the <strong>system</strong> bus modules. The failure of one module does not affect the connections to remaining<br />

modules.<br />

The <strong>system</strong> bus connection to the modules are electrically isolated from the base plate. An<br />

insulation voltage of at least 1 500 V in ensured between the processor module and each<br />

I/O module.<br />

A <strong>system</strong> bus module is required to manage a <strong>system</strong> bus. The <strong>system</strong> bus module in slot<br />

1 operates <strong>system</strong> bus A and the <strong>system</strong> bus module in slot 2 operates <strong>system</strong> bus B.<br />

i<br />

If only one <strong>system</strong> bus module is inserted in the base plate, only one <strong>system</strong> bus is available!<br />

If both <strong>system</strong> bus modules are used to operate the HIMax <strong>system</strong>, communication runs on<br />

both <strong>system</strong> busses simultaneously.<br />

If the HIMax <strong>system</strong> is composed of various base plates, use Ethernet patch cables to interconnect<br />

the <strong>system</strong> busses on the base plates. Insert the cables in the RJ-45 socket located<br />

on the connector boards of the <strong>system</strong> bus modules. To do this, connect the UP<br />

socket of one base plate to the DOWN socket of the next base plate. System bus A and<br />

<strong>system</strong> bus B must not be crossed.<br />

Two adjacent base plates can be connected to one base plate.<br />